SB 988: Home inspectors.
- Session Year: 2017-2018
- House: Senate
- Latest Version Date: 2018-08-27
Existing law regulates a person who performs certain home inspections for a fee in connection with a transfer of real property. Existing law provides that it is the duty of a home inspector who is not licensed as a general contractor, structural pest control operator, or architect, or registered as a professional engineer to conduct a home inspection with the degree of care that a reasonably prudent home inspector would exercise.
Under this bill, if a home inspector observes any shade of yellow corrugated stainless steel tubing, as defined, during a home inspection, the home inspector would be required to include that observation and a specified notification in the home inspection report. The bill would require the degree of care of a reasonably prudent home inspector to be used in determining whether a home inspector has complied with that requirement.
Existing law regulates a person who performs certain home inspections for a fee in connection with a transfer of real property. Existing law provides that it is the duty of a home inspector who is not licensed as a general contractor, structural pest control operator, or architect, or registered as a professional engineer to conduct a home inspection with the degree of care that a reasonably prudent home inspector would exercise.
Under this bill, if a home inspector observes any shade of yellow corrugated stainless steel tubing, as defined, during a home inspection, the home inspector would be required to include that observation and a specified notification in the home inspection report. The bill would require the degree of care of a reasonably prudent home inspector to be used in determining whether a home inspector has complied with that requirement.
Existing law regulates a person who performs certain home inspections for a fee in connection with a transfer of real property. Existing law provides that it is the duty of a home inspector who is not licensed as a general contractor, structural pest control operator, or architect, or registered as a professional engineer to conduct a home inspection with the degree of care that a reasonably prudent home inspector would exercise.
Under this bill, if a home inspector observes any shade of yellow corrugated stainless steel tubing, as defined, during a home inspection, the home inspector would be required to include that observation and a specified notification in the home inspection report. The bill would require the degree of care of a reasonably prudent home inspector to be used in determining whether a home inspector has complied with that requirement.
Existing law regulates a person who performs certain home inspections for a fee in connection with a transfer of real property. Existing law provides that it is the duty of a home inspector who is not licensed as a general contractor, structural pest control operator, or architect, or registered as a professional engineer to conduct a home inspection with the degree of care that a reasonably prudent home inspector would exercise.
Under this bill, if a home inspector observes any shade of yellow corrugated stainless steel tubing, as defined, during a home inspection, the home inspector would be required to include that observation and a specified notification in the home inspection report.
This act may be cited as the Proper Bonding and Grounding of Corrugated Stainless Steel Tubing Act.
SEC. 2.Section 7196.2 is added to the Business and Professions Code, to read:7196.2.(a)If a home inspector observes any shade of yellow corrugated stainless steel tubing during a home inspection, the home inspector shall include that observation, and the following notification, in the home inspection report:
Manufacturers of yellow corrugated stainless steel tubing believe that yellow corrugated stainless steel tubing is safer if properly bonded and grounded as required by the manufacturers installation instructions. Proper bonding and grounding of this product can only be determined by a licensed electrical contractor.
(b)For purposes of this section, corrugated stainless steel tubing means a flexible, stainless steel pipe used to supply natural gas and propane in residential, commercial, and industrial structures.
(c)The degree of care specified in Section 7196 shall be used in determining whether a home inspector has complied with the requirements of subdivision (a).
This act may be cited as the Proper Bonding and Grounding of Corrugated Stainless Steel Tubing Act.
SEC. 2.Section 7196.2 is added to the Business and Professions Code, to read:7196.2.(a)If a home inspector observes any shade of yellow corrugated stainless steel tubing during a home inspection, the home inspector shall include that observation, and the following notification, in the home inspection report:
Manufacturers of yellow corrugated stainless steel tubing believe that yellow corrugated stainless steel tubing is safer if properly bonded and grounded as required by the manufacturers installation instructions. Proper bonding and grounding of this product can only be determined by a licensed electrical contractor.
(b)For purposes of this section, corrugated stainless steel tubing means a flexible, stainless steel pipe used to supply natural gas and propane in residential, commercial, and industrial structures.
(c)The degree of care specified in Section 7196 shall be used in determining whether a home inspector has complied with the requirements of subdivision (a).
This act may be cited as the Proper Bonding and Grounding of Corrugated Stainless Steel Tubing Act.
SEC. 2.Section 7196.2 is added to the Business and Professions Code, to read:7196.2.(a)If a home inspector observes any shade of yellow corrugated stainless steel tubing during a home inspection, the home inspector shall include that observation, and the following notification, in the home inspection report:
Manufacturers of yellow corrugated stainless steel tubing believe that yellow corrugated stainless steel tubing is safer if properly bonded and grounded as required by the manufacturers installation instructions. Proper bonding and grounding of this product can only be determined by a licensed electrical contractor.
(b)For purposes of this section, corrugated stainless steel tubing means a flexible, stainless steel pipe used to supply natural gas and propane in residential, commercial, and industrial structures.
(c)The degree of care specified in Section 7196 shall be used in determining whether a home inspector has complied with the requirements of subdivision (a).
This act may be cited as the Proper Bonding and Grounding of Corrugated Stainless Steel Tubing Act.
SEC. 2.Section 7196.2 is added to the Business and Professions Code, to read:7196.2.(a)If a home inspector observes any shade of yellow corrugated stainless steel tubing during a home inspection, the home inspector shall include that observation, and the following notification, in the home inspection report:
Manufacturers of yellow corrugated stainless steel tubing believe that yellow corrugated stainless steel tubing is safer if properly bonded and grounded as required by the manufacturers installation instructions. Proper bonding and grounding of this product can only be determined by a licensed electrical contractor.
(b)For purposes of this section, corrugated stainless steel tubing means a flexible, stainless steel pipe used to supply natural gas and propane in residential, commercial, and industrial structures.
|
Date
|
Status
|
|---|---|
| Aug 27, 2018 | Chaptered by Secretary of State. Chapter 225, Statutes of 2018. |
| Aug 27, 2018 | Approved by the Governor. |
| Aug 15, 2018 | Enrolled and presented to the Governor at 4 p.m. |
| Aug 9, 2018 | In Senate. Ordered to engrossing and enrolling. |
| Aug 9, 2018 | Read third time. Passed. Ordered to the Senate. |
| Jun 13, 2018 | Read second time. Ordered to third reading. |
| Jun 12, 2018 | From committee: Do pass. (Ayes 14. Noes 2.) (June 12). |
| May 17, 2018 | Referred to Com. on B. & P. |
| May 10, 2018 | In Assembly. Read first time. Held at Desk. |
| May 10, 2018 | Read third time. Passed. (Ayes 37. Noes 0.) Ordered to the Assembly. |
| May 7, 2018 | Read second time. Ordered to third reading. |
| May 3, 2018 | Read third time and amended. |
| Apr 3, 2018 | Read second time. Ordered to third reading. |
| Apr 2, 2018 | From committee: Do pass. (Ayes 9. Noes 0.) (April 2). |
| Mar 20, 2018 | Set for hearing April 2. |
| Feb 14, 2018 | Referred to Com. on B., P. & E.D. |
| Feb 6, 2018 | From printer. May be acted upon on or after March 8. |
| Feb 5, 2018 | Introduced. Read first time. To Com. on RLS. for assignment. To print. |
|
Date
|
Description
|
Location
|
Votes
|
|
|---|---|---|---|---|
| Aug 9, 2018 | SB 988 Galgiani Senate Third Reading By ARAMBULA | Assembly Floor |
Passed |
|
| Jun 12, 2018 | Do pass. | Assembly Standing Committee on Business and Professions |
Passed |
|
| May 10, 2018 | Senate 3rd Reading SB988 Galgiani | Senate Floor |
Passed |
|
| Apr 2, 2018 | Do pass | Senate Standing Committee on Business, Professions and Economic Development |
Passed |
This list shows positions taken on this bill by organizations on the date displayed, which is linked to the original source.
Positions by individuals are not included.
SENATE THIRD READING
STR Bill Id:SB 988
Author:(Galgiani)
As Amended Ver:May 3, 2018
Majority vote
SENATE VOTE: 38-0
Committee | Votes | Ayes | Noes |
Business & Professions | 14-2 | Low, Arambula, Baker, Chen, Chiu, Cunningham, Eggman, Gipson, Grayson, Irwin, McCarty, Medina, Mullin, Ting | Brough, Obernolte |
SUMMARY: Requires a home inspector to include a specified notice in a home inspection report if the inspector observes any shade of yellow corrugated stainless steel tubing during a home inspection. Specifically, the bill:
- Requires a home inspector that observes any shade of yellow corrugated stainless steel tubing during a home inspection to include that observation and the following notification in the home inspection report:
"Manufacturers of yellow corrugated stainless steel tubing believe that yellow corrugated stainless steel tubing is safer if properly bonded and grounded as required by the manufacturer’s installation instructions. Proper bonding and grounding of this product can only be determined by a licensed electrical contractor."
- Defines "corrugated stainless steel tubing" to mean a flexible, stainless steel pipe used to supply natural gas and propane in residential, commercial, and industrial structures.
- Requires that the degree of care specified in Business and Professions Code Section 7196 shall be used in determining whether a home inspector has complied with the requirements of the bill.
FISCAL EFFECT: This bill has been keyed non-fiscal by Legislative Counsel.
COMMENTS: Home inspection reports. Home inspectors are not licensed by the state. However, licensed professionals such as contractors or structural pest control operators can perform home inspections. Current law requires a home inspector to conduct a home inspection with the degree of care that a reasonably prudent home inspector would exercise. To the extent that a home inspector does not do so, he or she could face legal liability. Home inspections are not mandated during a property transaction, but they are common practice in the state.
Corrugated stainless steel tubing (CSST) is a flexible piping system used to supply natural gas or propone to appliances, such as water heaters. CCST has been used widely in residential appliance installation since 1990. There are multiple types of CCST. This bill is limited to yellow CCST. Beginning in 2006, all manufacturers' instructions for yellow CCST to connect to natural gas or propane lines have required yellow CCST to be directly bonded (i.e. securely connected) and grounded. In addition, beginning in 2009, the National Fuel Gas Code, the International Fuel Gas Code, and the Uniform Plumbing Code require direct bonding and grounding of yellow CSST. Because there was a gap between initial introduction of yellow CCST and the implementation of uniform manufacturers' instructions, many homes have yellow CCST that has not been completely bonded or grounded.
According to the National Association of Fire State Marshals, if lightning strikes on or near a structure, there is a risk that the electricity can travel through a structure's gas piping system and reach a CSST connection to an appliance in the structure. It has been shown that, under such circumstances, an electrical arc can occur, perforating yellow CCST and causing a fire. Proper bonding and grounding of yellow CCST mitigates this risk of fire.
Currently, the California Plumbing Code does not specifically require yellow CCST be bonded and grounded. However, the California Plumbing Code does require all plumbing systems (which would cover yellow CCST attached to appliances such as water heaters) to be installed in accordance with all manufacturer’s installation instructions. As noted above, all manufacturers currently require CCST to be bonded and grounded.
Notification in other states. Since 2013, the Oklahoma Construction Industries Board (pursuant to legislation in that state) has required all home inspectors to make a written notation if they see yellow corrugated stainless steel tubing during a home inspection.
The Oklahoma notification requirement was recommended as model legislation by the Council of State Governments in 2014. Subsequently, Texas, Virginia, and Maryland have adopted similar notification requirements.
Under the bill, home inspectors would be required to disclose in the home inspection report if yellow CSST was observed in the home and provide a specified disclosure. This may result in some, minor additional workload to home inspectors. However, because the bill includes the specific disclosure to be made by the home inspector, it is not expected that the additional workload on home inspectors would be significant.
To the extent that yellow CCST was present in a home and was not disclosed by a home inspector in the home inspection report, the home inspector could face professional liability. However, the bill specifies that the standard for the degree of care needed to meet the requirements of the bill is the same standard that applies to home inspections generally – the home inspector must exercise a degree of care that a reasonably prudent home inspector would exercise.
Analysis Prepared by: Brendan McCarthy / B. & P. / (916) 319-3301 FN: 0003481
Date of Hearing:
ASSEMBLY COMMITTEE ON BUSINESS AND PROFESSIONS
Evan Low, Chair
SBPCA Bill Id:
Author:() – As Ver:
SENATE VOTE:
SUBJECT:
SUMMARY: This bill requires a home inspector to include a specified notice in a home inspection report if the inspector observes any shade of yellow corrugated stainless steel tubing during a home inspection.
EXISTING LAW:
- Defines “home inspection” as a noninvasive, physical examination, performed for a fee in connection with a transfer of real property, of the mechanical, electrical, or plumbing systems or structural and essential elements of a residential dwelling of one to four units, designed to identify material defects in those systems, structures, and components. (Business and Professions Code Section 7195 (a)(1))
- In connection with a transfer of real property with a swimming pool or spa, requires an appropriate inspection to include a noninvasive physical examination of the pool or spa and dwelling for the purpose of identifying which, if any, of the seven drowning prevention safety features listed in Section 115922 of the Health and Safety Code are present. (Business and Professions Code Section 7195 (a)(2))
- Provides that a home inspection, if requested by the client, may include an inspection of energy efficiency features. (Business and Professions Code Section 7195(a)(3))
- Defines a “home inspection report” as a written report prepared for a fee and issued after a home inspection. The report shall clearly describe and identify the inspected systems, structures, or components of the dwelling, any material defects identified, and any recommendations regarding the conditions observed or recommendations for evaluation by appropriate persons. (Business and Professions Code Section 7195(c))
- Makes it the duty of a home inspector who is not licensed as a general contractor, structural pest control operator, or architect, or registered as a professional engineer to conduct a home inspection with the degree of care that a reasonably prudent home inspector would exercise. (Business and Professions Code Section 7196)
- Makes contractual provisions that purport to waive the duty owed pursuant to Business and Professions Code Section 7196 or limit the liability of the home inspector to the cost of the home inspection report contrary to public policy and invalid. (Business and Professions Code Section 7198)
- Provides that the time for commencement of a legal action for breach of duty arising from a home inspection report shall not exceed four years from the date of the inspection. (Business and Professions Code Section 7199)
THIS BILL:
- Titles the bill the “Proper Bonding and Grounding of Corrugated Stainless Steel Tubing Act”.
- Requires a home inspector that observes any shade of yellow corrugated stainless steel tubing during a home inspection to include that observation and the following notification in the home inspection report:
“Manufacturers of yellow corrugated stainless steel tubing believe that yellow corrugated stainless steel tubing is safer if properly bonded and grounded as required by the manufacturer’s installation instructions. Proper bonding and grounding of this product can only be determined by a licensed electrical contractor.”
- Defines “corrugated stainless steel tubing” to mean a flexible, stainless steel pipe used to supply natural gas and propane in residential, commercial, and industrial structures.
- Requires that the degree of care specified in Business and Professions Code Section 7196 shall be used in determining whether a home inspector has complied with the requirements of the bill.
FISCAL EFFECT: This bill has been keyed “non-fiscal” by Legislative Counsel.
COMMENTS:
Purpose. This bill is sponsored by the Air-Conditioning, Heating, and Refrigeration Institute.
According to the author, “The purpose of this legislation is to ensure prospective homeowners are fully informed regarding the current installation standards for yellow corrugated stainless steel tubing (CSST), if it is found to be present on a property.
Specifically, SB 988 will require all home inspectors to make a written notation if yellow CSST is seen during the course of their inspection. The notification shall state that only a licensed electrical contractor can determine if yellow CSST is property bonded and grounded per the current National Fuel Gas Code and as required by the manufacturer’s instructions.”
Background.
Home inspection reports. Home inspectors are not licensed by the state. However, licensed professionals such as contractors or structural pest control operators can perform home inspections. Current law requires a home inspector to conduct a home inspection with the degree of care that a reasonably prudent home inspector would exercise. To the extent that a home inspector does not do so, he or she could face legal liability. Home inspections are not mandated during a property transaction, but they are common practice in the state.
Corrugated stainless steel tubing (CSST) is a flexible piping system used to supply natural gas or propone to appliances, such as water heaters. CCST has been used widely in residential appliance installation since 1990. There are multiple types of CCST. This bill is limited to yellow CCST. Beginning in 2006, all manufacturers’ instructions for yellow CCST to connect to natural gas or propane lines have required yellow CCST to be directly bonded (i.e. securely connected) and grounded. In addition, beginning in 2009, the National Fuel Gas Code, the International Fuel Gas Code, and the Uniform Plumbing Code require direct bonding and grounding of yellow CSST. Because there was a gap between initial introduction of yellow CCST and the implementation of uniform manufacturers’ instructions, many homes have yellow CCST that has not been completely bonded or grounded.
According to the National Association of Fire State Marshals, if lightning strikes on or near a structure, there is a risk that the electricity can travel through a structure’s gas piping system and reach a CSST connection to an appliance in the structure. It has been shown that, under such circumstances, an electrical arc can occur, perforating yellow CCST and causing a fire. Proper bonding and grounding of yellow CCST mitigates this risk of fire.
Currently, the California Plumbing Code does not specifically require yellow CCST be bonded and grounded. However, the California Plumbing Code does require all plumbing systems (which would cover yellow CCST attached to appliances such as water heaters) to be installed in accordance with all manufacturer’s installation instructions. As noted above, all manufacturers currently require CCST to be bonded and grounded.
Notification in other states. Since 2013, the Oklahoma Construction Industries Board (pursuant to legislation in that state) has required all home inspectors to make a written notation if they see yellow corrugated stainless steel tubing during a home inspection.
The Oklahoma notification requirement was recommended as model legislation by the Council of State Governments in 2014. Subsequently, Texas, Virginia, and Maryland have adopted similar notification requirements.
Current Related Legislation. AB 2371 (Carillo) of the current legislative session requires an examination of an irrigation system for defects and inefficiencies in operation as part of a home inspection associated with a property transfer (amongst other provisions relating to water use efficiency). That bill is pending in the Senate.
Prior Related Legislation. SB 442 (Newman Chapter 670, Statutes of 2017) requires newly constructed or remodeled swimming pools at private single-family residences to incorporate at least two of seven specified drowning-prevention safety features. That bill also requires home inspections conducted as part of a property transfer with a pool to include an assessment of whether the pool is equipped with adequate safety features.
ARGUMENTS IN SUPPORT:
The Air-Conditioning, Heating, and Refrigeration Institute writes in support: “Direct or indirect lightning strikes on or near a structure have been shown to cause an electrical surge that can travel into the structure and have in some cases, where the CSST was not properly bonded, caused a perforation in the sidewall of the tubing as the energy arcs from one metallic system to another seeking ground. This arcing event may perforate the pressurized gas piping and can lead to a fire… SB 988 fulfills an important public safety need by ensuring proper notification.”
ARGUMENTS IN OPPOSITION:
The California Real Estate Inspection Association writes in opposition that the bill “inappropriately places into law a notification mandate on home inspectors that is the responsibility of the manufacturers…inappropriately places into law the mandate that a home inspector place in his or her report the “belief” of manufacturers that CSST tubing is “safer” if properly bonded and grounded…imposes on home inspectors an unreasonable exposure to new liability. It is foreseeable that any litigation regarding CCSTs in homes will name the home inspector.”
POLICY ISSUES:
Under the bill, home inspectors would be required to disclose in the home inspection report if yellow CSST was observed in the home and provide a specified disclosure. This may result in some, minor additional workload to home inspectors. However, because the bill includes the specific disclosure to be made by the home inspector, it is not expected that the additional workload on home inspectors would be significant.
To the extent that yellow CCST was present in a home and was not disclosed by a home inspector in the home inspection report, the home inspector could face professional liability. However, the bill specifies that the standard for the degree of care needed to meet the requirements of the bill is the same standard that applies to home inspections generally – the home inspector must exercise a degree of care that a reasonably prudent home inspector would exercise.
REGISTERED SUPPORT:
Air-Conditioning, Heating, and Refrigeration Institute (sponsor)
California State Association of Electrical Workers
California State Pipe Trades Council
California Professional Firefighters
Western State’s Council of Sheet Metal Workers
REGISTERED OPPOSITION:
The California Real Estate Inspection Association
Analysis Prepared by: Brendan McCarthy / B. & P. / (916) 319-3301
Office of Senate Floor Analyses (916) 651-1520 Fax: (916) 327-4478 | SB |
THIRD READING
Bill No: SB 988
Amended:
SENATE BUS., PROF. & ECON. DEV. COMMITTEE: 9-0, 4/2/18
AYES: Hill, Fuller, Dodd, Galgiani, Glazer, Hernandez, Newman, Pan, Wilk
SOURCE: Air Conditioning, Heating, and Refrigeration Institute
DIGEST:
This bill requires a home inspector to include a specified statement about the observation of yellow corrugated stainless steel tubing (CSST) in a home inspection report.
Senate Floor Amendments of 5/3/18 clarify that the current degree of care required by a home inspector, when conducting a home inspection, will be used in determining whether a home inspector complied with the observation and notification requirements.
Existing law:
- Defines a “home inspection” as a noninvasive, physical examination, performed for a fee in connection with a transfer, as specified, of real property, of the mechanical, electrical, or plumbing systems or the structural and essential components of a residential dwelling of one to four units designed to identify material defects in those systems, structures and components. (Business and Professions Code (BPC) § 7195(a)(1))
- Defines a “home inspection report” as a written report prepared for a fee and issued after a home inspection and clearly describes and identifies the inspected systems, structures, or components of the dwelling, any material defects identified, and any recommendations regarding the conditions observed or recommendations for evaluation by appropriate person. (BPC § 7195(c))
- Defines a “home inspector” as any individual who performs a home inspection.
This bill:
- Requires a home inspector to include the following notification about the observation of any shade of yellow CSST in the home inspection report:
“Manufacturers of yellow corrugated stainless steel tubing believe that yellow corrugated stainless steel tubing is safer if properly bonded and grounded as required by the manufacturer’s installation instruction. Proper bonding and grounding of this product can only be determined by a licensed electrical contractor.”
- Defines “yellow CSST” to mean a flexible, stainless steel pipe used to supply natural gas and propane in residential, commercial, and industrial structures.
- States that the current degree of care required by a home inspector will be used in determining whether a home inspector has complied with 1), above.
Background
Home Inspectors. Home inspectors are not licensed in California. Existing law establishes a standard of care for home inspectors, defines terms related to paid home inspections, mandates specified information be included in a home inspection report, and prohibits home inspections in which the inspector has a financial interest, among other things. A home inspection report is intended to clearly identify and describe the inspected systems, structures, or components of the dwelling, including any material defects identified and recommendations regarding the conditions observed, or any recommendations for evaluation by the appropriate persons.
BPC § 7195(a) requires a home inspector to include a noninvasive physical examination of the pool or spa and the dwelling to identify which, if any, of the safety features identified in the Health and Safety Code to prevent drownings including, mesh removable fences around the pool, door alarms, pool covers, among others are observed. In addition, the home inspector is required to identify in the home inspection report, which of those safety features are present, and specifically note if there are less than two safety features present. As currently drafted, this bill does not require a home inspector to inspect for yellow CSST. This bill specifies that the current degree of care required for a home inspector when conducting a home inspection will be used in determining whether a home inspector has complied with the provisions of this bill.
Yellow CSST. According to the yellow CSST safety campaign, yellow CSST is a flexible, stainless steel pipe used to supply natural gas and propane in residential, commercial and industrial structures. Standard CSST is coated with a yellow exterior plastic coating and has been used in homes and businesses since 1990. In awareness materials prepared by the Air Conditioning, Heating, and Refrigeration Institute, “direct or indirect lightening [sic] strikes on or near a structure have been shown to cause an electrical surge to travel into the structure and in some cases have caused a perforation in the sidewall of the tubing as the energy arcs from one metallic system to another seeking ground. This arcing can ignite the pressurized gas leaking from the perforation, in some cases may lead to fire…Independent research has confirmed proper bonding and grounding significantly reduces the risk of damage and fire from an indirect lightening [sic] strike.”
A coalition of groups including The National Association of State Fire Marshals, Air Conditioning, Heating, and Refrigeration Institute, American Public Gas Association, among others, have partnered in a yellow CSST safety campaign to raise awareness to homeowners on the importance of proper bonding of yellow CSST due to potential damage risks associated with lightning. Part of that safety campaign includes requiring a home inspector to provide a statement in the home inspection report pertaining to the presence of yellow CSST. This bill requires a home inspector to provide the following statement in a home inspection report: “Manufacturers of yellow corrugated stainless steel tubing believe that yellow corrugated stainless steel tubing is safer if properly bonded and grounded as required by the manufacturer’s installation instruction. Proper bonding and grounding of this product can only be determined by a licensed electrical contractor.” This bill does not mandate the home inspector inspect for yellow CSST; however, if they observe yellow CSST, they must provide the statement above in the home inspection report.
FISCAL EFFECT: Appropriation: Fiscal Com.: Local:
Air Conditioning, Heating, and Refrigeration Institute (source)
California Professional Firefighters
None received
ARGUMENTS IN SUPPORT: The Air Conditioning, Heating, and Refrigeration Institute writes in support, noting that the bill fulfills an important public safety need by ensuring proper notification.
The California Professional Firefighters writes in support, noting that it is important that homeowner understand the importance of proper bonding of yellow CSST.
5/9/18 13:51:05
**** END ****
Office of Senate Floor Analyses (916) 651-1520 Fax: (916) 327-4478 | SB |
THIRD READING
Bill No: SB 988
:
SENATE BUS., PROF. & ECON. DEV. COMMITTEE: 9-0, 4/2/18
AYES: Hill, Fuller, Dodd, Galgiani, Glazer, Hernandez, Newman, Pan, Wilk
SOURCE: Air Conditioning, Heating, and Refrigeration Institute
DIGEST:
This bill requires a home inspector to include a specified statement about the observation of yellow corrugated stainless steel tubing (CSST) in a home inspection report.
Existing law:
- Defines a “home inspection” as a noninvasive, physical examination, performed for a fee in connection with a transfer, as specified, of real property, of the mechanical, electrical, or plumbing systems or the structural and essential components of a residential dwelling of one to four units designed to identify material defects in those systems, structures and components. (Business and Professions Code (BPC) § 7195(a)(1))
- Defines a “home inspection report” as a written report prepared for a fee and issued after a home inspection and clearly describes and identifies the inspected systems, structures, or components of the dwelling, any material defects identified, and any recommendations regarding the conditions observed or recommendations for evaluation by appropriate person. (BPC § 7195(c))
- Defines a “home inspector” as any individual who performs a home inspection.
This bill:
- Requires a home inspector to include the following notification about the observation of any shade of yellow CSST in the home inspection report:
“Manufacturers of yellow corrugated stainless steel tubing believe that yellow corrugated stainless steel tubing is safer if properly bonded and grounded as required by the manufacturer’s installation instruction. Proper bonding and grounding of this product can only be determined by a licensed electrical contractor.”
- Defines “yellow CSST” to mean a flexible, stainless steel pipe used to supply natural gas and propane in residential, commercial, and industrial structures.
Background
Home Inspectors. Home inspectors are not licensed in California. Existing law establishes a standard of care for home inspectors, defines terms related to paid home inspections, mandates specified information be included in a home inspection report, and prohibits home inspections in which the inspector has a financial interest, among other things. A home inspection report is intended to clearly identify and describe the inspected systems, structures, or components of the dwelling, including any material defects identified and recommendations regarding the conditions observed, or any recommendations for evaluation by the appropriate persons.
BPC § 7195(a) requires a home inspector to include a noninvasive physical examination of the pool or spa and the dwelling to identify which, if any, of the safety features identified in the Health and Safety Code to prevent drownings including, mesh removable fences around the pool, door alarms, pool covers, among others are observed. In addition, the home inspector is required to identify in the home inspection report, which of those safety features are present, and specifically note if there are less than two safety features present. As currently drafted, this bill does not require a home inspector to inspect for yellow CSST.
Yellow CSST. According to the yellow CSST safety campaign, yellow CSST is a flexible, stainless steel pipe used to supply natural gas and propane in residential, commercial and industrial structures. Standard CSST is coated with a yellow exterior plastic coating and has been used in homes and businesses since 1990. In awareness materials prepared by the Air Conditioning, Heating, and Refrigeration Institute, “direct or indirect lightening [sic] strikes on or near a structure have been shown to cause an electrical surge to travel into the structure and in some cases have caused a perforation in the sidewall of the tubing as the energy arcs from one metallic system to another seeking ground. This arcing can ignite the pressurized gas leaking from the perforation, in some cases may lead to fire…Independent research has confirmed proper bonding and grounding significantly reduces the risk of damage and fire from an indirect lightening [sic] strike.”
A coalition of groups including The National Association of State Fire Marshals, Air Conditioning, Heating, and Refrigeration Institute, American Public Gas Association, among others, have partnered in a yellow CSST safety campaign to raise awareness to homeowners on the importance of proper bonding of yellow CSST due to potential damage risks associated with lightning. Part of that safety campaign includes requiring a home inspector to provide a statement in the home inspection report pertaining to the presence of yellow CSST. This bill requires a home inspector to provide the following statement in a home inspection report: “Manufacturers of yellow corrugated stainless steel tubing believe that yellow corrugated stainless steel tubing is safer if properly bonded and grounded as required by the manufacturer’s installation instruction. Proper bonding and grounding of this product can only be determined by a licensed electrical contractor.” This bill does not mandate the home inspector inspect for yellow CSST; however, if they observe yellow CSST, they must provide the statement above in the home inspection report.
FISCAL EFFECT: Appropriation: Fiscal Com.: Local:
Air Conditioning, Heating, and Refrigeration Institute (source)
None received
ARGUMENTS IN SUPPORT: The Air Conditioning, Heating, and Refrigeration Institute writes in support, noting that the bill fulfills an important public safety need by ensuring proper notification.
4/25/18 16:40:06
**** END ****
SENATE COMMITTEE ON
BUSINESS, PROFESSIONS AND ECONOMIC DEVELOPMENT
Senator Jerry Hill, Chair
2017 - 2018 Regular
Bill No: Hearing Date: April 2, 2018
Author: | |||
Version: | February 5, 2018 | ||
Urgency: | No | Fiscal: | No |
Consultant: | Elissa Silva | ||
Subject:
SUMMARY:
Requires a home inspector to include a specified statement about the observation of yellow corrugated stainless steel tubing (CSST) in a home inspection report.
Existing law:
- Defines a “home inspection” as a noninvasive, physical examination, performed for a fee in connection with a transfer, as specified, of real property, of the mechanical, electrical, or plumbing systems or the structural and essential components of a residential dwelling of one to four units designed to identify material defects in those systems, structures and components. (Business and Professions Code (BPC) § 7195(a)(1))
- Permits a home inspection to include an inspection of energy efficiency items, as specified, if requested by the client. (BPC § 7195(a)(3))
- Defines a “home inspection report” as a written report prepared for a fee and issued after a home inspection and clearly describes and identifies the inspected systems, structures, or components of the dwelling, any material defects identified, and any recommendations regarding the conditions observed or recommendations for evaluation by appropriate person. (BPC § 7195(c))
- Defines a “home inspector” as any individual who performs a home inspection. (BPC § 7195(d))
- States that it is the duty of a home inspector who is not licensed as a general contractor, structural pest control operator, or architect, or registered as a professional engineer to conduct a home inspection with the degree of care that a reasonably prudent home inspector would exercise. (BPC § 7196)
This bill:
- Requires a home inspector to include the following notification about the observation of any shade of yellow CSST in the home inspection report:
“manufacturers of yellow CSST believe that yellow CSST is safer if properly bonded and grounded as required by the manufacturer’s installation instruction. Proper bonding and grounding of this product can only be determined by a licensed electrical contractor.”
- Defines “yellow CSST” to mean a flexible, stainless steel pipe used to supply natural gas and propane in residential, commercial, and industrial structures.
FISCAL EFFECT:
None. This bill is keyed “non-fiscal” by the Legislative Counsel.
COMMENTS:
- Purpose. This bill is sponsored by the, Air Conditioning, Heating and Refrigeration Institute. According to the Author, “Unfortunately, over half of yellow CSST installations in the U.S. were completed prior to the direct-bonding safety update to manufacturers’ instructions and national fuel gas codes. Installations prior to the code update were not properly bonded, which can have serious consequence when lightning strikes nearby…The National Association of State Fire Marshalls (NASF) has partnered with the CSST manufacturers to launch a yellow CSST safety campaign. [This bill] is part of this nationwide safety campaign to bring awareness to homeowners on the importance of proper bonding of yellow CSST and the potential risks if it is not properly bonded. It is unclear how many homes in California were installed with yellow CSST prior to the national code update. For this reason, it is critical that property owners are informed.”
- Home Inspectors. Home inspectors are not licensed in California. However, home inspectors can be licensed in other professional capacities such as contractors, architects, engineers, and structural pest control operators. Existing law establishes a standard of care for home inspectors, defines terms related to paid home inspections, mandates specified information be included in a home inspection report, and prohibits home inspections in which the inspector has a financial interest, among other things. There are private, voluntary certification programs for home inspectors; however, home inspectors are not required to be certified, only comply with specified industry standards.
A home inspection report is intended to clearly identify and describe the inspected systems, structures, or components of the dwelling, including any material defects identified and recommendations regarding the conditions observed, or any recommendations for evaluation by the appropriate persons. There is no requirement for purchasers of real property (one to four unit dwellings) to obtain a home inspection; however, it is typically recommended.
BPC § 7195(a)) requires a home inspector to include a noninvasive physical examination of the pool or spa and the dwelling to identify which, if any, of the safety features identified in the health and safety code to prevent drownings including, mesh removable fences around the pool, door alarms, pool covers, among others are observed. In addition, the home inspector is required to identify in the home inspection report, which of those safety features are present, and specifically note if there are less than two safety features present. This bill would require, in addition to including information on a home inspection report pertaining to pool and spa safety features, a home inspector would be required to provide a notification about the observation of yellow CSST in the home inspection report, only if it is observed by the home inspector. As currently drafted, this bill does not require a home inspector to inspect for yellow CSST.
- Yellow Corrugated Stainless Steel Tubing (CSST). According to the yellow CSST safety campaign, yellow CSST is a flexible, stainless steel pipe used to supply natural gas and propane in residential, commercial and industrial structures. Standard CSST is coated with a yellow exterior plastic coating and has been used in homes and businesses since 1990. The Air-Conditioning, Heating, & Refrigeration Institute estimates that yellow CSST has been installed in over 6 million homes in the United States since the early 1990’s. The safety of yellow CSST became an issue in the early 2000’s related to lightening strikes resulting in homes fires. In awareness materials prepared by the Air-Conditioning, Heating, & Refrigeration Institute, “direct or indirect lightening strikes on or near a structure have been shown to cause an electrical surge to travel into the structure and in some cases have caused a perforation in the sidewall of the tubing as the energy arcs from one metallic system to another seeking ground. This arcing can ignite the pressurized gas leaking from the perforation, in some cases may lead to fire…Independent research has confirmed proper bonding and grounding significantly reduces the risk of damage and fire from an indirect lightening strike.”
A coalition of groups including The National Association of State Fire Marshals, Air-Conditioning, Heating & Refrigeration Institute, American Public Gas Association, among others, have partnered in a yellow CSST safety campaign to raise awareness to homeowners on the importance of proper bonding of yellow CSST due to potential damage risks associated with lightning. Part of that safety campaign includes requiring a home inspector to provide a statement in the home inspection report pertaining to the presence of yellow CSST. This bill would require a home inspector to provide the following statement in a home inspection report: “manufacturers of yellow CSST believe that yellow CSST is safer if properly bonded and grounded as required by the manufacturer’s installation instruction. Proper bonding and grounding of this product can only be determined by a licensed electrical contractor.” This bill does not mandate the home inspector inspect for yellow CSST; however, if they do, they must provide the statement above in the home inspection report.
- Arguments in Support. The Air Conditioning, Heating, & Refrigeration Institute writes in support, noting that the bill fulfills an important public safety need by ensuring proper notification.
- Prior Related Legislation. SB 442 (Newman, Chapter 670, Statutes of 2017), requires newly constructed or remodeled swimming pools or spas at private single-family residences to incorporate at least two of seven specified drowning prevention safety features. It also requires home inspections conducted as part of the transfer of a property with a pool or spa to include an assessment of whether the pool is equipped with adequate drowning prevention features.
AB 1357 (Chu, Chapter 508, Statutes of 2017) exempts a licensed roofing contractor from the unfair business practice restrictions for home inspections if specified conditions are met.
AB 470 (Chu) of 2016 would have required newly constructed or remodeled swimming pools or spas at private single-family residences to incorporate at least two of seven specified drowning prevention safety features. It also would have required home inspections conducted as part of the transfer of a property with a pool or spa to include an assessment of whether the pool is equipped with adequate drowning prevention features. (Status: This bill was vetoed by the Governor who indicated in his veto message that “Nothing prevents a homeowner from adding as many additional safety features as they desire to their own pool. The choice on how to protect children is best left to the parents”.)
AB 1118 (Hayashi) of 2009 would have established a certification program for home inspectors and required the Office of Professional Examination Services under the Department of Consumer Affairs to create the home inspector examination, as specified. (Status: This bill died in the Assembly Committee on Business and Professions)
AB 2142 (Houston of 2004) would have authorizes home inspectors who are also licensed contractors or licensed structural pest control operators to make the repairs recommended by them in their own inspection reports, as long as specific disclosures are made and consumers are provided flexibility in choosing a contractor. (Status: This bill failed passage in the Assembly Committee on Business and Professions)
SUPPORT AND OPPOSITION:
Support:
Air-conditioning, Heating, & Refrigeration Institute (Sponsor)
Opposition:
None on file as of March 26, 2018.