SB 1099: Emergency backup generators: critical facilities: exemptions.
- Session Year: 2019-2020
- House: Senate
- Latest Version Date: 2020-07-27
|
Date
|
Status
|
|---|---|
| Jul 27, 2020 | From committee with author's amendments. Read second time and amended. Re-referred to Com. on NAT. RES. |
| Jun 29, 2020 | Referred to Com. on NAT. RES. |
| Jun 25, 2020 | In Assembly. Read first time. Held at Desk. |
| Jun 25, 2020 | Read third time. Passed. (Ayes 37. Noes 0. Page 3838.) Ordered to the Assembly. |
| Jun 9, 2020 | Read second time. Ordered to third reading. |
| Jun 8, 2020 | From committee: Be ordered to second reading pursuant to Senate Rule 28.8. |
| Jun 4, 2020 | Set for hearing June 9. |
| Jun 2, 2020 | Read second time and amended. Re-referred to Com. on APPR. |
| May 29, 2020 | From committee: Do pass as amended and re-refer to Com. on APPR. (Ayes 4. Noes 1. Page 3622.) (May 29). |
| May 22, 2020 | Set for hearing May 29. |
| Mar 18, 2020 | April 1 hearing postponed by committee. |
| Mar 10, 2020 | Set for hearing April 1. |
| Feb 27, 2020 | Referred to Com. on EQ. |
| Feb 20, 2020 | From printer. May be acted upon on or after March 21. |
| Feb 19, 2020 | Introduced. Read first time. To Com. on RLS. for assignment. To print. |
|
Date
|
Description
|
Location
|
Votes
|
|
|---|---|---|---|---|
| Jun 25, 2020 | Senate 3rd Reading SB1099 Dodd et al. | Senate Floor |
Passed |
|
| May 29, 2020 | Do pass as amended, but first amend, and re-refer to the Committee on [Appropriations] | Senate Standing Committee on Environmental Quality |
Passed |
This list shows positions taken on this bill by organizations on the date displayed, which is linked to the original source.
Positions by individuals are not included.
SENATE RULES COMMITTEE Office of Senate Floor Analyses (916) 651-1520 Fax: (916) 327-4478 | SB 1099 |
THIRD READING
Bill No: SB 1099
Author: Dodd (D) and Glazer (D), et al.
Amended: 6/2/20
Vote: 21
SENATE ENVIRONMENTAL QUALITY COMMITTEE: 4-1, 5/29/20
AYES: Allen, Hertzberg, Hill, McGuire
NOES: Dahle
NO VOTE RECORDED: Bates, Wieckowski
SENATE APPROPRIATIONS COMMITTEE: Senate Rule 28.8
SUBJECT: Emergency backup generators: critical facilities: exemption
SOURCE: Author
DIGEST:
This bill requires air districts to develop stipulations for an order of abatement that would allow permitted facilities to use backup generators (BUGs) in exceedance of hour limits, should they enter into a stipulated order of abatement (SOA) with the local air district. This bill further dictates some of the terms of that SOA, including reporting of use, and a schedule for replacing older polluting generators with the cleanest, feasible, applicable technology that is economically feasible.
ANALYSIS:
Existing federal law:
- Sets, through the Federal Clean Air Act (FCAA) and its implementing regulations, National Ambient Air Quality Standards (NAAQS) for six criteria pollutants and requires states to prepare, submit, and adopt a State Implementation Plan (SIP) to limit air pollution and attain federal standards. (42 U.S.C. §7401 et seq.)
Existing state law:
- Establishes the Air Resources Board (ARB) as the air pollution control agency in California and requires ARB, among other things, to coordinate, encourage, and review the efforts of all levels of government as they affect air quality. (Health and Safety Code (HSC) §39500 et seq.)
- Creates the 35 air pollution control and air quality management districts (air districts) to be responsible for regional air quality planning, monitoring, and stationary source and facility permitting. (HSC §40000 et seq.)
- Defines “emergency use” as providing electrical power during specified events, including the loss of normal electrical power for reasons beyond the control of the operator. (Title 17 of the California Code of Regulations §93115.4)
- Allows an air district board or air pollution control officer to, after notice and hearing, order an entity to abate its emissions from a given technology, and such an order may contain stipulations regarding that abatement. (HSC § 42451)
This bill:
- Defines pertinent terms for Section 42451.1 of the Health and Safety Code.
- Makes findings and declarations regarding:
- The impacts on humans and the environment of increasing wildfires.
- How Public Safety Power Shutoffs (PSPS) events create challenges for water agencies moving and delivering water.
- The necessity for action to reduce impacts from different events on different facilities, and that that action provide better access to alternative power sources for the purposes of water delivery and wildfire response.
- Requires air districts to develop stipulations for an SOA that allows the operator of a critical facility, as defined, to use a permitted emergency BUG in exceedance of that permit’s runtime and testing and maintenance limits if both of the following are met:
- The operation of the BUG occurs as the result of a deenergization event or other loss of power.
- The testing and maintenance for that emergency BUG is in accordance with the National Fire Protection Association Standard 110 for Emergency and Standby Power Systems.
- Mandates some of the conditions of a mutually agreed-upon SOA to permit BUG use in exceedance of runtime limits, including:
- A schedule for the replacement of Tier 1 or lower emergency BUG with the cleanest, feasible, and applicable technology.
- Reporting requirements about the use of the BUG due to PSPS or testing.
- Logistical considerations for duration of the SOA, and approval by the local air district hearing board.
Background
- Backup generators. In order to mitigate the damage of power loss, many of these critical service providers may rely on BUGs to replace lost grid power. Additionally, many businesses may use BUGs to avoid catastrophic system disruptions and to minimize economic disruption that could result from prolonged power outages. However, this use of BUGs may result in air quality and public health impacts.
According to estimates from ARB, nearly 125,000 BUGs were used in California during PSPS events in October 2019. Assuming an average of 50 hours of operation each, those generators released a cumulative total of 166.4 tons of nitrogen oxides (NOx), 19.4 tons of particulate matter (PM), and 8.9 tons of diesel PM. The diesel PM release was roughly equivalent to 29,000 additional heavy-duty diesel trucks being used for the month.
- Health impacts of diesel emissions. In 1998, California identified diesel PM as a toxic air contaminant based on its potential to cause cancer, premature death, and other health problems. Numerous studies have documented a range of adverse health impacts from long-term exposure to diesel pollution, including increased risk for respiratory and cardiovascular illnesses, such as asthma, heart attacks and lung cancer, stunted lung growth in children, adverse birth outcomes, more frequent emergency room visits, and higher mortality rates.
- Air district permitting rules. Each of the state’s 35 air districts adopts their own sets of regulations and rules tailored to the sources and air quality challenges of its region and overseen by ARB. Ultimately, these actions are designed to achieve NAAQS set by the FCAA. Collectively, these strategies (i.e. emission standards, fuel regulations, emission limits, etc.) are included in the SIP. ARB is the lead agency in California for achieving the emission reductions goals and timelines described in the SIP. The 35 air districts, as well as other agencies, prepare SIP elements to be reviewed and approved by ARB before being integrated into the SIP.
With few exceptions, anyone constructing or operating a facility that emits air pollutants must obtain an appropriate permit from the local air district. Each air district establishes its own fee schedule, and may maintain different requirements. An air district uses these permits to assess the air pollution impacts of stationary sources within its jurisdiction, and it may require additional standards or control technologies be used to align permitted entities’ emissions with the SIP.
- Using and maintaining BUGs in California. Because of the air quality and public health impacts of diesel emissions, ARB and air districts have adopted rules and regulations that affect the amount of time BUGs can be used. The amount of time permitted for routine maintenance is dictated by ARB’s Airborne Toxic Control Measure for Stationary Diesel Engines. This regulation—and the implementing rules from air districts—dictates that older, more-polluting engines be tested for less time to control cumulative emissions.
There is currently no statewide regulation limiting the hours a BUG can be run. Notably, the South Coast Air Quality Management District (SCAQMD) has adopted such rules. SCAQMD’s Rule 1110.2 dictates that a permitted BUG may only be run for 200 hours per year, including usage for maintenance and testing (an estimated 10-30 hours, depending on generator technology).
- Air district rules during emergencies. Air districts provide for administrative exemption from established rules and regulations through the variance process, or in some cases have specific rules that do not apply during an emergency. For example, Yolo-Solano Air Quality Management District’s Rule 110 exempts emergency standby engines used during an emergency from the District’s other regulations on engines used over 200 hours per year, and the Bay Area Air Quality Management District’s Rule 9-8-330 states a person may operate an emergency standby generator an unlimited number of hours for emergency use.
If a permitted facility anticipates they will need to exceed their authorized emissions due to reasons outside their control, they may submit a request for a variance to the board of the air district, who will hear and vote on the request at a public meeting. Should an interruption arise without time for the normal variance and hearing process, there is also an established emergency variance process. When an emergency variance is requested, it can be granted by the chair of the air district board (or a designee) without the board convening.
Comments
- Is there a real problem? The Senate Environmental Quality Committee has seen no evidence of BUG regulations causing any facility to shut down or receive a fine during a PSPS event. Moreover, it is the understanding of staff that the only air district whose rules could limit BUG use during a PSPS is SCAQMD. Despite this, advocates for SB 1099 and similar BUG-exempting bills claim that the looming possibility of such consequences merits legislative action. It is impossible to predict the extent to which California’s utility providers will rely on grid deenergization to mitigate wildfire risk going forward.
- Stipulated Orders of Abatement. An SOA is a legally-binding agreement between an air district and a facility operating a stationary pollution source. An air district hearing board has statutory authority to issue such an order, with terms and conditions, to a facility. In the event that a facility expects they may exceed their runtime limits and be in violation of their permit, they could enter into an SOA to find a mutually-agreeable solution to that potential exceedance with the air district. Instead of being fined for exceeding their permit conditions, the facility could be required to address their emissions by, for example, agreeing to retire highly polluting generators under a defined timeline.
Committee amendments to SB 1099 ensured that local air district authority is maintained in determining conditions that would allow a BUG to be used for more hours than it is permitted. Currently, most of the permitted BUGs in the state do not have their runtime limited during an emergency. The committee amendments do not require all critical facilities to enter into SOAs or retire their BUGs, nor do they require air districts to change their rules on runtime limits. SB 1099 ensures that, if critical facilities are subject to runtime limits, they have a clear and available path to certainty by entering into a mutually-agreeable SOA with their local air district.
FISCAL EFFECT: Appropriation: No Fiscal Com.: Yes Local: Yes
SUPPORT: (Verified 6/9/20)
Association of California Water Agencies
California Cable & Telecommunications Association
California Groundwater Coalition
California Municipal Utilities Association
California Water Service
Calleguas Municipal Water District
City of Thousand Oaks
Eastern Municipal Water District
Elsinore Valley Municipal Water District
Irvine Ranch Water District
Laguna Beach County Water District
Las Virgenes Municipal Water District
Mesa Water District
Metropolitan Water District of Southern California
Municipal Water District of Orange County
Northern California Water Association
Public Water Agencies Group
Rowland Water District
San Diego County Water Authority
Sanitation Districts of Los Angeles County
Santa Clarita Valley Water Agency
Trabuco Canyon Water District
Western Municipal Water District
OPPOSITION: (Verified 6/9/20)
Bay Area Air Quality Management District
California Air Pollution Control Officers Association
Environmental Defense Fund
Republic Services, Inc
South Coast Air Quality Management District
ARGUMENTS IN SUPPORT: According to the California Municipal Utilities Association, “The widespread use of Public Safety Power Shutoffs (PSPS) to mitigate the risk of these wildfires could have significant impacts on critical facilities including water and wastewater agencies, such as the inability to pump water, inadequate fire flows, sewage backups and air conditioning shutoffs in facilities with temperature-sensitive equipment. If these agencies cannot access reliable electricity, communities could also face a public health crisis if they lack safe drinking water for consumption, cooking and sanitation.
“To mitigate these effects and ensure reliable electricity during a PSPS or other catastrophic loss of power like a wildfire, critical facilities must depend on their onsite emergency generators. However, state and local air district restrictions for some existing generators adopted prior to the widespread use of PSPS do not provide enough time for proper testing in advance of an event or enough runtime during an event.”
ARGUMENTS IN OPPOSITION: According to the California Air Pollution Control Officers Association, “This bill appears to be a solution looking for a problem. To date, the bill’s supporters have not identified a single instance of an air district preventing an essential service provider from operating BUGs or penalizing their use in response to an actual emergency. Local air districts understand the importance of BUGs operating during a PSPS event or other emergency to provide necessary power, especially for essential services. However, it is also important to ensure that this power is provided in a way that minimizes the potential harmful effects of significant diesel emissions on the community that can be caused by the operation of BUGs. The potential statewide effects of this bill could be significant, especially for older BUGs that emit greater amounts of NOx and toxic emissions while operating, with these emissions occurring near sensitive receptors, such as children and the elderly.”
Prepared by: Eric Walters / E.Q. / (916) 651-4108
6/10/20 13:25:08
**** END ****
SENATE COMMITTEE ON ENVIRONMENTAL QUALITY
Senator Allen, Chair
2019 - 2020 Regular
Bill No: SB 1099
Author: | Dodd | ||
Version: | 2/19/2020 | Hearing Date: | 5/29/2020 |
Urgency: | No | Fiscal: | Yes |
Consultant: | Eric Walters | ||
SUBJECT: Emergency backup generators: critical facilities: exemption
DIGEST: Requires air districts to adopt or revise their rules to allow critical facilities, as defined, to be allowed to use backup generators (BUGs)—without it counting towards permitted annual runtime totals—during deenergization events and for testing/maintenance. Also prevents air districts from collecting permitting fees for any BUG.
ANALYSIS:
Existing federal law:
- Sets, through the Federal Clean Air Act (FCAA) and its implementing regulations, National Ambient Air Quality Standards (NAAQS) for six criteria pollutants and requires states to prepare, submit, and adopt a State Implementation Plan (SIP) to limit air pollution and attain federal standards. (42 U.S.C. §7401 et seq.)
Existing state law:
- Establishes the Air Resources Board (ARB) as the air pollution control agency in California and requires ARB, among other things, to coordinate, encourage, and review the efforts of all levels of government as they affect air quality. (Health and Safety Code (HSC) §39500 et seq.)
- Creates the 35 air pollution control and air quality management districts (air districts) to be responsible for regional air quality planning, monitoring, and stationary source and facility permitting. (HSC §40000 et seq.)
- Defines “emergency use” as providing electrical power during specified events, including the loss of normal electrical power for reasons beyond the control of the operator. (Title 17 of the California Code of Regulations (CCR) §93115.4)
- Requires, under SB 901 (Dodd, Chapter 626, Statutes of 2018), electric utilities to develop annual wildfire mitigation plans (WMPs) to prevent, combat, and respond to wildfires within their service territories. (Public Utilities Code (PUC) §8386)
- Allows any person to apply to an air district’s hearing board for a variance from the district’s rules, regulations, and orders (HSC §42350 et seq.), and makes specifications for the issuance of that variance, including:
- That no variance shall be granted unless it is found that compliance would otherwise result in either an arbitrary or unreasonable taking of property, or the practical closing and elimination of a lawful business.
- Requiring a hearing board to (when the petitioner is a public agency) consider whether immediate compliance would otherwise impose an unreasonable burden on an “essential public service”—specifically, a prison, detention facility, police or firefighting facility, school, health care facility, landfill gas control or processing facility, sewage treatment works, or water delivery operation, if owned and operated by a public agency.
- That no variance shall be granted unless it is found that compliance would otherwise result in either an arbitrary or unreasonable taking of property, or the practical closing and elimination of a lawful business.
- Allows an air district board or air pollution control officer (APCO) to, after notice and hearing, order an entity to abate its emissions from a given technology, and such an order may contain stipulations regarding that abatement. (HSC § 42451)
- Allows air districts to establish a permit system, consistent with FCAA requirements, which requires any person who builds, erects, alters, replaces, operates, or uses any equipment that issues air contaminants. (HSC §42300)
This bill:
- Defines pertinent terms for this chapter of the Health and Safety Code.
- Makes findings and declarations regarding:
- The impacts on humans and the environment of increasing wildfires.
- How PSPS events create challenges for water agencies moving and delivering water.
- The necessity for action to reduce impacts from different events on different facilities, and that that action provide better access to alternative power sources for the purposes of water delivery and wildfire response.
- Requires air districts to adopt (or revise existing) rules to not count towards any time limitation for a critical facility:
- Using a BUG during a PSPS; or
- Performing routine testing and maintenance (following certain instructions, as specified) on a BUG.
- Prevents an air district from imposing a fee for issuing or renewing a permit for any BUG used by a critical facility.
Background
- Public safety power shutoffs. California’s wildfires have become more frequent, threatened more residents, and happened throughout more of the year in recent decades. More than 25 million acres of California wildlands are classified as under very high or extreme fire threat. Roughly a quarter of the state’s residents live in this area. Climate change has exacerbated the hot, dry conditions that support catastrophic fires, and while California attempts to mitigate its contributions to global climate change, the state is also taking immediate actions to protect its residents from wildfires.
To better protect safety and public health from uncontrolled wildfires, utility providers have adopted the use of Public Safety Power Shutoff (PSPS) events. Electricity transmission and distribution systems have sparked a number of wildfires, and this risk can be reduced by de-energizing the power lines during extreme weather events. During October of 2019, California utility providers conducted a dozen PSPS events. These affected millions of residents across 30 counties. While being an important public safety tool, power loss also has many negative impacts, especially to vulnerable populations (including residential customers that rely on reliable electric service to power life-saving medical devices), medical and emergency service providers (including hospitals, fire departments and police stations), and important public service providers (such as water agencies, gas stations and grocery stores). - Backup generators. In order to mitigate the damage of power loss, many of these critical service providers may rely on backup generators (BUGs) to replace lost grid power. Additionally, many businesses may use BUGs to avoid catastrophic system disruptions and to minimize economic disruption that could result from prolonged power outages. However, this use of BUGs may result in air quality and public health impacts.
According to estimates from ARB, nearly 125,000 BUGs were used in California during PSPS events in October 2019. Assuming an average of 50 hours of operation each, those generators released a cumulative total of 166.4 tons of nitrogen oxides (NOx), 19.4 tons of particulate matter (PM), and 8.9 tons of diesel PM. The diesel PM release was roughly equivalent to 29,000 additional heavy-duty diesel trucks being used for the month. - Health impacts of diesel emissions. In 1998, California identified diesel PM as a toxic air contaminant based on its potential to cause cancer, premature death, and other health problems. Numerous studies have documented a range of adverse health impacts from long-term exposure to diesel pollution, including increased risk for respiratory and cardiovascular illnesses, such as asthma, heart attacks and lung cancer, stunted lung growth in children, adverse birth outcomes, more frequent emergency room visits, and higher mortality rates.
- Air district permitting rules. Each of the state’s 35 air districts adopts their own sets of regulations and rules tailored to the sources and air quality challenges of its region and overseen by ARB. Ultimately, these actions are designed to achieve NAAQS set by the FCAA. Collectively, these strategies (i.e. emission standards, fuel regulations, emission limits, etc.) are included in the State Implementation Plan (SIP). ARB is the lead agency in California for achieving the emission reductions goals and timelines described in the SIP. The 35 air districts, as well as other agencies, prepare SIP elements to be reviewed and approved by ARB before being integrated into the SIP.
With few exceptions, anyone constructing or operating a facility that emits air pollutants must obtain an appropriate permit from the local air district. Each air district establishes its own fee schedule, and may maintain different requirements. An air district uses these permits to assess the air pollution impacts of stationary sources within its jurisdiction, and it may require additional standards or control technologies be used to align permitted entities’ emissions with the SIP. - Using and maintaining BUGs in California. Because of the air quality and public health impacts of diesel emissions, ARB and air districts have adopted rules and regulations that affect the amount of time BUGs can be used. The amount of time permitted for routine maintenance is dictated by ARB’s Airborne Toxic Control Measure for Stationary Diesel Engines. This regulation—and the implementing rules from air districts—dictates that older, more-polluting engines be tested for less time to control cumulative emissions.
There is currently no statewide regulation limiting the hours a BUG can be run. Notably, the South Coast Air Quality Management District (SCAQMD) has adopted such rules. SCAQMD’s Rule 1110.2 dictates that a permitted BUG may only be run for 200 hours (~8.3 days) per year, including usage for maintenance and testing (an estimated 10-30 hours, depending on generator technology). - Air district rules during emergencies. Air districts provide for administrative exemption from established rules and regulations through the variance process, or in some cases have specific rules that do not apply during an emergency. For example, Yolo-Solano Air Quality Management District’s Rule 110 exempts emergency standby engines used during an emergency from the District’s other regulations on engines used over 200 hours per year, and the Bay Area Air Quality Management District’s Rule 9-8-330 states that a person may operate an emergency standby generator an unlimited number of hours for emergency use.
If a permitted facility anticipates they will need to exceed their authorized emissions due to reasons outside their control, they may submit a request for a variance to the board of the air district, who will hear and vote on the request at a public meeting. Should an interruption arise without time for the normal variance and hearing process, there is also an established emergency variance process. When an emergency variance is requested, it can be granted by the chair of the air district board (or a designee) without the board convening.
Comments
- Purpose of Bill. According to the author, “Exacerbated by climate change, the wildfire season is now year-round and getting worse in terms of total acreage and impacts to people, communities and the environment. Recognizing the risk of powerlines or other utility equipment igniting a wildfire, California’s investor-owned electric utilities have incorporated Public Safety Power Shutoffs (PSPS) into their wildfire mitigation plans to reduce the likelihood of such a scenario. But PSPS events have significant impacts on critical facilities including water and wastewater agencies, such as the inability to pump water, inadequate fire flows, sewage backups and air conditioning shutoffs in facilities with temperature-sensitive equipment. If agencies cannot access reliable electricity, communities could face a public health crisis if they lack safe drinking water for consumption, cooking and sanitation. This goes directly against the state’s policy of a Human Right to Water.
“To mitigate these effects and ensure reliable electricity during a PSPS or other catastrophic loss of power like a wildfire, critical facilities must depend on their standby onsite emergency generators. However, state and air district restrictions for some existing generators adopted prior to the widespread use of PSPS do not provide enough time for proper testing in advance of a PSPS event or enough runtime during a PSPS event.
“SB 1099 would require local air districts to adopt a rule, or revise an existing rule, to allow critical facilities with a permitted emergency backup generator to operate their generators during a PSPS or other loss of power and test and maintain them in alignment with national standards, without facing penalties for keeping the water flowing and other critical facilities operating. This bill would provide a tailored solution that will balance the need to preserve air quality throughout the state with the need to ensure people and public health are protected.”
- Is there a real problem? As of this hearing, the committee has seen no evidence of BUG regulations causing any facility to shut down or receive a fine during a PSPS event. Moreover, it is the understanding of staff that the only air district whose rules could limit BUG use during a PSPS is SCAQMD. Despite this, advocates for SB 1099 and similar BUG-exempting bills claim that the looming possibility of such consequences merits legislative action. It is impossible to predict the extent to which California’s utility providers will rely on grid deenergization to mitigate wildfire risk going forward.
- Stipulated Orders of Abatement. An SOA is a legally-binding agreement between an air district and a facility operating a stationary pollution source. An air district hearing board has statutory authority to issue such an order, with terms and conditions, to a facility. In the event that a facility expects they may exceed their runtime limits and be in violation of their permit, they could enter into an SOA to find a mutually-agreeable solution to that potential exceedance with the air district. Instead of being fined for exceeding their permit conditions, the facility could be required to address their emissions by, for example, agreeing to retire highly polluting generators under a defined timeline.
Given the extent to which an SOA allows a regulated facility to have certainty they will not be fined for using a permitted generator during a PSPS, while still allowing the air district to uphold their FCAA obligations to regulate stationary pollution sources, the committee may wish to consider amending SB 1099 ensure the applicability of an SOA instead of a direct exemption of BUG hours from district rules.
As part of the stipulations in the SOA, the committee may wish to consider terms and conditions including but not limited to:- Allowing a facility to use an emergency BUG in exceedance of runtime and/or testing and maintenance limits (so long as that use is due to a PSPS, and the testing and maintenance are done according to established standards).
- A schedule for a technically and economically feasible retirement of more-polluting generators.
- Requiring the facility to report to the air district its BUG use that would exceed its permitted conditions.
- Board approval of agreed-upon terms and conditions.
- Allowing a facility to use an emergency BUG in exceedance of runtime and/or testing and maintenance limits (so long as that use is due to a PSPS, and the testing and maintenance are done according to established standards).
- Which facilities are critical? The definition of critical facility used in SB 1099 is, “a facility necessary or convenient in providing essential public services, including, but not limited to, facilities such as police stations, fire stations, emergency operations centers, water and wastewater facilities, incident command posts, and communication systems used to support essential public services.” The addition of “or convenient” means that the list of facilities exempted from air district rules could be much larger than intended.
The broad definition of “critical facilities” in SB 1099 goes beyond the author’s stated goals; the committee may wish to consider constraining the definition of “critical facilities”, and specifically including health facilities.
Related/Prior Legislation
SB 802 (Glazer, 2020) would exempt health facilities from BUG use counting towards air district emission timing rules during a PSPS. SB 802 is currently in the Senate Environmental Quality committee.
SB 1185 (Moorlach, 2020) would require applicants for emergency variances to demonstrate they are using the cleanest, feasible, available technology, and it would require reporting on PSPS events from utilities to air districts and ARB. SB 1185 will be heard by the Senate Environmental Quality committee on 5/29/2020.
AB 2182 (Rubio, 2020) would exempt any alternative power source used by any essential service provider during a PSPS from all local, regional, or state regulations. AB 2182 is currently in the Assembly Utilities and Energy committee.
SOURCE:
California Municipal Utilities Association
Las Virgenes Municipal Water District
Support
Association of California Water Agencies (ACWA)
California Cable & Telecommunications Association
California Groundwater Coalition
California Water Service
Calleguas Municipal Water District
Eastern Municipal Water District
Elsinore Valley Municipal Water District
Irvine Ranch Water District
Laguna Beach County Water District
Mesa Water District
Metropolitan Water District of Southern California
Municipal Water District of Orange County
Northern California Water Association
Public Water Agencies Group
Rowland Water District
Rural County Representatives of California
San Diego County Water Authority
Sanitation Districts of Los Angeles County
Santa Clarita Valley Water Agency
Trabuco Canyon Water District
Western Municipal Water District
OPPOSITION
Bay Area Air Quality Management District
California Air Pollution Control Officers Association
Sierra Club
South Coast Air Quality Management District
ARGUMENTS IN SUPPORT:
According to one of the sponsors, the California Municipal Utilities Association,
“The widespread use of Public Safety Power Shutoffs (PSPS) to mitigate the risk of these wildfires could have significant impacts on critical facilities including water and wastewater agencies, such as the inability to pump water, inadequate fire flows, sewage backups and air conditioning shutoffs in facilities with temperature-sensitive equipment. If these agencies cannot access reliable electricity, communities could also face a public health crisis if they lack safe drinking water for consumption, cooking and sanitation.
“To mitigate these effects and ensure reliable electricity during a PSPS or other catastrophic loss of power like a wildfire, critical facilities must depend on their onsite emergency generators. However, state and local air district restrictions for some existing generators adopted prior to the widespread use of PSPS do not provide enough time for proper testing in advance of an event or enough runtime during an event.
“SB 1099 would require local air districts to adopt a rule, or revise an existing rule, to allow critical facilities with a permitted emergency backup generator to operate their generators during a PSPS or other loss of power and test and maintain them consistent with national standards, without facing penalties for keeping the water flowing and other critical facilities operating. This bill would provide a tailored solution that will balance the need to preserve air quality throughout the state with the need to ensure people and public health are protected.”
ARGUMENTS IN OPPOSITION: According to the California Air Pollution Control Officers Association,
“This bill appears to be a solution looking for a problem. To date, the bill’s supporters have not identified a single instance of an air district preventing an essential service provider from operating BUGs or penalizing their use in response to an actual emergency. Local air districts understand the importance of BUGs operating during a PSPS event or other emergency to provide necessary power, especially for essential services. However, it is also important to ensure that this power is provided in a way that minimizes the potential harmful effects of significant diesel emissions on the community that can be caused by the operation of BUGs. The potential statewide effects of this bill could be significant, especially for older BUGs that emit greater amounts of NOx and toxic emissions while operating, with these emissions occurring near sensitive receptors, such as children and the elderly. For example, the South Coast AQMD has more than 10,000 permitted diesel-fueled emergency BUGs in its four-county jurisdiction with varying sizes, ages, and emission levels, with about 40 percent of these generators more than twenty years old.
“SB 1099 would reduce local air districts’ authority to regulate air pollution related to operation of BUGs and would also impose a financial burden on local air districts’ already strained budgetary resources by eliminating the ability to collect fees needed to help fund local air district permitting functions related to mitigating emissions from BUGs. This would hurt air districts’ air pollution reduction efforts by shrinking overall resources, which will ultimately result in negative impacts to public health.
“Overall, this bill runs counter to local air districts’ missions to protect public health, reduce the impacts of air pollution throughout California, and attain federal air quality standards. Further, the issues raised in the bill have been and will continue to be successfully addressed at the local level without interruption of needed power during emergency situations.”
-- END --
Bill Author
Bill Co-Author(s):