AB 2469: Data centers: water use disclosures.
- Session Year: 2025-2026
- House: Assembly
- Latest Version Date: 2026-09-21
Current Status:
Passed
(2026-09-21: Chaptered by Secretary of State - Chapter 436, Statutes of 2026.)
Introduced
In Committee
Awaiting First Chamber Vote
Passed First Chamber
In Committee
Awaiting Second Chamber Vote
Passed Second Chamber
Enacted
The Planning and Zoning Law authorizes the legislative body of any county or city to adopt ordinances that, among other things, regulate the use of buildings, structures, and land as between industry, businesses, residences, and open space, as specified.
This bill would prohibit a city, county, or city and county from approving a discretionary or ministerial permit or other entitlement that would result in the construction, or an expansion that increases the maximum peak water use, of a data center unless specified conditions are satisfied, including, among others, that the applicant provides the city, county, or city and county prescribed information. The bill would include in this prescribed information a water scarcity plan and a water supply assessment, each as provided. The bill would also include in the specified conditions that the applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the applicable water supplier. The bill would provide that this provision is severable. By expanding the duties of local agencies to administer these provisions, this bill would impose a state-mandated local program.
The bill would include findings that changes proposed by this bill address a matter of statewide concern rather than a municipal affair and, therefore, apply to all cities, including charter cities.
The California Constitution requires the state to reimburse local agencies and school districts for certain costs mandated by the state. Statutory provisions establish procedures for making that reimbursement.
This bill would provide that no reimbursement is required by this act for a specified reason.
The Planning and Zoning Law authorizes the legislative body of any county or city to adopt ordinances that, among other things, regulate the use of buildings, structures, and land as between industry, businesses, residences, and open space, as specified.
This bill would prohibit a city, county, or city and county from approving a discretionary or ministerial permit or other entitlement that would result in the construction, or an expansion that increases the maximum peak water use, of a data center unless specified conditions are satisfied, including, among others, that the applicant provides the city, county, or city and county prescribed information. The bill would include in this prescribed information a water scarcity plan and a water supply assessment, each as provided. The bill would also include in the specified conditions that the applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the applicable water supplier. The bill would provide that this provision is severable. By expanding the duties of local agencies to administer these provisions, this bill would impose a state-mandated local program.
The bill would include findings that changes proposed by this bill address a matter of statewide concern rather than a municipal affair and, therefore, apply to all cities, including charter cities.
The California Constitution requires the state to reimburse local agencies and school districts for certain costs mandated by the state. Statutory provisions establish procedures for making that reimbursement.
This bill would provide that no reimbursement is required by this act for a specified reason.
The Planning and Zoning Law authorizes the legislative body of any county or city to adopt ordinances that, among other things, regulate the use of buildings, structures, and land as between industry, businesses, residences, and open space, as specified.
This bill would prohibit a city, county, or city and county from approving a discretionary or ministerial permit or other entitlement that would result in the construction, or an expansion that increases the maximum peak water use, of a data center unless specified conditions are satisfied, including, among others, that the applicant provides the city, county, or city and a county prescribed information. The bill would include in this prescribed information a water scarcity plan and a water supply assessment, each as provided. The bill would also include in the specified conditions that the applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the applicable water supplier. The bill would provide that this provision is severable. By expanding the duties of local agencies to administer these provisions, this bill would impose a state-mandated local program.
The bill would include findings that changes proposed by this bill address a matter of statewide concern rather than a municipal affair and, therefore, apply to all cities, including charter cities.
The California Constitution requires the state to reimburse local agencies and school districts for certain costs mandated by the state. Statutory provisions establish procedures for making that reimbursement.
This bill would provide that no reimbursement is required by this act for a specified reason.
The Planning and Zoning Law authorizes the legislative body of any county or city to adopt ordinances that, among other things, regulate the use of buildings, structures, and land as between industry, businesses, residences, and open space, as specified.
This bill would prohibit a city, county, or city and county from approving a discretionary or ministerial permit or other entitlement that would result in the construction, or an expansion that increases the maximum peak water use, of a data center unless specified conditions are satisfied, including, among others, that the applicant provides the city, county, or city and a county prescribed information. The bill would include in this prescribed information a water scarcity plan, plan and a water supply assessment, and a water use assessment, each as provided. The bill would also include in the specified conditions that the applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the Department of Water Resources or the applicable water supplier. By expanding the duties of local agencies to administer these provisions, this bill would impose a state-mandated local program.
Existing law requires the Department of Water Resources to recommend, and the State Water Resources Control Board to adopt, as prescribed, performance measures for water used by commercial, industrial, institutional, and large landscape water users (CII water use). Existing law requires each urban retail water supplier, as defined, to implement the performance measures adopted by the board under these provisions.This bill would require the department to develop a definition and estimate of annual water consumption, no later than June 30, 2028, for CII water users that qualify as large consumptive-use facilities, including data centers and similar water consumption patterns, as provided.The bill would include findings that changes proposed by this bill address a matter of statewide concern rather than a municipal affair and, therefore, apply to all cities, including charter cities.
The California Constitution requires the state to reimburse local agencies and school districts for certain costs mandated by the state. Statutory provisions establish procedures for making that reimbursement.
This bill would provide that no reimbursement is required by this act for a specified reason.
The Planning and Zoning Law authorizes the legislative body of any county or city to adopt ordinances that, among other things, regulate the use of buildings, structures, and land as between industry, businesses, residences, and open space, as specified.
This bill would prohibit a city, county, or city and county from approving a discretionary or ministerial permit or other entitlement that would result in the construction, or an expansion that increases the maximum peak water use, of a data center unless specified conditions are satisfied, including, among others, that the applicant provides the city, county, or city and a county prescribed information. The bill would include in this prescribed information a water scarcity plan, a water supply assessment, and a water use assessment, each as provided. The bill would also include in the specified conditions that the applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the Department of Water Resources or the applicable water supplier. By expanding the duties of local agencies to administer these provisions, this bill would impose a state-mandated local program.
Existing law requires the Department of Water Resources to recommend, and the State Water Resources Control Board to adopt, as prescribed, performance measures for water used by commercial, industrial, institutional, and large landscape water users (CII water use). Existing law requires each urban retail water supplier, as defined, to implement the performance measures adopted by the board under these provisions.
This bill would require the department to recommend develop a definition and estimate of annual water consumption, no later than June 30, 2028, and the board to adopt, no later than December 31, 2029, a for CII water use classification for users that qualify as large consumptive use consumptive-use facilities, including data centers. The bill would require that this classification be separate and distinct from classifications applicable to other CII water use. centers and similar water consumption patterns, as provided.
The bill would include findings that changes proposed by this bill address a matter of statewide concern rather than a municipal affair and, therefore, apply to all cities, including charter cities.
The California Constitution requires the state to reimburse local agencies and school districts for certain costs mandated by the state. Statutory provisions establish procedures for making that reimbursement.
This bill would provide that no reimbursement is required by this act for a specified reason.
The Planning and Zoning Law authorizes the legislative body of any county or city to adopt ordinances that, among other things, regulate the use of buildings, structures, and land as between industry, businesses, residences, and open space, as specified.
This bill would prohibit a city, county, or city and county from approving a discretionary or ministerial permit or other entitlement that would result in the construction, or an expansion that increases the maximum peak water use, of a data center unless specified conditions are satisfied, including, among others, that the applicant provides the city, county, or city and a county prescribed information. The bill would include in this prescribed information a water scarcity plan, a water supply assessment, and a water use assessment, each as provided. The bill would also include in the specified conditions that the applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the Department of Water Resources or the applicable water supplier. By expanding the duties of local agencies to administer these provisions, this bill would impose a state-mandated local program.
Existing law requires the Department of Water Resources to recommend, and the State Water Resources Control Board to adopt, as prescribed, performance measures for water used by commercial, industrial, institutional, and large landscape water users (CII water use). Existing law requires each urban retail water supplier, as defined, to implement the performance measures adopted by the board under these provisions.
This bill would require the department to recommend no later than June 30, 2028, and the board to adopt, no later than December 31, 2029, a CII water use classification for users that qualify as large consumptive use facilities, including data centers. The bill would require that this classification be separate and distinct from classifications applicable to other CII water use.
The bill would include findings that changes proposed by this bill address a matter of statewide concern rather than a municipal affair and, therefore, apply to all cities, including charter cities.
The California Constitution requires the state to reimburse local agencies and school districts for certain costs mandated by the state. Statutory provisions establish procedures for making that reimbursement.
This bill would provide that no reimbursement is required by this act for a specified reason.
The Planning and Zoning Law authorizes the legislative body of any county or city to adopt ordinances that, among other things, regulate the use of buildings, structures, and land as between industry, businesses, residences, and open space, as specified.
This bill would prohibit a city, county, or city and county from approving a discretionary or ministerial permit or other entitlement that would result in the construction, or an expansion that increases the maximum peak water use, of a data center unless specified conditions are satisfied, including, among others, that the applicant provides the city, county, or city and a county prescribed information. The bill would include in this prescribed information a water scarcity plan, a water supply assessment, and a water use assessment, each as provided. The bill would also include in the specified conditions that the construction or expansion is not within the boundaries of a groundwater basin designated as critically overdrafted by the Department of Water Resources, except as specified, and that the applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the Department of Water Resources or the applicable water supplier. By expanding the duties of local agencies to administer these provisions, this bill would impose a state-mandated local program.
Existing law requires the Department of Water Resources to recommend, and the State Water Resources Control Board to adopt, as prescribed, performance measures for water used by commercial, industrial, institutional, and large landscape water users (CII water use). Existing law requires each urban retail water supplier, as defined, to implement the performance measures adopted by the board under these provisions.
This bill would require the department to recommend no later than June 30, 2028, and the board to adopt, no later than December 31, 2029, a CII water use classification for users that qualify as large consumptive use facilities, including data centers. The bill would require that this classification be separate and distinct from classifications applicable to other CII water use.
The bill would include findings that changes proposed by this bill address a matter of statewide concern rather than a municipal affair and, therefore, apply to all cities, including charter cities.
The California Constitution requires the state to reimburse local agencies and school districts for certain costs mandated by the state. Statutory provisions establish procedures for making that reimbursement.
This bill would provide that no reimbursement is required by this act for a specified reason.
The Planning and Zoning Law authorizes the legislative body of any county or city to adopt ordinances that, among other things, regulate the use of buildings, structures, and land as between industry, businesses, residences, and open space, as specified.
This bill would prohibit a city, county, or city and county from approving a discretionary or ministerial permit or other entitlement that would result in the construction, or an expansion that increases the maximum peak water use, of a data center unless specified conditions are satisfied, including, among others, that the applicant provides the city, county, or city and a county prescribed information. The bill would include in this prescribed information a water scarcity plan, a water supply assessment, and a water use assessment, each as provided. The bill would also include in the specified conditions that the construction or expansion is not within the boundaries of a groundwater basin designated as critically overdrafted by the Department of Water Resources, except as specified, and that the applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the Department of Water Resources or the applicable water supplier. By expanding the duties of local agencies to administer these provisions, this bill would impose a state-mandated local program.
Existing law requires the Department of Water Resources to recommend, and the State Water Resources Control Board to adopt, as prescribed, performance measures for water used by commercial, industrial, institutional, and large landscape water users (CII water use). Existing law requires each urban retail water supplier, as defined, to implement the performance measures adopted by the board under these provisions.
This bill would require the department to recommend, recommend no later than June 30, 2028, and the board to adopt, no later than an unspecified date, December 31, 2029, a CII water use classification for users that qualify as large consumptive use facilities, including data centers. The bill would require that this classification be separate and distinct from classifications applicable to other CII water use.
The bill would include findings that changes proposed by this bill address a matter of statewide concern rather than a municipal affair and, therefore, apply to all cities, including charter cities.
The California Constitution requires the state to reimburse local agencies and school districts for certain costs mandated by the state. Statutory provisions establish procedures for making that reimbursement.
This bill would provide that no reimbursement is required by this act for a specified reason.
The Planning and Zoning Law authorizes the legislative body of any county or city to adopt ordinances that, among other things, regulate the use of buildings, structures, and land as between industry, businesses, residences, and open space, as specified.
This bill would prohibit a city, county, or city and county from approving a discretionary or ministerial permit or other entitlement that would result in the construction, or an expansion that increases the maximum peak use, of a data center unless specified conditions are satisfied, including, among others, that the applicant provides the city, county, or city and a county prescribed information. The bill would include in this prescribed information a water scarcity plan, a water supply assessment, and a water use assessment, each as provided. The bill would also include in the specified conditions that the construction or expansion is not within the boundaries of a groundwater basin designated as critically overdrafted by the Department of Water Resources, except as specified, and that the applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the Department of Water Resources or the applicable water supplier. By expanding the duties of local agencies to administer these provisions, this bill would impose a state-mandated local program.
Existing law requires the Department of Water Resources to recommend, and the State Water Resources Control Board to adopt, as prescribed, performance measures for water used by commercial, industrial, institutional, and large landscape water users (CII water use). Existing law requires each urban retail water supplier, as defined, to implement the performance measures adopted by the board under these provisions.
This bill would require the department to recommend, and the board to adopt, no later than an unspecified date, a CII water use classification for users that qualify as large consumptive use facilities, including data centers. The bill would require that this classification be separate and distinct from classifications applicable to other CII water use.
The bill would include findings that changes proposed by this bill address a matter of statewide concern rather than a municipal affair and, therefore, apply to all cities, including charter cities.
The California Constitution requires the state to reimburse local agencies and school districts for certain costs mandated by the state. Statutory provisions establish procedures for making that reimbursement.
This bill would provide that no reimbursement is required by this act for a specified reason.
Existing law, the Water Recycling Law, declares that the people of the state have a primary interest in the development of facilities to recycle water containing waste to supplement existing surface and underground water supplies and to assist in meeting the future water requirements of the state.This bill would make nonsubstantive changes to the above-referenced provisions.Existing law, the Water Recycling Law, declares that the people of the state have a primary interest in the development of facilities to recycle water containing waste to supplement existing surface and underground water supplies and to assist in meeting the future water requirements of the state.
This bill would make nonsubstantive changes to the above-referenced provisions.
(a)For purposes of this section, water scarcity plan means a report that includes measures to be implemented during an abnormally dry year, a moderate drought year, a severe drought year, an extreme drought year, and an exceptional drought year, as defined by the United States drought monitor, including staged withdrawal reductions, nonessential use curtailment, recycling and reuse, thermal load reductions, and temporary load shedding where necessary.
(b)Notwithstanding any other law, a city, county, or city and county shall not approve a discretionary or ministerial permit or other entitlement that would result in the construction, or expansion that increases the maximum peak water use, of a data center unless all of the following conditions are satisfied:
(1)The applicant has provided the city, county, or city and county with all of the following:
(A)A water supply assessment, as described in Part 2.10 (commencing with Section 10910) of Division 6 of the Water Code, for the construction or expansion.
(B)Beginning January 1, 2028, a water scarcity plan, as defined in subdivision (a).
(C)Projected water use and water efficiency measures.
(D)Disclosures regarding estimated workforce needs associated with the project, including all of the following:
(i)Workforce composition.
(ii)Job classifications.
(iii)Employment duration.
(iv)Wage ranges and benefits.
(v)The proportion of the workforce residing within the county in which the project is located.
(vi)The proportion of the workforce residing within the state.
(2)The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the applicable water supplier.
(3)Nothing in this section shall be construed to require a city, county, or city and county to approve a permit, entitlement, or other approval for the construction or expansion of a data center solely because the applicant has satisfied the requirements of this subdivision.
(c)Paragraph (2) of subdivision (b) is severable. If paragraph (2) of subdivision (b) or its application is held invalid, that invalidity shall not affect other provisions or applications that can be given effect without the invalid provision or application.
SEC. 2.The Legislature finds and declares that water conservation is a matter of statewide concern and is not a municipal affair as that term is used in Section 5 of Article XI of the California Constitution. Therefore, Section 1 of this act adding Section 65964.7 to the Government Code applies to all cities, including charter cities.
SEC. 3.No reimbursement is required by this act pursuant to Section 6 of Article XIIIB of the California Constitution because a local agency or school district has the authority to levy service charges, fees, or assessments sufficient to pay for the program or level of service mandated by this act, within the meaning of Section 17556 of the Government Code.
(a)For purposes of this section, water scarcity plan means a report that includes measures to be implemented during an abnormally dry year, a moderate drought year, a severe drought year, an extreme drought year, and an exceptional drought year, as defined by the United States drought monitor, including staged withdrawal reductions, nonessential use curtailment, recycling and reuse, thermal load reductions, and temporary load shedding where necessary.
(b)Notwithstanding any other law, a city, county, or city and county shall not approve a discretionary or ministerial permit or other entitlement that would result in the construction, or expansion that increases the maximum peak water use, of a data center unless all of the following conditions are satisfied:
(1)The applicant has provided the city, county, or city and county with all of the following:
(A)A water supply assessment, as described in Part 2.10 (commencing with Section 10910) of Division 6 of the Water Code, for the construction or expansion.
(B)Beginning January 1, 2028, a water scarcity plan, as defined in subdivision (a).
(C)Projected water use and water efficiency measures.
(D)Disclosures regarding estimated workforce needs associated with the project, including all of the following:
(i)Workforce composition.
(ii)Job classifications.
(iii)Employment duration.
(iv)Wage ranges and benefits.
(v)The proportion of the workforce residing within the county in which the project is located.
(vi)The proportion of the workforce residing within the state.
(2)The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the applicable water supplier.
(3)Nothing in this section shall be construed to require a city, county, or city and county to approve a permit, entitlement, or other approval for the construction or expansion of a data center solely because the applicant has satisfied the requirements of this subdivision.
(c)Paragraph (2) of subdivision (b) is severable. If paragraph (2) of subdivision (b) or its application is held invalid, that invalidity shall not affect other provisions or applications that can be given effect without the invalid provision or application.
SEC. 2.The Legislature finds and declares that water conservation is a matter of statewide concern and is not a municipal affair as that term is used in Section 5 of Article XI of the California Constitution. Therefore, Section 1 of this act adding Section 65964.7 to the Government Code applies to all cities, including charter cities.
SEC. 3.No reimbursement is required by this act pursuant to Section 6 of Article XIIIB of the California Constitution because a local agency or school district has the authority to levy service charges, fees, or assessments sufficient to pay for the program or level of service mandated by this act, within the meaning of Section 17556 of the Government Code.
(a)For purposes of this section, water scarcity plan means a report that includes measures to be implemented during an abnormally dry year, a moderate drought year, a severe drought year, an extreme drought year, and an exceptional drought year, as defined by the United States drought monitor, including staged withdrawal reductions, nonessential use curtailment, recycling and reuse, thermal load reductions, and temporary load shedding where necessary.
(b)Notwithstanding any other law, a city, county, or city and county shall not approve a discretionary or ministerial permit or other entitlement that would result in the construction, or expansion that increases the maximum peak water use, of a data center unless all of the following conditions are satisfied:
(1)The applicant has provided the city, county, or city and county with all of the following:
(A)A water supply assessment, as described in Part 2.10 (commencing with Section 10910) of Division 6 of the Water Code, for the construction or expansion.
(B)Beginning January 1, 2028, a water scarcity plan, as defined in subdivision (a).
(C)Projected water use and water efficiency measures.
(D)Disclosures regarding estimated workforce needs associated with the project, including all of the following:
(i)Workforce composition.
(ii)Job classifications.
(iii)Employment duration.
(iv)Wage ranges and benefits.
(v)The proportion of the workforce residing within the county in which the project is located.
(vi)The proportion of the workforce residing within the state.
(2)The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the applicable water supplier.
(3)Nothing in this section shall be construed to require a city, county, or city and county to approve a permit, entitlement, or other approval for the construction or expansion of a data center solely because the applicant has satisfied the requirements of this subdivision.
(c)Paragraph (2) of subdivision (b) is severable. If paragraph (2) of subdivision (b) or its application is held invalid, that invalidity shall not affect other provisions or applications that can be given effect without the invalid provision or application.
SEC. 2.The Legislature finds and declares that water conservation is a matter of statewide concern and is not a municipal affair as that term is used in Section 5 of Article XI of the California Constitution. Therefore, Section 1 of this act adding Section 65964.7 to the Government Code applies to all cities, including charter cities.
SEC. 3.No reimbursement is required by this act pursuant to Section 6 of Article XIIIB of the California Constitution because a local agency or school district has the authority to levy service charges, fees, or assessments sufficient to pay for the program or level of service mandated by this act, within the meaning of Section 17556 of the Government Code.
(a)For purposes of this section:
(1)Water section, water scarcity plan means a report that includes measures to be implemented during an abnormally dry year, a moderate drought year, a severe drought year, an extreme drought year, and an exceptional drought year, as defined by the United States drought monitor, including staged withdrawal reductions, nonessential use curtailment, recycling and reuse, thermal load reductions, and temporary load shedding where necessary.
(2)Water use assessment means a report that includes all of the following:(A)A description of the data center, including its location, identification of the owner and operator, and a detailed description of operations.(B)A detailed accounting of expected water intake, expressed in gallons per day and total volume, including:(i)Maximum and average daily demand.(ii)Maximum and average monthly demand.(iii)Demand over an average 12-month consecutive period.(iv)Water withdrawals.(C)A detailed explanation of each direct water use, including, but not limited to, cooling systems, humidification, potable and sanitary uses, fire suppression systems, and maintenance operations. For each use, the assessment includes identification of all of the following:(i)Input water quality requirements.(ii)Whether the use is consumptive.(iii)Average daily consumptive volume.(iv)Whether the use is continuous, intermittent, or seasonal.(v)Opportunities for reuse or closed-loop systems.(D)A cooling alternatives analysis that compares the proposed cooling method to a range of alternatives, including all of the following:(i)Evaluation of water use at the data center and at the site of energy generation.(ii)Evaluation of impact on source water and water scarcity.(iii)Consideration of closed-loop cooling.(b)Notwithstanding any other law, a city, county, or city and county shall not approve a discretionary or ministerial permit or other entitlement that would result in the construction, or expansion that increases the maximum peak water use, of a data center unless all of the following conditions are satisfied:
(1)The applicant has provided the city, county, or city and county with all of the following:
(A)A water supply assessment, as described in Part 2.10 (commencing with Section 10910) of Division 6 of the Water Code, for the construction or expansion.
(B)Upon request of the city, county, or city and county, a water use assessment, as defined in paragraph (2) of subdivision (a).(C)(B)Beginning January 1, 2028, a water scarcity plan, as defined in paragraph (1) of subdivision (a).
(D)(C)Projected water use and water efficiency measures.
(E)(D)Disclosures regarding workforce needs associated with the project, including all of the following:
(i)Workforce composition.
(ii)Job classifications.
(iii)Employment duration.
(iv)Wage ranges and benefits.
(v)The proportion of the workforce residing within the county in which the project is located.
(vi)The proportion of the workforce residing within the state.
(vii)All water resource plans, water usage reports, supporting documentation, and any approvals issued by a state or local agency related to the plans or applications.(2)The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the Department of Water Resources or the applicable water supplier.
(3)Nothing in this section shall be construed to require a city, county, or city and county to approve a permit, entitlement, or other approval for the construction or expansion of a data center solely because the applicant has satisfied the requirements of this subdivision.
SEC. 2.Section 10609.13 is added to the Water Code, to read:10609.13.The department, in coordination with the board, shall conduct necessary studies and investigations to develop a definition and estimate of annual water consumption, no later than June 30, 2028, for CII water users that qualify as large consumptive-use facilities, including data centers and similar water consumption patterns. CII outdoor irrigation water use that is served through a dedicated irrigation meter shall be excluded from the definition and estimate.SEC. 3.SEC. 2.The Legislature finds and declares that water conservation is a matter of statewide concern and is not a municipal affair as that term is used in Section 5 of Article XI of the California Constitution. Therefore, Section 1 of this act adding Section 65964.7 to the Government Code applies to all cities, including charter cities.
SEC. 4.SEC. 3.No reimbursement is required by this act pursuant to Section 6 of Article XIIIB of the California Constitution because a local agency or school district has the authority to levy service charges, fees, or assessments sufficient to pay for the program or level of service mandated by this act, within the meaning of Section 17556 of the Government Code.
(a)For purposes of this section:
(1)Water scarcity plan means a report that includes measures to be implemented during an abnormally dry year, as a moderate drought year, a severe drought year, and an extreme drought year, and an exceptional drought year, as defined by the United States drought monitor, including staged withdrawal reductions, nonessential use curtailment, recycling and reuse, thermal load reductions, and temporary load shedding where necessary.
(2)Water use assessment means a report that includes all of the following:
(A)A description of the data center, including its location, identification of the owner and operator, and a detailed description of operations.
(B)A detailed accounting of expected water intake, expressed in gallons per day and total volume, including:
(i)Maximum and average daily demand.
(ii)Maximum and average monthly demand.
(iii)Demand over an average 12-month consecutive period.
(iv)Water withdrawals.
(v)Phases of growth or expansion.(vi)Trigger points for additional demand.(vii)Full build-out and peak operation scenarios.(C)A detailed explanation of each direct water use, including, but not limited to, cooling systems, humidification, potable and sanitary uses, fire suppression systems, and maintenance operations. For each use, the assessment includes identification of all of the following:
(i)Input water quality requirements.
(ii)Whether the use is consumptive.
(iii)Average daily consumptive volume.
(iv)Whether the use is continuous, intermittent, or seasonal.
(v)Opportunities for reuse or closed-loop systems.
(D)A cooling alternatives analysis that compares the proposed cooling method to a range of alternatives, including all of the following:
(i)Evaluation of water use at the data center and at the site of energy generation.
(ii)Evaluation of impact on source water and water scarcity.
(iii)Consideration of closed-loop cooling.
(E)A detailed estimate of indirect water use associated with energy production disaggregated by generation type.(F)A cost-of-service study completed by the applicable water provider within the last five years, or funded by the data center if none exists.(b)Notwithstanding any other law, a city, county, or city and county shall not approve a discretionary or ministerial permit or other entitlement that would result in the construction, or expansion that increases the maximum peak water use, of a data center unless all of the following conditions are satisfied:
(1)The applicant has provided the city, county, or city and county with all of the following:
(A)A water supply assessment, as described in Part 2.10 (commencing with Section 10910) of Division 6 of the Water Code, for the construction or expansion.
(B)Upon request of the city, county, or city and county, a water use assessment, as defined in paragraph (2) of subdivision (a).
(C)Beginning January 1, 2028, a water scarcity plan, as defined in paragraph (1) of subdivision (a).
(D)Projected water use and water efficiency measures.
(E)Disclosures regarding workforce needs associated with the project, including all of the following:
(i)Workforce composition.
(ii)Job classifications.
(iii)Employment duration.
(iv)Wage ranges and benefits.
(v)The proportion of the workforce residing within the county in which the project is located.
(vi)The proportion of the workforce residing within the state.
(vii)All water resource plans, water usage reports, supporting documentation, and any approvals issued by a state or local agency related to the plans or applications.
(2)The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the Department of Water Resources or the applicable water supplier.
(3)Nothing in this section shall be construed to require a city, county, or city and county to approve a permit, entitlement, or other approval for the construction or expansion of a data center solely because the applicant has satisfied the requirements of this subdivision.
SEC. 2.Section 10609.13 is added to the Water Code, to read:10609.13.(a)The department, in coordination with the board, shall conduct necessary studies and investigations and recommend, to develop a definition and estimate of annual water consumption, no later than June 30, 2028, a for CII water use classification system for users that qualify as large consumptive use consumptive-use facilities, including data centers. The classification system required by this section shall be separate and distinct from classifications applicable to other CII water use. centers and similar water consumption patterns. CII outdoor irrigation water use that is served through a dedicated irrigation meter shall be excluded from the definition and estimate.
(b)(1)The board, in coordination with the department, shall adopt the classification for CII water use required by this section on or before December 31, 2029.(2)Each urban retail water supplier shall implement the classification adopted by the board pursuant to paragraph (1).SEC. 3.The Legislature finds and declares that water conservation is a matter of statewide concern and is not a municipal affair as that term is used in Section 5 of Article XI of the California Constitution. Therefore, Section 1 of this act adding Section 65964.7 to the Government Code applies to all cities, including charter cities.
SEC. 4.No reimbursement is required by this act pursuant to Section 6 of Article XIIIB of the California Constitution because a local agency or school district has the authority to levy service charges, fees, or assessments sufficient to pay for the program or level of service mandated by this act, within the meaning of Section 17556 of the Government Code.
(a)For purposes of this section:
(1)Water scarcity plan means a report that includes measures to be implemented during an abnormally dry year, as moderate drought year, a severe drought year, and extreme drought year, and an exceptional drought year, as defined by the United States drought monitor, including staged withdrawal reductions, nonessential use curtailment, recycling and reuse, thermal load reductions, and temporary load shedding where necessary.
(2)Water use assessment means a report that includes all of the following:
(A)A description of the data center, including its location, identification of the owner and operator, and a detailed description of operations.
(B)A detailed accounting of expected water intake, expressed in gallons per day and total volume, including:
(i)Maximum and average daily demand.
(ii)Maximum and average monthly demand.
(iii)Demand over an average 12-month consecutive period.
(iv)Water withdrawals.
(v)Phases of growth or expansion.
(vi)Trigger points for additional demand.
(vii)Full build-out and peak operation scenarios.
(C)A detailed explanation of each direct water use, including, but not limited to, cooling systems, humidification, potable and sanitary uses, fire suppression systems, and maintenance operations. For each use, the assessment includes identification of all of the following:
(i)Input water quality requirements.
(ii)Whether the use is consumptive.
(iii)Average daily consumptive volume.
(iv)Whether the use is continuous, intermittent, or seasonal.
(v)Opportunities for reuse or closed-loop systems.
(D)A cooling alternatives analysis that compares the proposed cooling method to a range of alternatives, including all of the following:
(i)Evaluation of water use at the data center and at the site of energy generation.
(ii)Evaluation of impact on source water and water scarcity.
(iii)Consideration of closed-loop cooling.
(E)A detailed estimate of indirect water use associated with energy production disaggregated by generation type.
(F)A cost-of-service study completed by the applicable water provider within the last five years, or funded by the data center if none exists.
(b)Notwithstanding any other law, a city, county, or city and county shall not approve a discretionary or ministerial permit or other entitlement that would result in the construction, or expansion that increases the maximum peak water use, of a data center unless all of the following conditions are satisfied:
(1)The applicant has provided the city, county, or city and county with all of the following:
(A)A water supply assessment that was completed pursuant to assessment, as described in Part 2.10 (commencing with Section 10910) of Division 6 of the Water Code, if applicable. Code, for the construction or expansion.
(B)Upon request of the city, county, or city and county, a water use assessment, as defined in paragraph (2) of subdivision (a).
(C)Beginning January 1, 2028, a water scarcity plan, as defined in paragraph (1) of subdivision (a).
(D)Projected water use and water efficiency measures.
(E)Disclosures regarding workforce needs associated with the project, including all of the following:
(i)Workforce composition.
(ii)Job classifications.
(iii)Employment duration.
(iv)Wage ranges and benefits.
(v)The proportion of the workforce residing within the county in which the project is located.
(vi)The proportion of the workforce residing within the state.
(vii)All water resource plans, water usage reports, supporting documentation, and any approvals issued by a state or local agency related to the plans or applications.
(2)The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the Department of Water Resources or the applicable water supplier.
SEC. 2.Section 10609.13 is added to the Water Code, to read:10609.13.(a)The department, in coordination with the board, shall conduct necessary studies and investigations and recommend, no later than June 30, 2028, a CII water use classification system for users that qualify as large consumptive use facilities, including data centers. The classification system required by this section shall be separate and distinct from classifications applicable to other CII water use.
(b)(1)The board, in coordination with the department, shall adopt the classification for CII water use required by this section on or before December 31, 2029.
(2)Each urban retail water supplier shall implement the classification adopted by the board pursuant to paragraph (1).
SEC. 3.The Legislature finds and declares that water conservation is a matter of statewide concern and is not a municipal affair as that term is used in Section 5 of Article XI of the California Constitution. Therefore, Section 1 of this act adding Section 65964.7 to the Government Code applies to all cities, including charter cities.
SEC. 4.No reimbursement is required by this act pursuant to Section 6 of Article XIIIB of the California Constitution because a local agency or school district has the authority to levy service charges, fees, or assessments sufficient to pay for the program or level of service mandated by this act, within the meaning of Section 17556 of the Government Code.
(a)For purposes of this section:
(1)Water scarcity plan means a report that includes measures to be implemented during an abnormally dry year, as moderate drought year, a severe drought year, and extreme drought year, and an exceptional drought year, as defined by the United States drought monitor, including staged withdrawal reductions, nonessential use curtailment, recycling and reuse, thermal load reductions, and temporary load shedding where necessary.
(2)Water use assessment means a report that includes all of the following:
(A)A description of the data center, including its location, identification of the owner and operator, and a detailed description of operations.
(B)A detailed accounting of expected water intake, expressed in gallons per day and total volume, including:
(i)Maximum and average daily demand.
(ii)Maximum and average monthly demand.
(iii)Demand over an average 12-month consecutive period.
(iv)Water withdrawals.
(v)Phases of growth or expansion.
(vi)Trigger points for additional demand.
(vii)Full build-out and peak operation scenarios.
(C)A detailed explanation of each direct water use, including, but not limited to, cooling systems, humidification, potable and sanitary uses, fire suppression systems, and maintenance operations. For each use, the assessment includes identification of all of the following:
(i)Input water quality requirements.
(ii)Whether the use is consumptive.
(iii)Average daily consumptive volume.
(iv)Whether the use is continuous, intermittent, or seasonal.
(v)Opportunities for reuse or closed-loop systems.
(D)A cooling alternatives analysis that compares the proposed cooling method to a range of alternatives, including all of the following:
(i)Evaluation of water use at the data center and at the site of energy generation.
(ii)Evaluation of impact on source water and water scarcity.
(iii)Consideration of closed-loop cooling.
(E)A detailed estimate of indirect water use associated with energy production disaggregated by generation type.
(F)A cost-of-service study completed by the applicable water provider within the last five years, or funded by the data center if none exists.
(b)Notwithstanding any other law, a city, county, or city and county shall not approve a discretionary or ministerial permit or other entitlement that would result in the construction, or expansion that increases the maximum peak water use, of a data center unless all of the following conditions are satisfied:
(1)The applicant has provided the city, county, or city and county with all of the following:
(A)A water supply assessment that was completed pursuant to Part 2.10 (commencing with Section 10910) of Division 6 of the Water Code, if applicable.
(B)Upon request of the city, county, or city and county, a water use assessment, as defined in paragraph (2) of subdivision (a).
(C)Beginning January 1, 2028, a water scarcity plan, as defined in paragraph (1) of subdivision (a).
(D)Projected and actual water use and water efficiency measures.
(E)Disclosures regarding workforce needs associated with the project, including all of the following:
(i)Workforce composition.
(ii)Job classifications.
(iii)Employment duration.
(iv)Wage ranges and benefits.
(v)The proportion of the workforce residing within the county in which the project is located.
(vi)The proportion of the workforce residing within the state.
(vii)All water resource plans, water usage reports, supporting documentation, and any approvals issued by a state or local agency related to the plans or applications.
(2)The construction or expansion is not located within the boundaries of a groundwater basin designated as critically overdrafted by the Department of Water Resources. The department may waive this prohibition upon a comprehensive assessment demonstrating that the project does not pose a disproportionate risk to the health, welfare, or environment of an environmental justice community or equity investment eligible community.(3)(2)The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the Department of Water Resources or the applicable water supplier.
SEC. 2.Section 10609.13 is added to the Water Code, to read:10609.13.(a)The department, in coordination with the board, shall conduct necessary studies and investigations and recommend, no later than June 30, 2028, a CII water use classification system for users that qualify as large consumptive use facilities, including data centers. The classification system required by this section shall be separate and distinct from classifications applicable to other CII water use.
(b)(1)The board, in coordination with the department, shall adopt the classification for CII water use required by this section on or before December 31, 2029.
(2)Each urban retail water supplier shall implement the classification adopted by the board pursuant to paragraph (1).
SEC. 3.The Legislature finds and declares that water conservation is a matter of statewide concern and is not a municipal affair as that term is used in Section 5 of Article XI of the California Constitution. Therefore, Section 1 of this act adding Section 65964.7 to the Government Code applies to all cities, including charter cities.
SEC. 4.No reimbursement is required by this act pursuant to Section 6 of Article XIIIB of the California Constitution because a local agency or school district has the authority to levy service charges, fees, or assessments sufficient to pay for the program or level of service mandated by this act, within the meaning of Section 17556 of the Government Code.
(a)For purposes of this section:
(1)Water scarcity plan means a report that includes measures to be implemented under 25-, 50-, and 100-year drought scenarios, during an abnormally dry year, as moderate drought year, a severe drought year, and extreme drought year, and an exceptional drought year, as defined by the United States drought monitor, including staged withdrawal reductions, nonessential use curtailment, recycling and reuse, thermal load reductions, and temporary load shedding where necessary.
(2)Water use assessment means a report that includes all of the following:
(A)A description of the data center, including its location, identification of the owner and operator, and a detailed description of operations.
(B)A detailed accounting of expected water intake, expressed in gallons per day and total volume, including:
(i)Maximum and average daily demand.
(ii)Maximum and average monthly demand.
(iii)Demand over an average 12-month consecutive period.
(iv)A distinction between withdrawals and deliveries.(iv)Water withdrawals.
(v)Phases of growth or expansion.
(vi)Trigger points for additional demand.
(vii)Full build-out and peak operation scenarios.
(C)A detailed explanation of each direct water use, including including, but not limited to, cooling systems, humidification, potable and sanitary uses, fire suppression systems, and commissioning or maintenance operations. For each use, the assessment includes identification of all of the following:
(i)Input water quality requirements.
(ii)Whether the use is consumptive.
(iii)Average daily consumptive volume.
(iv)Whether the use is continuous, intermittent, or seasonal.
(v)Opportunities for reuse or closed-loop systems.
(D)A cooling alternatives analysis that compares the proposed cooling method to a range of alternatives, including all of the following:
(i)Evaluation of water use at the data center and at the site of energy generation.
(ii)Evaluation of impact on source water and water scarcity.
(iii)Consideration of closed-loop cooling.
(E)A detailed estimate of indirect water use associated with energy production disaggregated by generation type.
(F)A cost-of-service study completed by the applicable water provider within the last five years, or funded by the data center if none exists.
(b)Notwithstanding any other law, a city, county, or city and county shall not approve a discretionary or ministerial permit or other entitlement that would result in the construction, or expansion that increases the maximum peak water use, of a data center unless all of the following conditions are satisfied:
(1)The applicant has provided the city, county, or city and county with all of the following:
(A)A water supply assessment that was completed pursuant to Part 2.10 (commencing with Section 10910) of Division 6 of the Water Code, if applicable.
(B)Upon request of the city, county, or city and county, a water use assessment, as defined in paragraph (2) of subdivision (a).
(C)Beginning January 1, 2028, a water scarcity plan, as defined in paragraph (1) of subdivision (a).
(D)Projected and actual water use and water efficiency measures.
(E)Disclosures regarding workforce needs associated with the project, including all of the following:
(i)Workforce composition.
(ii)Job classifications.
(iii)Employment duration.
(iv)Wage ranges and benefits.
(v)The proportion of the workforce residing within the county in which the project is located.
(vi)The proportion of the workforce residing within the state.
(vii)All water resource plans, water usage reports, supporting documentation, and any approval issues approvals issued by a state or local agency related to the plans or applications.
(2)The construction or expansion is not located within the boundaries of a groundwater basin designated as critically overdrafted by the Department of Water Resources. The department may waive this prohibition upon a comprehensive assessment demonstrating that the project does not pose a disproportionate risk to the health, welfare, or environment of an environmental justice community or equity investment eligible community.
(3)The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the Department of Water Resources or the applicable water supplier.
SEC. 2.Section 10609.13 is added to the Water Code, to read:10609.13.(a)The department, in coordination with the board, shall conduct necessary studies and investigations and recommend, no later than ____, June 30, 2028, a CII water use classification system for users that qualify as large consumptive use facilities, including data centers. The classification system required by this section shall be separate and distinct from classifications applicable to other CII water use.
(b)(1)The board, in coordination with the department, shall adopt the classification for CII water use required by this section on or before ____. December 31, 2029.
(2)Each urban retail water supplier shall implement the classification adopted by the board pursuant to paragraph (1).
SEC. 3.The Legislature finds and declares that water conservation is a matter of statewide concern and is not a municipal affair as that term is used in Section 5 of Article XI of the California Constitution. Therefore, Section 1 of this act adding Section 65964.7 to the Government Code applies to all cities, including charter cities.
SEC. 4.No reimbursement is required by this act pursuant to Section 6 of Article XIIIB of the California Constitution because a local agency or school district has the authority to levy service charges, fees, or assessments sufficient to pay for the program or level of service mandated by this act, within the meaning of Section 17556 of the Government Code.
(a)For purposes of this section:
(1)Water scarcity plan means a report that includes measures to be implemented under 25-, 50-, and 100-year drought scenarios, including staged withdrawal reductions, nonessential use curtailment, recycling and reuse, thermal load reductions, and temporary load shedding where necessary.
(2)Water use assessment means a report that includes all of the following:
(A)A description of the data center, including its location, identification of the owner and operator, and a detailed description of operations.
(B)A detailed accounting of expected water intake, expressed in gallons per day and total volume, including:
(i)Maximum and average daily demand.
(ii)Maximum and average monthly demand.
(iii)Demand over an average 12-month consecutive period.
(iv)A distinction between withdrawals and deliveries.
(v)Phases of growth or expansion.
(vi)Trigger points for additional demand.
(vii)Full build-out and peak operation scenarios.
(C)A detailed explanation of each direct water use, including cooling systems, humidification, potable and sanitary uses, fire suppression systems, and commissioning or maintenance operations. For each use, the assessment includes identification of all of the following:
(i)Input water quality requirements.
(ii)Whether the use is consumptive.
(iii)Average daily consumptive volume.
(iv)Whether the use is continuous, intermittent, or seasonal.
(v)Opportunities for reuse or closed-loop systems.
(D)A cooling alternatives analysis that compares the proposed cooling method to a range of alternatives, including all of the following:
(i)Evaluation of water use at the data center and at the site of energy generation.
(ii)Evaluation of impact on source water and water scarcity.
(iii)Consideration of closed-loop cooling.
(E)A detailed estimate of indirect water use associated with energy production disaggregated by generation type.
(F)A cost-of-service study completed within the last five years, or funded by the data center if none exists.
(b)Notwithstanding any other law, a city, county, or city and county shall not approve a discretionary or ministerial permit or other entitlement that would result in the construction, or expansion that increases the maximum peak use, of a data center unless all of the following conditions are satisfied:
(1)The applicant has provided the city, county, or city and county with all of the following:
(A)A water supply assessment that was completed pursuant to Part 2.10 (commencing with Section 10910) of Division 6 of the Water Code, if applicable.
(B)Upon request of the city, county, or city and county, a water use assessment, as defined in paragraph (2) of subdivision (a).
(C)Beginning January 1, 2028, a water scarcity plan, as defined in paragraph (1) of subdivision (a).
(D)Projected and actual water use and water efficiency measures.
(E)Disclosures regarding workforce needs associated with the project, including all of the following:
(i)Workforce composition.
(ii)Job classifications.
(iii)Employment duration.
(iv)Wage ranges and benefits.
(v)The proportion of the workforce residing within the county in which the project is located.
(vi)The proportion of the workforce residing within the state.
(vii)All water resource plans, water usage reports, supporting documentation, and any approval issues by a state or local agency related to the plans or applications.
(2)The construction or expansion is not located within the boundaries of a groundwater basin designated as critically overdrafted by the Department of Water Resources. The department may waive this prohibition upon a comprehensive assessment demonstrating that the project does not pose a disproportionate risk to the health, welfare, or environment of an environmental justice community or equity investment eligible community.
(3)The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the Department of Water Resources or the applicable water supplier.
SEC. 2.Section 10609.13 is added to the Water Code, to read:10609.13.(a)The department, in coordination with the board, shall conduct necessary studies and investigations and recommend, no later than ____, a CII water use classification system for users that qualify as large consumptive use facilities, including data centers. The classification system required by this section shall be separate and distinct from classifications applicable to other CII water use.
(b)(1)The board, in coordination with the department, shall adopt the classification for CII water use required by this section on or before ____.
(2)Each urban retail water supplier shall implement the classification adopted by the board pursuant to paragraph (1).
SEC. 3.The Legislature finds and declares that water conservation is a matter of statewide concern and is not a municipal affair as that term is used in Section 5 of Article XI of the California Constitution. Therefore, Section 1 of this act adding Section 65964.7 to the Government Code applies to all cities, including charter cities.
SEC. 4.No reimbursement is required by this act pursuant to Section 6 of Article XIIIB of the California Constitution because a local agency or school district has the authority to levy service charges, fees, or assessments sufficient to pay for the program or level of service mandated by this act, within the meaning of Section 17556 of the Government Code.
SECTION 1.Section 13500 of the Water Code is amended to read:13500.This chapter shall be known, and may be cited, as the Water Recycling Law.This chapter shall be known as known, and may be cited cited, as the Water Recycling Law.
|
Date
|
Status
|
|---|---|
| Sep 21, 2026 | Chaptered by Secretary of State - Chapter 436, Statutes of 2026. |
| Sep 21, 2026 | Approved by the Governor. |
| Sep 15, 2026 | Enrolled and presented to the Governor at 3 p.m. |
| Aug 31, 2026 | Senate amendments concurred in. To Engrossing and Enrolling. (Ayes 61. Noes 12. Page 6968.). |
| Aug 31, 2026 | Senate amendments concurred in. To Engrossing and Enrolling. (Ayes 61. Noes 12.). |
| Aug 31, 2026 | Senate amendments concurred in. To Engrossing and Enrolling. |
| Aug 30, 2026 | In Assembly. Concurrence in Senate amendments pending. |
| Aug 30, 2026 | Read third time. Passed. Ordered to the Assembly. (Ayes 28. Noes 9.). |
| Aug 28, 2026 | Read second time. Ordered to third reading. |
| Aug 27, 2026 | Read third time and amended. Ordered to second reading. |
| Aug 17, 2026 | Read second time. Ordered to third reading. |
| Aug 13, 2026 | Read second time and amended. Ordered returned to second reading. |
| Aug 13, 2026 | From committee: Amend, and do pass as amended. (Ayes 4. Noes 2.) (August 13). |
| Aug 10, 2026 | In committee: Referred to APPR. suspense file. |
| Aug 3, 2026 | In committee: Set, first hearing. Hearing canceled at the request of author. |
| Jul 2, 2026 | Read second time and amended. Re-referred to Com. on APPR. |
| Jul 2, 2026 | From committee: Amend, and do pass as amended and re-refer to Com. on APPR. (Ayes 5. Noes 2.) (July 1). |
| Jun 24, 2026 | From committee: Do pass and re-refer to Com. on L. GOV. (Ayes 4. Noes 1.) (June 23). Re-referred to Com. on L. GOV. |
| Jun 15, 2026 | From committee chair, with author's amendments: Amend, and re-refer to committee. Read second time, amended, and re-referred to Com. on N.R. & W. |
| Jun 10, 2026 | Referred to Coms. on N.R. & W. and L. GOV. |
| May 28, 2026 | In Senate. Read first time. To Com. on RLS. for assignment. |
| May 27, 2026 | Read third time. Passed. Ordered to the Senate. (Ayes 61. Noes 14. Page 5464.) |
| May 27, 2026 | Read third time. Passed. Ordered to the Senate. (Ayes 61. Noes 14.) |
| May 27, 2026 | Read third time. Passed. Ordered to the Senate. |
| May 22, 2026 | Read third time and amended. Ordered to third reading. (Page 5274.) |
| May 22, 2026 | Read third time and amended. Ordered to third reading. |
| May 18, 2026 | Read second time. Ordered to third reading. |
| May 14, 2026 | From committee: Do pass. (Ayes 11. Noes 4.) (May 14). |
| May 6, 2026 | In committee: Set, first hearing. Referred to APPR. suspense file. |
| Apr 23, 2026 | From committee: Do pass and re-refer to Com. on APPR. (Ayes 8. Noes 2.) (April 22). Re-referred to Com. on APPR. |
| Apr 15, 2026 | From committee: Do pass and re-refer to Com. on L. GOV. (Ayes 9. Noes 2.) (April 14). Re-referred to Com. on L. GOV. |
| Apr 9, 2026 | Re-referred to Com. on W., P., & W. |
| Apr 8, 2026 | From committee chair, with author's amendments: Amend, and re-refer to Com. on W., P., & W. Read second time and amended. |
| Mar 17, 2026 | Re-referred to Com. on W., P., & W. |
| Mar 16, 2026 | From committee chair, with author's amendments: Amend, and re-refer to Com. on W., P., & W. Read second time and amended. |
| Mar 16, 2026 | Referred to Coms. on W., P., & W. and L. GOV. |
| Feb 21, 2026 | From printer. May be heard in committee March 23. |
| Feb 20, 2026 | Read first time. To print. |
|
Date
|
Description
|
Location
|
Votes
|
|
|---|---|---|---|---|
| Aug 31, 2026 | AB 2469 Papan Concurrence in Senate Amendments | Assembly Floor |
Passed |
|
| Aug 30, 2026 | Assembly 3rd Reading AB2469 Papan By Durazo | Senate Floor |
Passed |
|
| Aug 13, 2026 | Do pass as amended | Senate Standing Committee on Appropriations |
Passed |
|
| Aug 10, 2026 | Placed on suspense file | Senate Standing Committee on Appropriations |
Passed |
|
| Jul 1, 2026 | Do pass as amended, but first amend, and re-refer to the Committee on [Appropriations] | Senate Standing Committee on Local Government |
Passed |
|
| Jun 23, 2026 | Do pass, but first be re-referred to the Committee on [Local Government] | Senate Standing Committee on Natural Resources and Water |
Passed |
|
| May 27, 2026 | AB 2469 Papan Assembly Third Reading | Assembly Floor |
Passed |
|
| May 14, 2026 | Do pass. | Assembly Standing Committee on Appropriations |
Passed |
|
| Apr 22, 2026 | Do pass and be re-referred to the Committee on [Appropriations] | Assembly Standing Committee on Local Government |
Passed |
|
| Apr 14, 2026 | Do pass and be re-referred to the Committee on [Local Government] | Assembly Standing Committee on Water, Parks, and Wildlife |
Passed |
This list shows positions taken on this bill by organizations on the date displayed, which is linked to the original source.
Positions by individuals are not included.
|
Organization
|
Position
|
Date
|
|---|---|---|
| 7th Generation Advisors | ** Support | |
| Bay Area Council | ** Against | |
| Building Owners and Managers Association of California | ** Against | |
| CalAsian Chamber of Commerce | ** Against | |
| California African American Chamber Of Commerce | ** Against | |
| California Broadband & Video Association | ** Against | |
| California Broadband & Video Association (unless amended) | ** Against | |
| California Business Properties Association | ** Against | |
| California Chamber Of Commerce | ** Against | |
| California Coastal Protection Network | ** Support | |
| California Coastkeeper Alliance | ** Support | |
| California Environmental Voters | ** Support | |
| California Hispanic Chamber Of Commerce | ** Against | |
| California Manufacturers & Technology Association (CMTA) | ** Against | |
| California State Association Of Counties | ** Against | |
| Center For Biological Diversity | ** Support | |
| Center For Public Environmental Oversight | ** Support | |
| cleanearth4kids.org | ** Support | |
| Clean Water Action | ** Support | |
| Communitiy Water Center | ** Support | |
| Community Alliance With Family Farmers | ** Support | |
| Data Center Coalition | ** Against | |
| Fix the World Consulting, LLC | ** Support | |
| League Of California Cities | ** Against | |
| Los Angeles Waterkeeper | ** Support | |
| Naiop California | ** Against | |
| NRDC | ** Support | |
| Planning And Conservation League | ** Support | |
| Resource Renewal Institute | ** Support | |
| Rural County Representatives of California | ** Against | |
| Sierra Club California | ** Support | |
| Silicon Valley Leadership Group (SVLG) | ** Against | |
| Techca | ** Against | |
| Technet | ** Against |
CONCURRENCE IN SENATE AMENDMENTS
CSA1 Bill Id:AB 2469
Author:(Papan)
As Amended Ver:August 27, 2026
Majority vote
SUMMARY
Prohibits a local agency from approving construction of a new, or expansion of an existing, data center unless the project applicant provides the local agency with a water supply assessment, a water scarcity plan (beginning January 1, 2028), and other disclosures regarding the workforce needs associated with the data center project. Requires a data center proponent to assume the full cost of any water infrastructure upgrades necessary to provide water service to the data center.
Senate Amendments
- Delete the requirement that an applicant for a discretionary or ministerial permit for a data center project complete a water use assessment upon the request of a city, county, or city and county.
- Delete the definition of ″water use assessment.″
- Delete the requirement for the Department of Water Resources (DWR) to determine the increased cost of water conveyance, water treatment or storage, or water distribution infrastructure improvements necessary for a data center project. These costs are to be solely determined by the applicable water supplier.
- Delete the requirement that DWR, in coordination with the State Water Resources Control Board (State Water Board), conduct studies and investigations to develop a definition and estimate of annual water use consumption by large commercial, industrial, and institutional (CII) facilities, including data centers, by June 30, 2028.
- Add a severability clause regarding the provision of this bill that requires a data center proponent to assume the full cost of any water infrastructure upgrades necessary to provide water service to the data center.
COMMENTS
Data centers are buildings or facilities that ″support servers, digital storage equipment, and network infrastructure for the purpose of large-scale data processing and data storage. Increasing demand for data creation, processing, and storage from existing and emerging technologies, such as online platforms/social media, video streaming, smart and connected infrastructure, autonomous vehicles, and artificial intelligence, has led to exponential growth in data center workloads and compute instances″ (Bakar Siddik, Shehabi, and Marston, 2021). There is increasing awareness of the energy and water demands (primarily related to cooling) associated with data centers as artificial intelligence and other technologies are being deployed.
Data centers can have substantial and sometimes irregular demand for cooling water. All computer chips produce heat as waste energy from the electricity flowing through them. While this heat is minimal in the context of a personal computer, data centers made up of thousands of servers produce an immense amount of heat that needs to be removed from the facility to maintain safety and performance. To manage this heat, data centers use a variety of cooling technologies, either sequentially or depending on weather conditions and server load.
Data center water use patterns can be irregular as a result of switching between cooling technologies. Research shows that the ″peaking factor″ (the factor of the peak use over average use) for data centers can be double or more the peaking factor for other large users (Han et al. 2026). These high peaks occur because data centers need to shift to evaporative cooling technologies to exhaust waste heat during hot and dry weather conditions, or use more water to remove more heat. Shifting between cooling technologies can result in large surges in demand that need to be accommodated by water distribution infrastructure, even if the average demand is far lower.
Evaporative cooling systems, like those sometimes used in data centers, are consumptive uses of water. This bill would require data center operators to distinguish their consumptive and nonconsumptive water uses. Consumptive water use refers to water that is withdrawn or diverted from the environment that is made unavailable for future use because it has evaporated, transpired, been incorporated into products or crops, or otherwise been made unavailable for immediate use. In contrast, non-consumptive uses of water quickly return to the environment. Examples of non-consumptive use include recreation, hydroelectric power generation, or instream flow.
Data centers need a reliable water supply. Due to the reliability requirement to deliver the demanded water, water infrastructure (both water delivery and wastewater) must be sized to accommodate the peaks in demand. Local water suppliers are then required to build capacity well in excess of average need and potentially may build capacity in excess of any need that materializes, especially if they are building based on limited information about projected water demand.
Better data about water use, whether during the water supply assessment process (if required, see discussion below) or based on research data from across the sector, would assist local water agencies in planning for actual need. Local water utilities could also work with data centers to understand options for the times of highest demand and collaborate on strategies to deliver water supply reliability. The risk of stranded or overbuilt assets can be mitigated by requiring new large customers to pay for necessary infrastructure upgrades as part of the connection process, potentially extending beyond traditional connection fees to include upgrades to mains, pumping stations, and other infrastructure as needed.
Water use by data centers falls under the CII classification, but is not calculated under the urban water use objective (″Making Conservation A Way of Life″) intended to increase water use efficiency in California′s urban areas. However, as required by the legislative package to enact Making Conservation a Way of Life, DWR conducted a study (completed in 2022) on CII water use and recommended performance measures to the State Water Board that would improve water use efficiency in the CII sector. One of the study′s recommendations was to require urban retail water suppliers to classify their CII users by one of 19 user types (e.g., manufacturing/industrial, technology/science). The State Water Board incorporated this recommendation into the final Making Conservation a Way of Life regulations by requiring urban retail water suppliers to classify CII users into one of 22 categories by June 30, 2027; the categories are based on the ENERGY STAR Portfolio Manager categories. This bill requires DWR to develop a separate classification for CII users based on their consumptive use of water by June 30, 2028.
A water supply assessment is required for a proposed project (CII or otherwise) with a water use that exceeds certain thresholds and is completed as part of the California Environmental Quality Act process. The water use threshold that triggers the requirement for a water supply assessment is generally the amount of water required for a proposed residential development of more than 500 dwelling units or commercial or industrial uses that are of defined sizes (Water Code § 10912). To complete the water supply assessment, the project proponent must provide information to municipal planning decisionmakers about the expected water use. The water supply assessment process provides the primary opportunity for public input and awareness of water use by a proposed CII (or other) water user.
According to the Author
″California′s finite water supplies are under growing stress from climate change, prolonged drought, and the expansion of large consumptive water users. While the Legislature has long recognized the importance of coordinating land use decisions with available water supplies, the rapid growth of data centers has exposed gaps in existing law. Data centers represent a new kind of development that can impose significant, highly concentrated water demands on local systems.
″This gap is particularly important because data centers operate continuously and can drive substantial peak-day demand, often requiring new treatment, storage, or distribution infrastructure. Without timely and standardized information during the entitlement process, municipalities and water retailers may lack clear visibility into a project′s water needs and the leverage to ensure that adequate supplies, infrastructure capacity, and conservation measures are in place before service commitments are made.
″[This bill] directly addresses this problem. The bill requires meaningful water planning before local approval and directs state agencies to better identify and manage large consumptive water users. In doing so, [this bill] gives local governments and water suppliers the information they need to evaluate data center water demand before irreversible siting and infrastructure decisions are made.″
Arguments in Support
The California Coastkeeper Alliance supports this bill and argues that it will inform local decision-making, condition data center project approvals on meeting necessary requirements, and avoid increased water rates resulting from data center water demand. California Coastkeeper Alliance states: ″By requiring data center project applicants to assume responsibility for the costs of water infrastructure additions required to serve their needs, [this bill] would also ensure ratepayers do not end up bearing the costs of infrastructure they do not create demand for. This principle is consistent with the ″proportional cost of service″ requirement in California′s Constitution. Additionally, the bill appropriately allocates risk to project applicants, ensuring that if a facility closes prematurely, water suppliers and ultimately ratepayers will not end up footing the bill for disused infrastructure.″
Arguments in Opposition
The Data Center Coalition opposes this bill and maintains it imposes ″additional burdensome and disparate reporting requirements on data centers as compared to other″ CII users, raises privacy and security concerns, and will undermine California′s already shrinking data center market. Rather than placing unique requirements on data centers, the Data Center Coalition asserts ″a more equitable approach would acknowledge that data centers are just one water consumer among many diverse industries. Data center operators are actively prioritizing responsible water use through operational best practices and innovative development strategies, often collaborating with local authorities and conservation organizations on water restoration and reclamation projects.″
FISCAL COMMENTS
According to the Senate Appropriations Committee, this bill will result in unknown, but likely minor costs, for DWR and the State Water Board.
VOTES:
ASM WATER, PARKS, AND WILDLIFE: 9-2-2
YES: Papan, Alvarez, Ávila Farías, Bennett, Boerner, Caloza, Hart, Muratsuchi, Rogers
NO: Jeff Gonzalez, Alanis
ABS, ABST OR NV: Bains, Gallagher
ASM LOCAL GOVERNMENT: 8-2-0
YES: Carrillo, Pacheco, Ramos, Ransom, Blanca Rubio, Stefani, Ward, Wilson
NO: Ta, Johnson
ASM APPROPRIATIONS: 11-4-0
YES: Wicks, Aguiar-Curry, Calderon, Caloza, Fong, Mark González, Krell, Pacheco, Pellerin, Sharp-Collins, Solache
NO: Hoover, Dixon, Ta, Tangipa
ASSEMBLY FLOOR: 61-14-5
YES: Addis, Aguiar-Curry, Ahrens, Alanis, Alvarez, Arambula, Ávila Farías, Bauer-Kahan, Bennett, Berman, Boerner, Bonta, Bryan, Calderon, Caloza, Carrillo, Connolly, Elhawary, Fong, Gabriel, Garcia, Gipson, Jeff Gonzalez, Mark González, Haney, Harabedian, Hart, Irwin, Jackson, Kalra, Krell, Lee, Lowenthal, Macedo, McKinnor, Muratsuchi, Nguyen, Ortega, Pacheco, Papan, Patel, Pellerin, Petrie-Norris, Quirk-Silva, Ramos, Ransom, Michelle Rodriguez, Rogers, Blanca Rubio, Sanchez, Schiavo, Schultz, Sharp-Collins, Solache, Soria, Stefani, Ward, Wicks, Wilson, Zbur, Rivas
NO: Castillo, Chen, DeMaio, Dixon, Ellis, Flora, Hadwick, Hoover, Johnson, Patterson, Ta, Tangipa, Valencia, Wallis
ABS, ABST OR NV: Bains, Davies, Gallagher, Lackey, Celeste Rodriguez
UPDATED
VERSION: August 27, 2026
CONSULTANT: Pablo Garza / W., P., & W. / (916) 319-2096 FN: 0004538
SENATE RULES COMMITTEE Office of Senate Floor Analyses (916) 651-4171 | AB 2469 |
THIRD READING
Bill No: AB 2469
Author: Papan (D)
Amended: 8/27/26 in Senate
Vote: 21
SENATE NATURAL RES. & WATER COMMITTEE: 4-1, 6/23/26
AYES: Becker, Allen, Laird, Stern
NOES: Seyarto
NO VOTE RECORDED: Cabaldon, Grove
SENATE LOCAL GOVERNMENT COMMITTEE: 5-2, 7/1/26
AYES: Durazo, Arreguín, Ashby, Cervantes, Laird
NOES: Choi, Seyarto
ASSEMBLY FLOOR: 61-14, 5/27/26 - See last page for vote
SUBJECT: Data centers: water use disclosures
SOURCE: Author
DIGEST:
This bill imposes requirements on cities and counties to meet before they can issue permits to proposed data center projects.
Senate Floor amendments of 8/27/26 inserted a severability clause into the bill to ensure that if one provision is determined to be invalid, that determination would not invalidate the entire bill.
ANALYSIS:
Existing law:
- Requires a water supplier to prepare a water supply assessment for residential, commercial, or industrial projects that must undergo review under the California Environmental Quality Act (CEQA) and will use more than a specified amount of water.
- Allows cities and counties to make and enforce “all local, police, sanitary and other ordinances and regulations not in conflict with general laws.” It is from this fundamental state constitutional power (commonly called the “police power”) that cities and counties derive their authority to regulate behavior to preserve the health, safety, and welfare of the public, including land use authority.
- Requires the state to reduce urban per capita water use by 20% December 31, 2020, and requires each urban retail water supplier to establish their own target to help meet the statewide 20% reduction goal.
This bill:
- Prohibits a city or county from approving a permit or other entitlement that would result in the construction or expansion of a data center that increases the maximum peak water use unless:
- The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the water supplier.
- The applicant has provided the city or county with:
- A water supply assessment;
- As of January 1, 2028, a water scarcity plan;
- Projected water use and water efficiency measures; and
- Disclosures regarding workforce needs associated with the project.
- States this bill should not be construed to require a city or county to approve any permit request from a data center solely because the applicant has complied with this bill’s provisions.
- Includes a severability clause, stating that if a provision requiring a data center project applicant to assume full responsibility for the cost of any water conveyance, treatment, storage, or distribution infrastructure improvements necessary to serve the project is found to be invalid, that shall not invalidate the remaining provisions of this bill.
Background
Data centers. Data centers are facilities that support information technology servers, digital storage equipment, and network infrastructure for large-scale data processing and data storage. Increasing demand for data creation, processing, and storage from existing and emerging technologies, such as online platforms/social media, video streaming, smart and connected infrastructure, autonomous vehicles, and artificial intelligence has led to exponential growth in data center workloads.
Cooling technology and water demand. Data centers can have substantial and sometimes irregular demands for cooling water. All computer chips produce heat as waste energy from the electricity flowing through them. While this heat is minimal in the context of a personal computer, data centers made up of thousands of servers produce an immense amount of heat that needs to be removed from the facility to maintain safety and performance. To manage this heat, data centers use a variety of cooling technologies, including:
- Air-based cooling.
- Chilled water systems
- Evaporative cooling systems.
- Liquid cooling.
- Economization technologies.
Many data centers combine several technologies and the blend of possible technologies introduces tradeoffs between electricity and water use (and between onsite and offsite water use).
Implications for water infrastructure. Data centers – like all businesses, residential customers, and other water users – need a reliable water supply. Absent reliable information about expected usage, water suppliers must make infrastructure decisions based on estimates and projections that may or may not come true, meaning they could wind up under- or over-building water supply systems.
Improving planning and coordination. Better data about water use, whether during the water supply assessment process or based on research data from across the sector, would help local water agencies better plan to meet actual needs. Local water utilities could work with data centers to understand the times of highest demand and collaborate on strategies to deliver water supply reliability.
The risk of stranded or overbuilt assets can be mitigated by requiring new large customers to pay for necessary water infrastructure upgrades as part of the connection process, potentially extending beyond traditional connection fees to include upgrades to mains, pumping stations, and other needed infrastructure.
CII water use. A 2022 Department of Water Resources (DWR) study on commercial, industrial, and institutional (CII) water use recommended performance measures to the State Water Resources Control Board (SWRCB) to improve water use efficiency in the CII sector, one of which was to require urban retail water suppliers to classify their CII users by one of 19 user types (e.g., manufacturing/industrial, technology/science, etc.). The SWRCB incorporated this recommendation into regulations, requiring urban retail water suppliers to classify CII users into one of 22 categories by June 30, 2027.
Comments
Purpose of the bill. According to the author, “California’s finite water supplies are under growing stress from climate change, prolonged drought, and the expansion of large consumptive water users. While the Legislature has long recognized the importance of coordinating land use decisions with available water supplies, the rapid growth of data centers has exposed gaps in existing law. Data centers represent a new kind of development that can impose significant, highly concentrated water demands on local systems.
“This gap is particularly important because data centers operate continuously and can drive substantial peak-day demand, often requiring new treatment, storage, or distribution infrastructure. Without timely and standardized information during the entitlement process, municipalities and water retailers may lack clear visibility into a project’s water needs and the leverage to ensure that adequate supplies, infrastructure capacity, and conservation measures are in place before service commitments are made
“AB 2469 directly addresses this problem. The bill requires meaningful water planning before local approval and directs state agencies to better identify and manage large consumptive water users. In doing so, AB 2469 gives local governments and water suppliers the information they need to evaluate data center water demand before irreversible siting and infrastructure decisions are made.”
Seeing the whole field – for one sector. This bill requires data centers to submit certain information to a city or county before the city or county can issue an entitlement for the project. This information includes a water supply assessment, a water scarcity plan, and projected water use and water efficiency plan – accompanied by certain disclosures regarding workforce needs of the project.
However, this bill doesn’t apply these same requirements to other CII sectors or users with similar water demands. So, while this bill will provide cities, counties, and water suppliers with more information about projected water demand, they still will not have a complete picture since this measure only applies to a slice of the state’s largest water users.
Similarly, this bill’s requirement to create a “water scarcity plan” detailing how water users will reduce their usage if asked or required to only applies to data centers.
FISCAL EFFECT: Appropriation: No Fiscal Com.: Yes Local: Yes
According to the Senate Appropriations Committee’s analysis, the bill will impose minor costs on DWR and the SWRCB.
SUPPORT: (Verified 8/27/26)
7th Generation Advisors
California Coastal Protection Network
California Coastkeeper Alliance
California Environmental Voters
Center for Biological Diversity
Center for Public Environmental Oversight
Clean Water Action
Cleanearth4kids.org
Community Alliance With Family Farmers
Fix the World Consulting, LLC
Los Angeles Waterkeeper
Planning and Conservation League
Resource Renewal Institute
Sierra Club California
OPPOSITION: (Verified 8/27/26)
Bay Area Council
Building Owners and Managers Association of California
CalAsian Chamber of Commerce
California African American Chamber of Commerce
California Broadband & Video Association
California Business Properties Association
California Chamber of Commerce
California Hispanic Chamber of Commerce
California State Association of Counties
Data Center Coalition
League of California Cities
NAIOP California
Rural County Representatives of California
Silicon Valley Leadership Group (SVLG)
TechCA
TechNet
ASSEMBLY FLOOR: 61-14, 5/27/26
AYES: Addis, Aguiar-Curry, Ahrens, Alanis, Alvarez, Arambula, Ávila Farías, Bauer-Kahan, Bennett, Berman, Boerner, Bonta, Bryan, Calderon, Caloza, Carrillo, Connolly, Elhawary, Fong, Gabriel, Garcia, Gipson, Jeff Gonzalez, Mark González, Haney, Harabedian, Hart, Irwin, Jackson, Kalra, Krell, Lee, Lowenthal, Macedo, McKinnor, Muratsuchi, Nguyen, Ortega, Pacheco, Papan, Patel, Pellerin, Petrie-Norris, Quirk-Silva, Ramos, Ransom, Michelle Rodriguez, Rogers, Blanca Rubio, Sanchez, Schiavo, Schultz, Sharp-Collins, Solache, Soria, Stefani, Ward, Wicks, Wilson, Zbur, Rivas
NOES: Castillo, Chen, DeMaio, Dixon, Ellis, Flora, Hadwick, Hoover, Johnson, Patterson, Ta, Tangipa, Valencia, Wallis
NO VOTE RECORDED: Bains, Davies, Gallagher, Lackey, Celeste Rodriguez
Prepared by: Evan Goldberg / N.R. & W. / (916) 651-4116
8/28/26 11:28:52
**** END ****
SENATE RULES COMMITTEE Office of Senate Floor Analyses (916) 651-4171 | AB 2469 |
THIRD READING
Bill No: AB 2469
Author: Papan (D)
Amended: 8/13/26 in Senate
Vote: 21
SENATE NATURAL RES. & WATER COMMITTEE: 4-1, 6/23/26
AYES: Becker, Allen, Laird, Stern
NOES: Seyarto
NO VOTE RECORDED: Cabaldon, Grove
SENATE LOCAL GOVERNMENT COMMITTEE: 5-2, 7/1/26
AYES: Durazo, Arreguín, Ashby, Cervantes, Laird
NOES: Choi, Seyarto
SENATE APPROPRIATIONS COMMITTEE: 4-2, 8/13/26
AYES: Cervantes, Grayson, Richardson, Wahab
NOES: Seyarto, Dahle
NO VOTE RECORDED: Cabaldon
ASSEMBLY FLOOR: 61-14, 5/27/26 - See last page for vote
SUBJECT: Data centers: water use disclosures
SOURCE: Author
DIGEST: This bill
imposes requirements on cities and counties to meet before they can issue permits to proposed data center projects.
ANALYSIS:
Existing law:
- Requires a water supplier to prepare a water supply assessment for residential, commercial, or industrial projects that must undergo review under the California Environmental Quality Act (CEQA) and will use more than a specified amount of water.
- Allows cities and counties to make and enforce “all local, police, sanitary and other ordinances and regulations not in conflict with general laws.” It is from this fundamental state constitutional power (commonly called the “police power”) that cities and counties derive their authority to regulate behavior to preserve the health, safety, and welfare of the public, including land use authority.
- Requires the state to reduce urban per capita water use by 20% December 31, 2020, and requires each urban retail water supplier to establish their own target to help meet the statewide 20% reduction goal.
This bill:
- Prohibits a city or county from approving a permit or other entitlement that would result in the construction or expansion of a data center that increases the maximum peak water use unless:
- The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the water supplier.
- The applicant has provided the city or county with:
- A water supply assessment;
- As of January 1, 2028, a water scarcity plan;
- Projected water use and water efficiency measures; and
- Disclosures regarding workforce needs associated with the project.
- States this bill should not be construed to require a city or county to approve any permit request from a data center solely because the applicant has complied with the bill’s provisions.
Background
Data centers. Data centers are facilities that support information technology servers, digital storage equipment, and network infrastructure for large-scale data processing and data storage. Increasing demand for data creation, processing, and storage from existing and emerging technologies, such as online platforms/social media, video streaming, smart and connected infrastructure, autonomous vehicles, and artificial intelligence has led to exponential growth in data center workloads.
Cooling technology and water demand. Data centers can have substantial and sometimes irregular demands for cooling water. All computer chips produce heat as waste energy from the electricity flowing through them. While this heat is minimal in the context of a personal computer, data centers made up of thousands of servers produce an immense amount of heat that needs to be removed from the facility to maintain safety and performance. To manage this heat, data centers use a variety of cooling technologies, including:
- Air-based cooling.
- Chilled water systems
- Evaporative cooling systems.
- Liquid cooling.
- Economization technologies.
Many data centers combine several technologies and the blend of possible technologies introduces tradeoffs between electricity and water use (and between onsite and offsite water use).
Implications for water infrastructure. Data centers – like all businesses, residential customers, and other water users – need a reliable water supply. Absent reliable information about expected usage, water suppliers must make infrastructure decisions based on estimates and projections that may or may not come true, meaning they could wind up under- or over-building water supply systems.
Improving planning and coordination. Better data about water use, whether during the water supply assessment process or based on research data from across the sector, would help local water agencies better plan to meet actual needs. Local water utilities could work with data centers to understand the times of highest demand and collaborate on strategies to deliver water supply reliability.
The risk of stranded or overbuilt assets can be mitigated by requiring new large customers to pay for necessary water infrastructure upgrades as part of the connection process, potentially extending beyond traditional connection fees to include upgrades to mains, pumping stations, and other needed infrastructure.
CII water use. A 2022 Department of Water Resources (DWR) study on commercial, industrial, and institutional (CII) water use recommended performance measures to the State Water Resources Control Board (SWRCB) to improve water use efficiency in the CII sector, one of which was to require urban retail water suppliers to classify their CII users by one of 19 user types (e.g., manufacturing/industrial, technology/science, etc.). The SWRCB incorporated this recommendation into regulations, requiring urban retail water suppliers to classify CII users into one of 22 categories by June 30, 2027.
Comments
Purpose of the bill. According to the author, “California’s finite water supplies are under growing stress from climate change, prolonged drought, and the expansion of large consumptive water users. While the Legislature has long recognized the importance of coordinating land use decisions with available water supplies, the rapid growth of data centers has exposed gaps in existing law. Data centers represent a new kind of development that can impose significant, highly concentrated water demands on local systems.
“This gap is particularly important because data centers operate continuously and can drive substantial peak-day demand, often requiring new treatment, storage, or distribution infrastructure. Without timely and standardized information during the entitlement process, municipalities and water retailers may lack clear visibility into a project’s water needs and the leverage to ensure that adequate supplies, infrastructure capacity, and conservation measures are in place before service commitments are made
“AB 2469 directly addresses this problem. The bill requires meaningful water planning before local approval and directs state agencies to better identify and manage large consumptive water users. In doing so, AB 2469 gives local governments and water suppliers the information they need to evaluate data center water demand before irreversible siting and infrastructure decisions are made.”
Seeing the whole field – for one sector. This bill requires data centers to submit certain information to a city or county before the city or county can issue an entitlement for the project. This information includes a water supply assessment, a water scarcity plan, and projected water use and water efficiency plan – accompanied by certain disclosures regarding workforce needs of the project.
However, this bill doesn’t apply these same requirements to other CII sectors or users with similar water demands. So, while this bill will provide cities, counties, and water suppliers with more information about projected water demand, they still will not have a complete picture since this measure only applies to a slice of the state’s largest water users.
Similarly, this bill’s requirement to create a “water scarcity plan” detailing how water users will reduce their usage if asked or required to only applies to data centers.
FISCAL EFFECT: Appropriation: No Fiscal Com.: Yes Local: Yes
According to the Senate Appropriations Committee’s analysis, the bill will impose minor costs on DWR and the SWRCB.
SUPPORT: (Verified 8/6/26)
7th Generation Advisors
California Coastal Protection Network
California Coastkeeper Alliance
California Environmental Voters
Center for Biological Diversity
Center for Public Environmental Oversight
Clean Water Action
Cleanearth4kids.org
Community Alliance With Family Farmers
Fix the World Consulting, LLC
Los Angeles Waterkeeper
Planning and Conservation League
Resource Renewal Institute
Sierra Club California
OPPOSITION: (Verified 8/6/26)
Bay Area Council
Building Owners and Managers Association of California
CalAsian Chamber of Commerce
California African American Chamber of Commerce
California Broadband & Video Association
California Business Properties Association
California Chamber of Commerce
California Hispanic Chamber of Commerce
California State Association of Counties
Data Center Coalition
League of California Cities
NAIOP California
Rural County Representatives of California
Silicon Valley Leadership Group (SVLG)
TechCA
TechNet
ASSEMBLY FLOOR: 61-14, 5/27/26
AYES: Addis, Aguiar-Curry, Ahrens, Alanis, Alvarez, Arambula, Ávila Farías, Bauer-Kahan, Bennett, Berman, Boerner, Bonta, Bryan, Calderon, Caloza, Carrillo, Connolly, Elhawary, Fong, Gabriel, Garcia, Gipson, Jeff Gonzalez, Mark González, Haney, Harabedian, Hart, Irwin, Jackson, Kalra, Krell, Lee, Lowenthal, Macedo, McKinnor, Muratsuchi, Nguyen, Ortega, Pacheco, Papan, Patel, Pellerin, Petrie-Norris, Quirk-Silva, Ramos, Ransom, Michelle Rodriguez, Rogers, Blanca Rubio, Sanchez, Schiavo, Schultz, Sharp-Collins, Solache, Soria, Stefani, Ward, Wicks, Wilson, Zbur, Rivas
NOES: Castillo, Chen, DeMaio, Dixon, Ellis, Flora, Hadwick, Hoover, Johnson, Patterson, Ta, Tangipa, Valencia, Wallis
NO VOTE RECORDED: Bains, Davies, Gallagher, Lackey, Celeste Rodriguez
Prepared by: Evan Goldberg / N.R. & W. / (916) 651-4116
8/17/26 10:03:08
**** END ****
SENATE COMMITTEE ON
Senator Sabrina Cervantes, Chair
2025 - 2026 Regular Session
AB 2469 (Papan) - Data centers: water use disclosures
Version: | Policy Vote: |
Urgency: | Mandate: |
Hearing Date: | Consultant: |
Bill Summary:
This bill would prohibit cities and counties from approving a discretionary or ministerial permit for the construction or expansion of a data center unless the applicant has provided specified water use and workforce information and assumed the full cost of water infrastructure needed to serve the project. It would also require the Department of Water Resources (DWR) to develop an estimate of annual water consumption for CII water users that qualify as large consumptive-use facilities, including data centers.
*********** ANALYSIS ADDENDUM – SUSPENSE FILE ***********
The following information is revised to reflect amendments
adopted by the committee on August 13, 2026
Fiscal Impact:
- Unknown but likely minor costs for DWR and the State Water Board.
Author Amendments:
Author amendments would eliminate DWR's role in determining the full cost of water infrastructure improvements.
-- END --
SENATE COMMITTEE ON
Senator Sabrina Cervantes, Chair
2025 - 2026 Regular Session
AB 2469 (Papan) - Data centers: water use disclosures
Version: | Policy Vote: |
Urgency: | Mandate: |
Hearing Date: | Consultant: |
Bill Summary:
This bill would prohibit cities and counties from approving a discretionary or ministerial permit for the construction or expansion of a data center unless the applicant has provided specified water use and workforce information and assumed the full cost of water infrastructure needed to serve the project. It would also require the Department of Water Resources (DWR) to develop an estimate of annual water consumption for CII water users that qualify as large consumptive-use facilities, including data centers.
Fiscal Impact:
- DWR estimates ongoing costs of $2 million in the first year and $500,000 annually thereafter (General Fund or other fund) to collect data, conduct technical studies and analysis, and coordinate with water suppliers in developing a definition and estimate of annual water consumption for these facilities, and to continue coordinating with water suppliers as the data center sector grows and changes.
- The State Water Board anticipates its costs would be minor and absorbable.
Background:
Data centers are buildings or facilities that support servers, digital storage equipment, and network infrastructure for large-scale data processing and storage. Increasing demand for data creation, processing, and storage from existing and emerging technologies, including artificial intelligence, has led to rapid growth in data center workloads, and with it increasing attention to the energy and water demands — primarily for cooling — associated with these facilities. Estimates of direct onsite water consumption vary by facility type and size, ranging from about 18,000 gallons per day for smaller facilities to approximately 300,000 gallons per day for a mid-sized data center and around 550,000 gallons per day for a hyperscale facility. Because data centers shift between cooling technologies depending on weather and server load, their water demand can be irregular, with peaks well above average use.
Water supply assessments. Existing law requires a water supply assessment for a proposed residential, commercial, or industrial project that exceeds specified water use thresholds. The assessment is prepared by the public water system identified to serve the project or, where none is identified, by the city or county, and must be incorporated into the project's review under CEQA. The assessment describes the project's expected water use and the supplier's ability to meet it; where supplies are found insufficient, the preparer must set forth plans for acquiring additional supplies.
Existing CII water use classification requirements. Existing law required DWR, in coordination with the State Water Board, to conduct studies and develop recommendations for efficient water use by commercial, industrial, and institutional (CII) water users. DWR's study, completed in 2022, recommended that urban retail water suppliers classify their CII users by user type. The State Water Board incorporated this recommendation into its Making Conservation a Way of Life regulations, which require urban retail water suppliers to classify CII users into one of 22 categories by June 30, 2027. Water used in data center cooling falls within the regulations' definition of "process water," which is excluded from state water efficiency targets and reporting.
Water infrastructure and cost recovery. Because water delivery and wastewater infrastructure must be sized to accommodate peak rather than average demand, large new customers with irregular demand patterns can require suppliers to build capacity well in excess of average need, with the risk of stranded assets if projects do not materialize or close. Under existing law, local agencies recover infrastructure costs from new development through connection fees, which pay for the physical facilities needed to connect a structure to the system, and capacity charges, which cover a customer's proportional share of systemwide infrastructure needed to serve added demand; these fees cannot exceed the estimated reasonable cost of providing the service.
Proposed Law:
This bill would:
- Prohibit a city, county, or city and county from approving a discretionary or ministerial permit or other entitlement that would result in the construction, or expansion that increases the maximum peak water use, of a data center unless all of the following conditions are met:
- The applicant has provided the city, county, or city and county with all of the following:
- A water supply assessment, as described.
- Upon request of the city, county, or city and county, a water use assessment, as defined by the bill.
- Commencing January 1, 2028, a water scarcity plan, as defined by the bill.
- Projected water use and water efficiency measures.
- Disclosures regarding workforce needs associated with the project, as specified.
- The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by DWR or the applicable water supplier.
- Provide that the above shall not be construed to require a city, county, or city and county to approve a permit, entitlement, or other approval for the construction or expansion of a data center solely because the applicant has satisfied the requirements.
- Require DWR, in coordination with the State Water Board, to conduct necessary studies and investigations to develop a definition and estimate of annual water consumption, no later than June 30, 2028, for CII water users that qualify as large consumptive-use facilities, including data centers and similar water consumption patterns, excluding CII outdoor irrigation water use served through a dedicated irrigation meter.
- Impose a state-mandated local program by expanding the duties of local agencies to administer these provisions.
- Include findings that the changes proposed by this bill address a matter of statewide concern rather than a municipal affair and, therefore, apply to all cities, including charter cities.
- Provide that no reimbursement is required by this bill for a specified reason.
Related Legislation:
AB 2619 (Papan, 2026) would require data centers, when applying for a business license, to provide their expected water use to their water supplier and to the appropriate city or county and, when renewing a license, to report their annual water use to the appropriate city or county. The bill would also require DWR and the State Energy Resources Conservation and Development Commission (CEC) to develop guidelines and best practices to maximize the efficient use of natural resources to address developing and emerging needs of technology, and would require DWR to develop guidance that cities and counties may use for assessing projected water use, water efficiency measures, and cumulative water resources impacts of proposed data centers.
AB 93 (Papan, 2025) was similar to AB 2619. The bill was vetoed.
AB 755 (Papan, 2023) requires a public entity to conduct a water usage demand analysis before completing, or as part of, a cost-of-service analysis conducted to set fees and charges for water service.
Staff Comments:
Reduced uncertainty. If DWR's definition and consumption estimate improves demand forecasting, there could potentially be some savings associated with planning and avoided overbuilding as a result of this bill, which would accrue mainly to local water suppliers and their ratepayers.
Reimbursable mandate costs. To the extent the Commission on State Mandates determines that the provisions of this bill create a new program or impose a higher level of service on local agencies, local agencies could claim reimbursement of those costs, which could have a General Fund impact. By prohibiting cities and counties from approving a discretionary or ministerial permit as provided, this bill would impose new duties on local agencies. This bill provides that no reimbursement is required because local agencies have the authority to levy service charges, fees, or assessments sufficient to pay for the mandated program.
-- END --
SENATE COMMITTEE ON LOCAL GOVERNMENT
Senator María Elena Durazo, Chair
2025 - 2026 Regular
Bill No: | AB 2469 | Hearing Date: | 7/1/26 |
Author: | Papan | Fiscal: | Yes |
Version: | 6/15/26 | Consultant: | Peterson |
Data centers: water use disclosures
Prohibits a city or county from approving a discretionary or ministerial permit or entitlement that would result in construction or expansion that increases the maximum peak water use of a data center unless the data center meets specified conditions.
Background
Planning and approving new housing is mainly a local responsibility. The California Constitution allows cities and counties to “make and enforce within its limits, all local, police, sanitary and other ordinances and regulations not in conflict with general laws.” It is from this fundamental power (commonly called the police power) that cities and counties derive their authority to regulate behavior to preserve the health, safety, and welfare of the public—including land use authority.
Planning and Zoning Law. State law provides additional powers and duties for cities and counties regarding land use. The Planning and Zoning Law requires every county and city to adopt a general plan that sets out planned uses for all of the area the plan covers. Cities’ and counties’ major land use decisions—including most zoning ordinances and other aspects of development permitting—must be consistent with their general plans.
Water supply planning for new development. An urban water supplier with more than 3,000 customers must adopt an urban water management plan (UWMP). An important component of a UWMP is an assessment of water service reliability during normal, dry, and multiple-dry years. Part of that analysis requires information about the availability of groundwater supplies.
Cities and counties must consider information provided by water suppliers when they act on proposals for large-scale residential, commercial, hotel, industrial, or mixed-use projects (SB 901, Costa, 1995). Every large-scale development project—proposing 500 or more new connections or an equivalent size for other uses—must have a water supply assessment (WSA) (SB 610, Costa, 2001), prepared according to the following process:
- First, a city or county, at the time that it determines that a development is subject to the California Environmental Quality Act (CEQA), must identify any water system that may supply water for the project;
- If the proposed project was included in the UWMP of one of the identified systems, the water system prepares the WSA for the project; and
- If the projected demand was not accounted for, or the city or county was not able to identify a water system to serve the project, the city or county prepares the assessment, in consultation with the local agency formation commission and other relevant water systems.
A WSA must identify any existing water supply entitlements, water rights, or water service contracts relevant to the identified water supply for the proposed project, and describe the quantities of water received in prior years by the public water system or the city or county through its water rights or other sources.
If a water supply for a proposed project includes groundwater, the WSA must include additional information, including a description of any groundwater basins that will supply the project, the court or SWRCB order if the basin is adjudicated, and an analysis of the sufficiency of the groundwater from the basin or basins. Following the enactment of the Sustainable Groundwater Management Act (SGMA) in 2014, which comprehensively reformed California’s groundwater laws, the Legislature updated the requirements for projects that rely on groundwater to integrate SGMA and the WSA statutes.
If, as a result of its WSA, the water system, or city or county if it is preparing the WSA, concludes that its water supplies are, or will be, insufficient, it must provide plans for acquiring additional water supplies, and set forth the measures that are being undertaken to acquire and develop those water supplies.
The WSA must be completed within 90 days of the request by the city or county, but the water system may request a 30 day extension. Once completed, the WSA must be incorporated into the analysis of the project under the California Environmental Quality Act (CEQA).
Data centers. Data centers are buildings or facilities that “support servers, digital storage equipment, and network infrastructure for the purpose of large-scale data processing and data storage. Increasing demand for data creation, processing, and storage from existing and emerging technologies, such as online platforms/social media, video streaming, smart and connected infrastructure, autonomous vehicles, and artificial intelligence, has led to exponential growth in data center workloads and compute instances.”[1] Data centers use a lot of water. This is because, “[l]ike cooling systems in large office buildings, water often is evaporated in data center cooling towers, leaving behind salty wastewater known as blowdown that has to be treated by local utilities.”[2] A mid-sized data center uses 300,000 gallons of water a day, enough for 1,000 households, and data centers rank among the top ten industrial and commercial water users.[3]
The author wants to require local agencies to consider more information before they approve or expand data centers.
Proposed Law
Assembly Bill 2469 prohibits a city or county from approving a discretionary or ministerial permit or entitlement that would result in construction or expansion that increases the maximum peak water use of a data center unless all the following conditions are met:
- The applicant has provided the city or county all the following:
- A water supply assessment if applicable; and
- Upon request of the city or county, a water use assessment for the construction or expansion;
- Beginning January 1, 2028, a water scarcity plan;
- Projected water use and water efficiency measures; and
- Specified disclosures regarding workforce needs associated with the project.
- The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by the Department of Water Resources (DWR) or the applicable water supplier.
DWR, in coordination with the State Water Resources Control Board (SWRCB), must conduct necessary studies and investigations before recommending, no later than June 30, 2028, a water use classification system for large-consumptive use facilities, including data centers, distinct from other water uses.
The SWRCB, in coordination with DWR, must adopt the classification for water use on or before December 31, 2029. Each urban retail water supplier must implement this classification.
AB 2469 defines its terms.
Comments
1. Purpose of the bill. According to the author, “California’s finite water supplies are experiencing growing stress from climate change, prolonged drought, and the expansion of large consumptive water users. While the Legislature has long recognized the importance of coordinating land use decisions with available water supplies, the rapid growth of data centers has exposed gaps in existing law. Data centers represent a new kind of development that can impose significant, highly concentrated water demands on local systems.
“This gap is particularly important because data centers operate continuously and can drive substantial peak-day demand, often requiring new treatment, storage, or distribution infrastructure. Without timely and standardized information during the entitlement process, municipalities and water retailers may lack clear visibility into a project’s water needs and the leverage to ensure that adequate supplies, infrastructure capacity, and conservation measures are in place prior to entering into service commitments.
“AB 2469 directly addresses these water management difficulties. AB 2469 requires meaningful water planning before local approval and protects critically overdrafted groundwater basins. In doing so, AB 2469 provides local governments and water suppliers the information they need to evaluate data center water demand before making irreversible siting and infrastructure decisions.”
2. Home rule. State law leaves many decisions about how local agencies approve projects up to the local agencies themselves. This ensures that important decisions, like whether to locate a data center in their jurisdiction, are made by the local agencies that most directly reflect the community’s values. Instead, AB 2469 mandates a statewide project approval process for data centers. AB 2469 does not prohibit a local agency from approving a data center, but it does require it to receive more comprehensive information than many other projects before it can approve it. This could make approving data centers more difficult or more time consuming. Additionally, creating a process that satisfies AB 2469’s requirements may be more costly for local agencies to implement, which local agencies will likely have to pass on to permit applicants. While AB 2469 does so in an effort to further important water conservation goals, local agencies may have a better sense of what information they need to make informed decisions about local water needs for data centers than the State Legislature. The Committee may wish to consider whether decisions over how to approve data centers are better left up to local agencies.
3. Tell me more? AB 2469 requires data centers, as a condition of local approval, to assume responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project. However, the measure does not specify exactly how DWR or the water supplier is supposed to calculate the full cost, which leaves open some questions about what costs the data center is responsible for paying. Some common costs that developers pay are connection fees and capacity charges. A local agency assesses a connection fee when it physically connects a structure to the water or sewer system, which pays for the physical facilities necessary to make a water connection or sewer connection, such as meters, meter boxes, pipelines, and the estimated reasonable cost of labor and materials for their installation of those facilities. A local agency assesses a capacity charge on the customer to cover the proportional cost of maintaining or constructing system wide infrastructure necessary to meet the additional water or sewer demand for new users of the system. When a local agency imposes water or sewer connection fees or capacity charges, the fees or charges cannot exceed the estimated reasonable cost of providing the service without the fee becoming a tax requiring 2/3 voter approval. If a data center pays a required capacity charge, does that count as paying the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project? The Committee may wish to consider whether AB 2469 provides sufficient direction to water suppliers and data centers as far as what costs they are subject to paying.
4. The times they are a changin’. The Senate Committee on Rules has ordered a double referral of AB 2469: first to the Committee on Natural Resources and Water, which approved AB 2469 at its June 23rd hearing on a vote of 4-1, and second to the Committee on Local Government. At its hearing, the Committee on Natural Resources and Water approved the measure with committee amendments to limit the contents of the water use assessments. Due to timing, the Committee on Natural Resources and Water requested that these amendments be taken as committee amendments in the Committee on Local Government.
In addition, the author has requested the Committee adopt author amendments to:
- Clarify that the measure’s water supply assessment provisions do not alter a project’s applicability to the California Environmental Quality Act;
- Clarify that, even if the city or county receives all the necessary information, they do not have to approve a data center project; and
- Replace provisions requiring DWR to create a classification system for large-consumptive use facilities with a requirement to develop a definition and estimate of annual water consumption for these users.
5. Related legislation. AB 2619 (Papan) requires data center owners to submit specified information on water use when they apply for a local business license or renew an existing one. The measure is also scheduled for the Committee’s July 1st hearing.
6. Charter city. AB 2469 says that its statutory provisions apply to charter cities. To support this assertion, the bill includes a legislative finding and declaration that water conservation is a matter of statewide concern, not a municipal affair. Because the Constitution does not define “municipal affairs,” the courts determine whether a topic is a municipal affair or whether it is an issue of statewide concern.
7. Mandate. The California Constitution requires the state to reimburse local governments for the costs of new or expanded state mandated local programs. Because AB 2469 imposes new duties on local governments, Legislative Counsel says it imposes a new state mandate. AB 2469 disclaims the state’s responsibility for providing reimbursement by citing local governments’ authority to charge for the costs of implementing the bill’s provisions.
Assembly Actions
Assembly Water, Parks, and Wildlife Committee: 9-2
Assembly Local Government Committee: 8-2
Assembly Appropriations Committee: 11-4
Assembly Floor: 61-14
Support and Opposition
(6/26/26)
Support: 7th Generation Advisors
California Coastal Protection Network
California Coastkeeper Alliance
California Environmental Voters
Center for Biological Diversity
Center for Public Environmental Oversight
Clean Water Action
Cleanearth4kids.org
Communitiy Water Center
Community Alliance With Family Farmers
Fix the World Consulting, LLC
Los Angeles Waterkeeper
Nrdc
Planning and Conservation League
Resource Renewal Institute
Sierra Club California
Opposition: Bay Area Council
Building Owners and Managers Association of California
Calasian Chamber of Commerce
Calbroadband
California African American Chamber of Commerce
California Business Properties Association
California Chamber of Commerce
California Hispanic Chambers of Commerce (CHCC)
California Manufacturers & Technology Association (CMTA)
California State Association of Counties (CSAC)
Data Center Coalition
League of California Cities
Naiop California
Rural County Representatives of California (RCRC)
Silicon Valley Leadership Group (SVLG)
Techca
Technet
-- END --
Md Abu Bakar Siddik, Arman Shehabi, and Landon Marston, “The Environmental Footprint of Data Centers in the United States,” Environmental Research Letters, 16 (2021). ↑
https://www.npr.org/2022/08/30/1119938708/data-centers-backbone-of-the-digital-economy-face-water-scarcity-and-climate-ris ↑
Ibid. ↑
SENATE COMMITTEE ON NATURAL RESOURCES AND WATER
Senator Josh Becker, Chair
2025 - 2026 Regular
Bill No: AB Hearing Date: June 23, 2026
Author: | |||
Version: | Amended | ||
Urgency: | Fiscal: | ||
Consultant: | |||
Subject: Data centers: water use disclosures
SUMMARY
This bill would prohibit a city, county, or city and county, from approving a discretionary or ministerial permit of a data center unless the applicant has provided a water supply assessment, a water use assessment if requested by the local jurisdiction, a water scarcity plan, projected water use and water efficiency measures, and disclosures regarding workforce needs associated with the project. The bill would also require the Department of Water Resources to conduct studies and investigations and recommend a commercial, industrial, and institutional water use classification system for users that qualify as large consumptive use facilities, including data centers.
BACKGROUND AND EXISTING LAW
Data centers.
Data centers are buildings or facilities that “support servers, digital storage equipment, and network infrastructure for the purpose of large-scale data processing and data storage. Increasing demand for data creation, processing, and storage from existing and emerging technologies, such as online platforms/social media, video streaming, smart and connected infrastructure, autonomous vehicles, and artificial intelligence, has led to exponential growth in data center workloads and compute instances.”[1] There is increasing awareness of the energy and water demands (primarily related to cooling) associated with data centers as artificial intelligence (AI) and other technologies are being deployed.
While California has been home to data centers for decades, in recent years, developments in technology have increased the demand for large data centers capable of storing, processing, and serving huge amounts of data. California is a desirable destination for data center projects, with a highly skilled workforce, close proximity to computing demand, and access to large fiber optic connections around the world. Clusters of data centers exist in Silicon Valley, San Francisco, Los Angeles, and Sacramento, with other projects located around the state.
Data Centers and Water Use.
Although data centers are estimated to be among the top ten water consuming industries in the United States their water use and related impacts are understudied, and approaches for managing water use and impacts have not kept pace with the industry’s rapid growth.[2] According to a report by UC Berkeley Center for Law, Energy & the Environment California, Regulating Data Center Water Use in California (CLEE report), water use by data centers can strain local and regional water supplies and adversely impact ecosystems; it is estimated that about one-fifth of U.S. data centers used water from water-stressed watersheds in 2021, and an estimated two-thirds of the data centers built since 2022 are located in areas of high water stress. Some of the fastest-growing data center hubs in the United States are in semi-arid West – often in areas that experience frequent droughts or chronic water scarcity.
Data centers use a lot of water. A data center’s on-site water use depends on its location, the cooling technologies it employs, its operational water usage efficiency, and more. Data centers produce tremendous heat that must be removed from the facility to maintain safety and performance. Estimates for direct-onsite water consumption vary by facility type and size. These estimates range from about 18,000 gallons per day for smaller wholesale and retail data centers to approximately 300,000 gallons per day for a mid-sized data center, and around 550,000 gallons per day for a hyperscale data center.
Not only do data centers use large volumes of water, the volume of water needed at any particular time can be irregular. Data centers use a variety of cooling technologies, either sequentially or depending on weather conditions and server load. Data center water use patterns can be irregular as a result of switching between these cooling technologies, including high demand peaks that water distribution infrastructure must be designed to accommodate, even if the average demand is far lower. Water infrastructure (both water delivery and wastewater) must be sized to accommodate these peaks in demand.
Cooling technology and water demand. Data centers can have substantial and sometimes irregular demand for cooling water. All computer chips produce heat as waste energy from the electricity flowing through them. While this heat is minimal in the context of a personal computer, data centers made up of thousands of servers produce an immense amount of heat that needs to be removed from the facility to maintain safety and performance. To manage this heat, data centers use a variety of cooling technologies, including:
- Air-based cooling. Chilled air is circulated through server racks using computer room air conditioners or air handlers to remove heat from equipment.
- Chilled water systems. Mechanical chillers produce chilled water that absorbs heat from servers through heat exchangers before the heat is rejected outdoors.
- Evaporative cooling systems. Cooling towers or evaporative coolers use the evaporation of water to remove heat, which can significantly reduce electricity use but increases water consumption.
- Liquid cooling. Coolant is delivered directly to server components or through cold plates and immersion systems, allowing heat to be removed more efficiently than with air cooling.
- Economization technologies. Air-side or water-side economizers take advantage of cool outdoor air or water temperatures to reduce the need for mechanical cooling when environmental conditions allow.
Many data centers combine several technologies either sequentially or depending on weather conditions and server load. The blend of possible technologies introduces tradeoffs between electricity and water use (and between onsite and offsite water use).
Irregular water demand and peak use. Data center water use patterns can be irregular as a result of switching between cooling technologies. Research shows that the “peaking factor” (the factor of the peak use over average use) for data centers can be double or more the peaking factor for other large users.[3]. These high peaks occur because data centers need to shift to evaporative cooling technologies to exhaust waste heat during hot and dry weather conditions, or use more water to remove more heat. Shifting between cooling technologies can result in large surges in demand that need to be accommodated by water distribution infrastructure, even if the average demand is far lower.
Consumptive water use. Evaporative cooling systems, like those sometimes used in data centers, are consumptive uses of water. This bill would require data center operators to distinguish their consumptive and nonconsumptive water uses. Consumptive water uses refers to water that is withdrawn or diverted from the environment that is made unavailable for future use because it has evaporated, transpired, been incorporated into products or crops, or otherwise been made unavailable for immediate use. In contrast, non-consumptive uses of water quickly return to the environment. Examples of non-consumptive use include recreation, hydroelectric power generation, or instream flow.
Scale of potential demand. Existing and proposed data centers range from relatively small “edge” or collocated facilities to huge “hyperscalers,” including a proposed $10 billion, 330 MW project in Imperial County that could use as much as 750,000 gallons of water per day. As data centers continue to surge in growth, concerns about data center water use are driving discussions around sustainability, evaluations of appropriate location siting, and available supply.
Implications for water infrastructure. Data centers need a reliable water supply. Due to the reliability requirement to deliver the demanded water, water infrastructure (both water delivery and wastewater) must be sized to accommodate the peaks in demand. Local water suppliers are then required to build capacity well in excess of average need and potentially may build capacity in excess of any need that materializes, especially if they are building based on limited information about projected water demand.
Absent reliable information about expected usage, water infrastructure decisions are based on estimates and projections that may or may not be borne out. In practice, this limited visibility compounds the general trend across California water agencies to project (and build for) higher water use than is actually realized.[4] In addition to overbuilding for capacity, local water suppliers risk stranded assets if data center projects either do not materialize or close. In an industry characterized by many proposed projects with fewer constructed projects and rapid obsolescence of cutting-edge technology, these risks are meaningful and may exacerbate concerns over water affordability.
Improving planning and coordination. Better data about water use, whether during the water supply assessment process (if required, see discussion below) or based on research data from across the sector, would assist local water agencies in planning for actual need. Local water utilities could also work with data centers to understand options for the times of highest demand and collaborate on strategies to deliver water supply reliability.[5] The risk of stranded or overbuilt assets can be mitigated by requiring new large customers to pay for necessary infrastructure upgrades as part of the connection process, potentially extending beyond traditional connection fees to include upgrades to mains, pumping stations, and other infrastructure as needed.
CII water use. Water use by data centers falls under the CII classification, but is not calculated under the urban water use objective (“Making Conservation A Way of Life”) intended to increase water use efficiency in California's urban areas. However, as required by the legislative package to enact Making Conservation a Way of Life, DWR conducted a study (completed in 2022) on CII water use and recommended performance measures to the State Water Board that would improve water use efficiency in the CII sector. One of the study’s recommendations was to require urban retail water suppliers to classify their CII users by one of 19 user types (e.g., manufacturing/industrial, technology/science). The State Water Board incorporated this recommendation into the final Making Conservation a Way of Life regulations by requiring urban retail water suppliers to classify CII users into one of 22 categories by June 30, 2027; the categories are based on the ENERGY STAR Portfolio Manager categories. This bill requires DWR to develop a separate classification for CII users that qualify as large consumptive use facilities, including data centers, by June 30, 2028.
Water supply assessments. A water supply assessment is required for a proposed project (CII or otherwise) with a water use that exceeds certain thresholds and is completed as part of the CEQA process. The water use thresholds that trigger a water supply assessment are as follows (Water Code § 10912):
- A proposed residential development of more than 500 dwelling units;
- A proposed shopping center or business establishment employing more than 1,000 persons or having more than 500,000 square feet of floor space;
- A proposed commercial office building employing more than 1,000 persons or having more than 25,000 square feet of floor space;
- A proposed hotel or motel that has more than 500 rooms;
- A proposed industrial, manufacturing, or processing plant, or industrial park planned to house more than 1,000 persons, occupying more than 40 acres of land, or having more than 650,000 square feet of floor area;
- A proposed mixed-use project that includes one or more of the above; and
- A proposed project that would demand an amount of water equivalent to, or greater than, the amount of water required by a 500 dwelling unit project.
- A proposed residential development of more than 500 dwelling units;
To complete the water supply assessment, the project proponent must provide information to municipal planning decisionmakers about the expected water use. The water supply assessment process provides the primary opportunity for public input and awareness of water use by a proposed CII (or other) water user.
Planning and Approving New Development.
Planning and approving new development is mainly a local responsibility. The California Constitution allows cities and counties to “make and enforce within its limits, all local, police, sanitary and other ordinances and regulations not in conflict with general laws.” It is from this fundamental power (commonly called the police power) that cities and counties derive their authority to regulate behavior to preserve the health, safety, and welfare of the public – including land use authority. Cities and counties enforce this land use authority through zoning regulations, as well as through an “entitlement process” for obtaining discretionary as well as ministerial approvals.
The scale of the proposed development and the existing environmental setting determine the degree of local review that occurs. For larger developments, the local entitlement process commonly requires multiple discretionary decisions regarding the subdivision of land, environmental review pursuant to the California Environmental Quality Act (CEQA), design review, and project review by the local agency’s legislative body (city council or county board) or by a planning commission delegated by the legislative body.
Existing law:
- Requires DWR, in coordination with the State Water Board, to conduct studies and investigations to develop recommendations for efficient water use by commercial, industrial, and institutional (CII) water users by October 1, 2021. The State Water Board shall adopt performance measures for CII water use based on these recommendations by June 30, 2022 (Water Code § 10609.10).
- Requires a water supplier to prepare a water supply assessment for a residential, commercial, or industrial project that must undergo review under CEQA) and will use more than a specified amount of water (see discussion under Background, above). The water supply assessment must contain information regarding the project’s water use and the ability of the water supplier to meet the project’s water demands (Water Code § 10910 et seq.).
- Allows cities and counties to “make and enforce within its limits, all local, police, sanitary and other ordinances and regulations not in conflict with general laws.” It is from this fundamental power (commonly called the police power) that cities and counties derive their authority to regulate behavior to preserve the health, safety, and welfare of the public, including land use authority (California Constitution, Article XI, § 7).
- Establishes the California Energy Commission with various responsibilities with respect to developing and implementing the state’s energy policies (Public Resources Code § 25000 et seq.).
- Requires the state to achieve a 20% reduction in urban per capita water use by December 31, 2020 (20x2020 target) and requires each urban retail water supplier to establish their own target to contribute towards achieving the statewide 20% reduction goal (Water Code §§ 10608.16, 10608.20) (SB 7x 7).
- Requires the DWR, in coordination with the State Water Board, to conduct studies and investigations to develop recommendations for efficient water use by commercial, industrial, and institutional (CII) water users by October 1, 2021. The State Water Board shall adopt performance measures for CII water use based on these recommendations by June 30, 2022 (Water Code § 10609.10).
PROPOSED LAW
This bill would:
- Prohibit a city, county, or city and county from approving a discretionary or ministerial permit or other entitlement that would result in the construction, or expansion that increases the maximum peak water use, of a data center unless the following conditions are met:
- The applicant has provided the city, county, or city and county with all of the following:
- A water supply assessment, as described.
- Upon request of the city, county, or city and county, a water use assessment, as defined by the bill.
- Commencing January 1, 2028, a water scarcity plan, as defined by the bill.
- Projected water use and water efficiency measures.
- Disclosures regarding workforce needs associated with the project, as specified.
- The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project, as determined by DWR or the applicable water supplier.
- The applicant has provided the city, county, or city and county with all of the following:
- Require DWR, in coordination with the State Water Resources Control Board (State Water Board) to conduct necessary studies and investigations and recommend, no later than June 30, 2028, a CII water use classification system for users that qualify was large consumptive use facilities, including data centers. The classification system is required to be separate and distinct from classifications applicable to other CII water use.
- Require the State Water Board, in coordination with DWR, to adopt the classification for CII water use by December 31, 2029.
- Require each urban retail water supplier to implement the above-described classification adopted by the State Water Board.
ARGUMENTS IN SUPPORT
According to the author, “California’s finite water supplies are under growing stress from climate change, prolonged drought, and the expansion of large consumptive water users. While the Legislature has long recognized the importance of coordinating land use decisions with available water supplies, the rapid growth of data centers has exposed gaps in existing law. Data centers represent a new kind of development that can impose significant, highly concentrated water demands on local systems.”
“This gap is particularly important because data centers operate continuously and can drive substantial peak-day demand, often requiring new treatment, storage, or distribution infrastructure. Without timely and standardized information during the entitlement process, municipalities and water retailers may lack clear visibility into a project’s water needs and the leverage to ensure that adequate supplies, infrastructure capacity, and conservation measures are in place before service commitments are made.”
“AB 2469 directly addresses this problem. The bill requires meaningful water planning before local approval and directs state agencies to better identify and manage large consumptive water users. In doing so, AB 2469 gives local governments and water suppliers the information they need to evaluate data center water demand before irreversible siting and infrastructure decisions are made.”
ARGUMENTS IN OPPOSITION
A coalition letter representing groups such as TechNet and Silicon Valley Leadership Group, among others, argue that “data centers are the backbone of [the] digital economy.” The coalition argues that the bill would “single out data centers for additional levels of reporting to include site-specific operational details as part of … a ‘water use assessment,’ which is not otherwise required of other CII sectors and end users with similar water demands.” The coalition also questions why separate and distinct CII water use classification is needed for “large consumptive use facilities” when data centers are “not an outlier when it comes to water use among CII sectors.” The coalition also argues that the “proposed water reporting requirements could force businesses to disclose sensitive trade secrets, harm their competitive edge, and risk creating safety and security vulnerabilities.”
In addition to the arguments above, California Chamber of Commerce (CalChamber) argues that the “new CII classification for ‘large consumptive use facilities’ is redundant of existing reporting requirements” and does not think that “further classification will bring further focus on water efficiency from those users.”
COMMENTS
This bill is double referred. This bill is double referred with the Senate Local Government Committee, with this committee being the committee of first referral. Elements of this bill under the jurisdiction of the Senate Local Government Committee are included here for context and completeness only and will be discussed before that Committee.
Having a full picture of water usage is essential to smart planning. This bill requires data centers to have submitted certain information to the city or county before the city or county can issue an entitlement for the project. This information includes a water supply assessment, a water use assessment (if requested by the city or county), a water scarcity plan, and certain disclosures regarding workforce needs of the project. The opposition questions why data centers should be required to submit such information, when other CII sectors or other end users with similar water demands. During a time when water supply is limited, it is important for water suppliers and local jurisdictions to know how this finite resource is being used. As pointed out by the CLEE Report, “understanding water use and consumption…, its impact on water resources and communities, and mitigation options is important, especially in drier regions. This includes understanding in what local contexts data center water use is likely to have the most- and least-impacts.” When local jurisdictions have access to this information, they can make fully informed decisions when deciding whether to approve a particular project.
Opponents view the reporting requirements under the bill as punitive towards data centers. It has been argued by requiring data centers to submit a water scarcity plan is punitive because it forces them to demonstrate how they will “shutter operations” during various drought conditions. They have argued that other businesses are not being required to do this. However, if the state is in an abnormally dry year, shouldn’t every one pitch in to help the state be more efficient with its water? It is worth noting while data centers, under the bill, are the only ones required to do a water scarcity plan, there may be similar requirements imposed on other industries – just not in the form of a “water scarcity plan.”
There are various examples of different industries cutting back on water usage during times of drought or in order to help conserve the state’s water uses. For example, the Sustainable Groundwater Management Act requires sustainable groundwater agencies to develop a plan to sustainably manage its groundwater supplies. For some, that plan has required groundwater users to pump less water out of the ground. Agricultural water suppliers are required to adopt agricultural management plans which include, among other requirements, a drought plan for periods of limited water supply describing the actions of the supplier for drought preparedness and management of water supplies and allocations during drought years.
Is the new CII classification redundant of existing law? According CalChamber, requiring DWR and the State Water Board to develop and adopt a specific classification system for “large consumptive use facilities” will add little value above what is already required by existing law. Pursuant to the Making Conservation a California Way of Life regulations urban retail water suppliers are already required to classify every CII customer based on the customer’s end use of water and are required to identify and classify the top 2.5% of overall CII users and the top 20% in each category. Additionally, the urban retail water suppliers are required to implement conservation programs for inefficient water users, applying best management practices and specifically tailored conservation actions for each category. Thus, according to CalChamber large consumptive users will already be identified for water efficiency measures under the existing regulations.
In response, the author’s office argues that it is not redundant, but rather looking at users based on their “consumptive use,” which is different than other uses, even within the CII sector. Under “consumptive use,” water withdrawals are not returned to the local environment and are instead evaporated, transpired, or incorporated into products or crops. As such, a data center is a consumptive user. According to information provided by the author, approximately 80% of the water used by data centers evaporates.[6] While CII classifications are broken down by sector, there hasn’t been an evaluation of the type (consumptive/non-consumptive) of use within those sectors.
Finally, the author argues the need for this additional classification type is because the Making Conservation Way of Life regulations exempt “process water” from efficiency targets and reporting. “Process water” is “water used by industrial water users for producing a product or product content or water used for research and development. Process water includes, but is not limited to, continuous manufacturing processes, and water used for testing, cleaning, and maintaining equipment. Water used to cool machinery or buildings used in the manufacturing process or necessary to maintain product quality or chemical characteristics for product manufacturing or control rooms, data centers, laboratories, clean rooms, and other industrial facility units that are integral to the manufacturing or research and development process is process water. Water used in the manufacturing process that is necessary for complying with local, state, and federal health and safety laws, and is not incidental water, is process water. Process water does not mean incidental water uses” (WAT. §10608.12(y)). The author acknowledges that it is unclear what percentage of CII water use can be attributed to process water, but the definition appears to include a vast majority of indoor industrial water uses, except incidental water uses.
The author argues that the exemption of process water in state water efficiency frameworks means that CII water users did not have to reduce their use of process water by 20% under SB 7x7 and that process water is not calculated as part of the urban water use objectives.
Related legislation
AB 2619 (Papan), of the current legislative session, would require data centers, when applying for a business license, to provide their expected water use to their water supplier and to the appropriate city or county; and when renewing a license, to report their annual water use to the appropriate city or county. This bill would require Department of Water Resources (DWR) and State Energy Resources Conservation and Development Commission (Energy Commission or CEC) to develop guidelines and best practices to maximize the efficient use of natural resources to address developing and emerging needs of technology, and would require DWR to develop guidance that cities and counties may use for assessing projected water use, water efficiency measures, and cumulative water resources impacts of proposed data centers. This bill is pending before this Committee.
AB 93 (Papan, 2025) was similar to AB 2619. AB 93 was vetoed.
AB 755 (Papan, Chapter 542, Statutes of 2023) requires a public entity to conduct a water usage demand analysis, before completing, or as part of, a cost-of-service analysis conducted to set fees and charges for water service.
SUGGESTED AMENDMENTS: Discussions are underway to potentially address concerns of stakeholder groups.
SUPPORT
7th Generation Advisors
California Coastal Protection Network
California Coastkeeper Alliance
California Environmental Voters
Center for Biological Diversity
Center for Public Environmental Oversight
Clean Water Action
Cleanearth4kids.org
Community Alliance With Family Farmers
Fix the World Consulting, LLC
Los Angeles Waterkeeper
Planning and Conservation League
Resource Renewal Institute
Sierra Club California
OPPOSITION
Bay Area Council
Building Owners and Managers Association of California
CalAsian Chamber of Commerce
California African American Chamber of Commerce
California Broadband & Video Association (unless amended)
California Business Properties Association
California Chamber of Commerce
California Hispanic Chamber of Commerce
California State Association of Counties (unless amended)
Data Center Coalition
League of California Cities (unless amended)
NAIOP California
Rural County Representatives of California (unless amended)
Silicon Valley Leadership Group (SVLG)
TechCA
TechNet
-- END --
Md Abu Bakar Siddik, Arman Shehabi, and Landon Marston, “The Environmental Footprint of Data Centers in the United States,” Environmental Research Letters, 16 (2021). ↑
Regulating Data Center Water Use in California, UC Berkeley Center for Law, Energy, & the Environment, February 2026 ↑
Yuelin Han, Pengfei Li, Adam Wierman, and Shaolei Ren, “Small Bottle, Big Pipe: Quantifying and Addressing the Impact of Data Centers on Public Water Systems,” arXiv preprint, doi:10.48550/arXiv.2603.02705 (2026). ↑
Johanna A. Capone and Landon T. Marston, “Water Demand Projection Accuracy and Demand Management Trends in California Cities,” Water Resources Research 61, no. 11 (2025). ↑
Marie Grimm, Nell Green Nylen, and Michael Kiparsky, Regulating Data Center Water Use in California, (Center for Law, Energy & the Environment, UC Berkeley School of Law, Berkeley, CA: 2026), 40-43. See https://www.law.berkeley.edu/data-center-water-use. ↑
Li, P., Yang, J., Islam, M., Ren, S.;Making AI Less “Thirsty”: Uncovering and Addressing the Secret Water Footprint of AI Models, March 2025. ↑
ASSEMBLY THIRD READING
ATR Bill Id:AB 2469
Author:(Papan)
As Amended Ver:May 22, 2026
Majority vote
SUMMARY
Prohibits a local agency from approving construction of a new, or expansion of an existing, data center unless an applicant for a data center project provides the local agency with detailed information regarding the data center′s water use and meets other requirements related to workforce and infrastructure for the data center.
Major Provisions
- Defines ″water scarcity plan″ as a report that includes measures to be implemented under different drought scenarios defined by the U.S. Drought Monitor to reduce water use.
- Defines ″water use assessment″ as a report that includes a description of a data center and its operations and the following information regarding water use by the data center:
- A detailed accounting of water intake expressed in gallons per day and total volume, including maximum and average daily demand, maximum and average monthly demand, demand over an average 12-month period, water withdrawals, phases of growth or expansion, trigger points for additional demand, full build-out and peak operation scenarios;
- A detailed explanation of each direct water use including specified information regarding cooling systems, humidification, potable and sanitary uses, fire suppression systems, and maintenance operations;
- A cooling alternatives analysis that compares the proposed cooling method to a range of alternatives including evaluation of water use at the data center and at the site of energy generation, an evaluation of impact on source water and water scarcity, and consideration of closed-loop cooling;
- A detailed estimate of indirect water use associated with energy production disaggregated by type; and
- A cost of service study completed by the applicable water supplier within the last five years, or funded by the data center if none exists.
- Prohibits a city, county, or city and county from approving the construction, or expansion that increases the maximum peak water use, of a data center unless the following conditions are satisfied:
- The applicant has provided a water supply assessment;
- The applicant has provided a water use assessment, if requested by the city, county, or city and county;
- The applicant, beginning January 1, 2028, has provided a water scarcity plan;
- The applicant has provided the data center′s projected water use and water efficiency measures;
- The applicant has made specified disclosures regarding workforce needs associated with the project;
- The applicant has provided all water resource plans, water usage reports, supporting documentation, and any approvals issued by a state or local agency related to the plans or applications; and
- The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project as determined by the Department of Water Resources (DWR) or the applicable water supplier.
- Requires DWR, in coordination with the State Water Resources Control Board (State Water Board), to conduct necessary studies and investigations and recommend no later than June 30, 2028 a commercial, industrial, institutional (CII) water use classification system for users that qualify as large consumptive use facilities, including data centers.
- Requires the State Water Board in coordination with DWR to adopt the CII water use classification recommended by DWR pursuant to this bill by December 31, 2029.
COMMENTS
Data centers are buildings or facilities that ″support servers, digital storage equipment, and network infrastructure for the purpose of large-scale data processing and data storage. Increasing demand for data creation, processing, and storage from existing and emerging technologies, such as online platforms/social media, video streaming, smart and connected infrastructure, autonomous vehicles, and artificial intelligence, has led to exponential growth in data center workloads and compute instances″ (Bakar Siddik, Shehabi, and Marston, 2021). There is increasing awareness of the energy and water demands (primarily related to cooling) associated with data centers as artificial intelligence and other technologies are being deployed. Data centers can have substantial and sometimes irregular demand for cooling water. All computer chips produce heat as waste energy from the electricity flowing through them. While this heat is minimal in the context of a personal computer, data centers made up of thousands of servers produce an immense amount of heat that needs to be removed from the facility to maintain safety and performance. To manage this heat, data centers use a variety of cooling technologies, either sequentially or depending on weather conditions and server load.
Data center water use patterns can be irregular as a result of switching between cooling technologies. Research shows that the ″peaking factor″ (the factor of the peak use over average use) for data centers can be double or more the peaking factor for other large users (Han et al. 2026). These high peaks occur because data centers need to shift to evaporative cooling technologies to exhaust waste heat during hot and dry weather conditions, or use more water to remove more heat. Shifting between cooling technologies can result in large surges in demand that need to be accommodated by water distribution infrastructure, even if the average demand is far lower.
Evaporative cooling systems, like those sometimes used in data centers, are consumptive uses of water. This bill would require data center operators to distinguish their consumptive and nonconsumptive water uses. Consumptive water use refers to water that is withdrawn or diverted from the environment that is made unavailable for future use because it has evaporated, transpired, been incorporated into products or crops, or otherwise been made unavailable for immediate use. In contrast, non-consumptive uses of water quickly return to the environment. Examples of non-consumptive use include recreation, hydroelectric power generation, or instream flow.
Data centers need a reliable water supply. Due to the reliability requirement to deliver the demanded water, water infrastructure (both water delivery and wastewater) must be sized to accommodate the peaks in demand. Local water suppliers are then required to build capacity well in excess of average need and potentially may build capacity in excess of any need that materializes, especially if they are building based on limited information about projected water demand.
Better data about water use, whether during the water supply assessment process (if required, see discussion below) or based on research data from across the sector, would assist local water agencies in planning for actual need. Local water utilities could also work with data centers to understand options for the times of highest demand and collaborate on strategies to deliver water supply reliability. The risk of stranded or overbuilt assets can be mitigated by requiring new large customers to pay for necessary infrastructure upgrades as part of the connection process, potentially extending beyond traditional connection fees to include upgrades to mains, pumping stations, and other infrastructure as needed. Water use by data centers falls under the CII classification, but is not calculated under the urban water use objective (″Making Conservation A Way of Life″) intended to increase water use efficiency in California′s urban areas. However, as required by the legislative package to enact Making Conservation a Way of Life, DWR conducted a study (completed in 2022) on CII water use and recommended performance measures to the State Water Board that would improve water use efficiency in the CII sector. One of the study′s recommendations was to require urban retail water suppliers to classify their CII users by one of 19 user types (e.g., manufacturing/industrial, technology/science). The State Water Board incorporated this recommendation into the final Making Conservation a Way of Life regulations by requiring urban retail water suppliers to classify CII users into one of 22 categories by June 30, 2027; the categories are based on the ENERGY STAR Portfolio Manager categories. This bill requires DWR to develop a separate classification for CII users based on their consumptive use of water by June 30, 2028. A water supply assessment is required for a proposed project (CII or otherwise) with a water use that exceeds certain thresholds and is completed as part of the California Environmental Quality Act process. The water use threshold that triggers the requirement for a water supply assessment is generally the amount of water required for a proposed residential development of more than 500 dwelling units or commercial or industrial uses that are of defined sizes (Water Code Section 10912). To complete the water supply assessment, the project proponent must provide information to municipal planning decisionmakers about the expected water use. The water supply assessment process provides the primary opportunity for public input and awareness of water use by a proposed CII (or other) water user.
According to the Author
California′s finite water supplies are under growing stress from climate change, prolonged droughts, and the expansion of large consumptive water users. While the Legislature has long recognized the importance of coordinating land use decisions with available water supplies, the rapid growth of data centers has exposed gaps in existing law. Data centers represent a new kind of development that can impose significant, highly concentrated water demands on local systems.
This gap is particularly important because data centers operate continuously and can drive substantial peak-day demand, often requiring new treatment, storage, or distribution infrastructure. Without timely and standardized information during the entitlement process, municipalities and water retailers may lack clear visibility into a project′s water needs and the leverage to ensure that adequate supplies, infrastructure capacity, and conservation measures are in place prior to entering into service commitments.
[This bill] directly addresses these water management difficulties. [This bill] requires meaningful water planning before local approval and protects critically overdrafted groundwater basins. In doing so, [this bill] provides local governments and water suppliers the information they need to evaluate data center water demand before making irreversible siting and infrastructure decisions.
Arguments in Support
The California Coastkeeper Alliance supports this bill and argues that it will inform local decision-making, condition data center project approvals on meeting necessary requirements, and avoid increased water rates resulting from data center water demand. California Coastkeeper Alliance states: ″By requiring data center project applicants to assume responsibility for the costs of water infrastructure additions required to serve their needs, [this bill] would also ensure ratepayers do not end up bearing the costs of infrastructure they do not create demand for. This principle is consistent with the ″proportional cost of service″ requirement in California′s Constitution. Additionally, the bill appropriately allocates risk to project applicants, ensuring that if a facility.″
Arguments in Opposition
The Data Center Coalition opposes this bill and maintains it imposes ″additional burdensome and disparate reporting requirements on data centers as compared to other″ CII users, raises privacy and security concerns, and will undermine California′s already shrinking data center market. Rather than placing unique requirements on data centers, the Data Center Coalition asserts ″a more equitable approach would acknowledge that data centers are just one water consumer among many diverse industries. Data center operators are actively prioritizing responsible water use through operational best practices and innovative development strategies, often collaborating with local authorities and conservation organizations on water restoration and reclamation projects.″
FISCAL COMMENTS
According to the Assembly Appropriations Committee, this bill has the following fiscal impact:
- DWR estimates ongoing annual staffing costs of $750,000 (General Fund) to develop assessment criteria, manage waiver determinations, and potentially promulgate regulations. In addition, to conduct studies and investigations and recommend a CII water use classification for large consumptive use facilities like data centers, DWR estimates a one-time contracting cost of $1 million as well as $500,000 in annual ongoing costs for one senior environmental scientist. It is not clear that the bill requires ongoing work of DWR post-2029 and whether DWR requires ongoing funding once it recommends and consults with the State Water Board on the new classification.
- The State Water Board estimates ongoing annual General Fund costs of $250,000 to coordinate with DWR, adopt a new CII water use classification, promulgate a regulation for large consumptive use facilities, and perform subsequent monitoring and updates.
The Legislative Analyst′s Office recently warned of General Fund structural deficits of around $35 billion per year in the 2027-28 fiscal year and ongoing.
VOTES
ASM WATER, PARKS, AND WILDLIFE: 9-2-2
YES: Papan, Alvarez, Ávila Farías, Bennett, Boerner, Caloza, Hart, Muratsuchi, Rogers
NO: Jeff Gonzalez, Alanis
ABS, ABST OR NV: Bains, Gallagher
ASM LOCAL GOVERNMENT: 8-2-0
YES: Carrillo, Pacheco, Ramos, Ransom, Blanca Rubio, Stefani, Ward, Wilson
NO: Ta, Johnson
ASM APPROPRIATIONS: 11-4-0
YES: Wicks, Aguiar-Curry, Calderon, Caloza, Fong, Mark González, Krell, Pacheco, Pellerin, Sharp-Collins, Solache
NO: Hoover, Dixon, Ta, Tangipa
UPDATED
VERSION: May 22, 2026
CONSULTANT: Pablo Garza / W., P., & W. / (916) 319-2096 FN: 0003114
ASSEMBLY THIRD READING
ATR Bill Id:AB 2469
Author:(Papan)
As Amended Ver:April 8, 2026
Majority vote
SUMMARY
Prohibits a local agency from approving construction of a new, or expansion of an existing, data center unless an applicant for a data center project provides the local agency with detailed information regarding the data center′s water use and meets other requirements related to workforce and infrastructure for the data center.
Major Provisions
- Defines ″water scarcity plan″ as a report that includes measures to be implemented under different drought scenarios defined by the U.S. Drought Monitor to reduce water use.
- Defines ″water use assessment″ as a report that includes a description of a data center and its operations and the following information regarding water use by the data center:
- A detailed accounting of water intake expressed in gallons per day and total volume, including maximum and average daily demand, maximum and average monthly demand, demand over an average 12-month period, water withdrawals, phases of growth or expansion, trigger points for additional demand, full build-out and peak operation scenarios;
- A detailed explanation of each direct water use including specified information regarding cooling systems, humidification, potable and sanitary uses, fire suppression systems, and maintenance operations;
- A cooling alternatives analysis that compares the proposed cooling method to a range of alternatives including evaluation of water use at the data center and at the site of energy generation, an evaluation of impact on source water and water scarcity, and consideration of closed-loop cooling;
- A detailed estimate of indirect water use associated with energy production disaggregated by type; and
- A cost of service study completed by the applicable water supplier within the last five years, or funded by the data center if none exists.
- Prohibits a city, county, or city and county from approving the construction, or expansion that increases the maximum peak water use, of a data center unless the following conditions are satisfied:
- The applicant has provided a water supply assessment;
- The applicant has provided a water use assessment, if requested by the city, county, or city and county;
- The applicant, beginning January 1, 2028, has provided a water scarcity plan;
- The applicant has provided the data center′s projected and actual water use and water efficiency measures;
- The applicant has made specified disclosures regarding workforce needs associated with the project;
- The applicant has provided all water resource plans, water usage reports, supporting documentation, and any approvals issued by a state or local agency related to the plans or applications;
- The project is not located in a groundwater basin designated as critically overdrafted by the Department of Water Resources (DWR). DWR may waive this prohibition upon a comprehensive assessment demonstrating the project does not pose a disproportionate risk to the health, welfare, or environment of an environmental justice community or equity investment eligible community; and
- The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project as determined by DWR or the applicable water supplier.
- Requires DWR, in coordination with the State Water Resources Control Board (State Water Board), to conduct necessary studies and investigations and recommend no later than June 30, 2028 a commercial, industrial, institutional (CII) water use classification system for users that qualify as large consumptive use facilities, including data centers.
- Requires the State Water Board in coordination with DWR to adopt the CII water use classification recommended by DWR pursuant to this bill by December 31, 2029.
COMMENTS
Data centers are buildings or facilities that ″support servers, digital storage equipment, and network infrastructure for the purpose of large-scale data processing and data storage. Increasing demand for data creation, processing, and storage from existing and emerging technologies, such as online platforms/social media, video streaming, smart and connected infrastructure, autonomous vehicles, and artificial intelligence, has led to exponential growth in data center workloads and compute instances″ (Bakar Siddik, Shehabi, and Marston, 2021). There is increasing awareness of the energy and water demands (primarily related to cooling) associated with data centers as artificial intelligence and other technologies are being deployed.
Data centers can have substantial and sometimes irregular demand for cooling water. All computer chips produce heat as waste energy from the electricity flowing through them. While this heat is minimal in the context of a personal computer, data centers made up of thousands of servers produce an immense amount of heat that needs to be removed from the facility to maintain safety and performance. To manage this heat, data centers use a variety of cooling technologies, either sequentially or depending on weather conditions and server load.
Data center water use patterns can be irregular as a result of switching between cooling technologies. Research shows that the ″peaking factor″ (the factor of the peak use over average use) for data centers can be double or more the peaking factor for other large users (Han et al. 2026). These high peaks occur because data centers need to shift to evaporative cooling technologies to exhaust waste heat during hot and dry weather conditions, or use more water to remove more heat. Shifting between cooling technologies can result in large surges in demand that need to be accommodated by water distribution infrastructure, even if the average demand is far lower.
Evaporative cooling systems, like those sometimes used in data centers, are consumptive uses of water. This bill would require data center operators to distinguish their consumptive and nonconsumptive water uses. Consumptive water use refers to water that is withdrawn or diverted from the environment that is made unavailable for future use because it has evaporated, transpired, been incorporated into products or crops, or otherwise been made unavailable for immediate use. In contrast, non-consumptive uses of water quickly return to the environment. Examples of non-consumptive use include recreation, hydroelectric power generation, or instream flow.
Data centers need a reliable water supply. Due to the reliability requirement to deliver the demanded water, water infrastructure (both water delivery and wastewater) must be sized to accommodate the peaks in demand. Local water suppliers are then required to build capacity well in excess of average need and potentially may build capacity in excess of any need that materializes, especially if they are building based on limited information about projected water demand.
Better data about water use, whether during the water supply assessment process (if required, see discussion below) or based on research data from across the sector, would assist local water agencies in planning for actual need. Local water utilities could also work with data centers to understand options for the times of highest demand and collaborate on strategies to deliver water supply reliability. The risk of stranded or overbuilt assets can be mitigated by requiring new large customers to pay for necessary infrastructure upgrades as part of the connection process, potentially extending beyond traditional connection fees to include upgrades to mains, pumping stations, and other infrastructure as needed.
Water use by data centers falls under the CII classification, but is not calculated under the urban water use objective (″Making Conservation A Way of Life″) intended to increase water use efficiency in California′s urban areas. However, as required by the legislative package to enact Making Conservation a Way of Life, DWR conducted a study (completed in 2022) on CII water use and recommended performance measures to the State Water Board that would improve water use efficiency in the CII sector. One of the study′s recommendations was to require urban retail water suppliers to classify their CII users by one of 19 user types (e.g., manufacturing/industrial, technology/science). The State Water Board incorporated this recommendation into the final Making Conservation a Way of Life regulations by requiring urban retail water suppliers to classify CII users into one of 22 categories by June 30, 2027; the categories are based on the ENERGY STAR Portfolio Manager categories. This bill requires DWR to develop a separate classification for CII users based on their consumptive use of water by June 30, 2028.
A water supply assessment is required for a proposed project (CII or otherwise) with a water use that exceeds certain thresholds and is completed as part of the California Environmental Quality Act process. The water use threshold that triggers the requirement for a water supply assessment is generally the amount of water required for a proposed residential development of more than 500 dwelling units or commercial or industrial uses that are of defined sizes (Water Code § 10912). To complete the water supply assessment, the project proponent must provide information to municipal planning decisionmakers about the expected water use. The water supply assessment process provides the primary opportunity for public input and awareness of water use by a proposed CII (or other) water user.
According to the Author
California′s finite water supplies are under growing stress from climate change, prolonged droughts, and the expansion of large consumptive water users. While the Legislature has long recognized the importance of coordinating land use decisions with available water supplies, the rapid growth of data centers has exposed gaps in existing law. Data centers represent a new kind of development that can impose significant, highly concentrated water demands on local systems.
This gap is particularly important because data centers operate continuously and can drive substantial peak-day demand, often requiring new treatment, storage, or distribution infrastructure. Without timely and standardized information during the entitlement process, municipalities and water retailers may lack clear visibility into a project′s water needs and the leverage to ensure that adequate supplies, infrastructure capacity, and conservation measures are in place prior to entering into service commitments.
[This bill] directly addresses these water management difficulties. [This bill] requires meaningful water planning before local approval and protects critically overdrafted groundwater basins. In doing so, [this bill] provides local governments and water suppliers the information they need to evaluate data center water demand before making irreversible siting and infrastructure decisions.
Arguments in Support
The California Coastkeeper Alliance supports this bill and argues that it will inform local decision-making, condition data center project approvals on meeting necessary requirements, and avoid increased water rates resulting from data center water demand. California Coastkeeper Alliance states: ″By requiring data center project applicants to assume responsibility for the costs of water infrastructure additions required to serve their needs, [this bill] would also ensure ratepayers do not end up bearing the costs of infrastructure they do not create demand for. This principle is consistent with the ″proportional cost of service″ requirement in California′s Constitution. Additionally, the bill appropriately allocates risk to project applicants, ensuring that if a facility.″
Arguments in Opposition
The Data Center Coalition opposes this bill and maintains it imposes ″additional burdensome and disparate reporting requirements on data centers as compared to other″ CII users, raises privacy and security concerns, and will undermine California′s already shrinking data center market. Rather than placing unique requirements on data centers, the Data Center Coalition asserts ″a more equitable approach would acknowledge that data centers are just one water consumer among many diverse industries. Data center operators are actively prioritizing responsible water use through operational best practices and innovative development strategies, often collaborating with local authorities and conservation organizations on water restoration and reclamation projects.″
FISCAL COMMENTS
According to the Assembly Appropriations Committee, this bill has the following fiscal impact:
- By authorizing DWR to waive the prohibition on a local agency′s approval of the construction or expansion of a data center if the project is located in a basin designated as critically overdrafted by DWR, this bill imposes ongoing costs on DWR. DWR must conduct a ″comprehensive assessment″ demonstrating that the project does not pose a disproportionate risk to the health, welfare, or environment of an environmental justice community or equity investment-eligible community.
DWR estimates ongoing annual staffing costs of $750,000 (General Fund) to develop assessment criteria, manage waiver determinations, and potentially promulgate regulations. In addition, to conduct studies and investigations and recommend a CII water use classification for large consumptive use facilities like data centers, DWR estimates a one-time contracting cost of $1 million as well as $500,000 in annual ongoing costs for one senior environmental scientist. It is not clear that the bill requires ongoing work of DWR post-2029 and whether DWR requires ongoing funding once it recommends and consults with the State Water Board on the new classification. - State Water Board estimates ongoing annual General Fund costs of $250,000 to coordinate with DWR, adopt a new CII water use classification, promulgate a regulation for large consumptive use facilities, and perform subsequent monitoring and updates.
The Legislative Analyst′s Office recently warned of General Fund structural deficits of around $35 billion per year in the 2027-28 fiscal year and ongoing.
VOTES
ASM WATER, PARKS, AND WILDLIFE: 9-2-2
YES: Papan, Alvarez, Ávila Farías, Bennett, Boerner, Caloza, Hart, Muratsuchi, Rogers
NO: Jeff Gonzalez, Alanis
ABS, ABST OR NV: Bains, Gallagher
ASM LOCAL GOVERNMENT: 8-2-0
YES: Carrillo, Pacheco, Ramos, Ransom, Blanca Rubio, Stefani, Ward, Wilson
NO: Ta, Johnson
ASM APPROPRIATIONS: 11-4-0
YES: Wicks, Aguiar-Curry, Calderon, Caloza, Fong, Mark González, Krell, Pacheco, Pellerin, Sharp-Collins, Solache
NO: Hoover, Dixon, Ta, Tangipa
UPDATED
VERSION: April 8, 2026
CONSULTANT: Pablo Garza / W., P., & W. / (916) 319-2096 FN: 0002719
Date of Hearing: May 6, 2026
ASSEMBLY COMMITTEE ON APPROPRIATIONS
Buffy Wicks, Chair
ABPCA Bill Id:AB 2469
Author:(Papan) – As Amended Ver:April 8, 2026
Policy Committee: | Water, Parks and Wildlife | Vote: | 9 - 2 |
Local Government | 8 - 2 | ||
|
|
Urgency: No State Mandated Local Program: Yes Reimbursable: No
SUMMARY:
This bill prohibits a local agency from approving construction of a new, or expansion of an existing, data center unless an applicant for a data center project provides the local agency with detailed information regarding the data center’s water use and meets other requirements related to workforce and infrastructure.
Specifically, this bill, among other things:
- Prohibits a city, county, or city and county from approving a discretionary or ministerial permit or other entitlement that would result in the construction, or expansion that increases the maximum peak water use, of a data center unless the following conditions are satisfied:
- The applicant has provided a water supply assessment (which the bill defines as a report that includes a description of a data center and its operations and specified information regarding water use by the data center).
- The applicant has provided a water use assessment, if requested by the city, county, or city and county.
- The applicant, beginning January 1, 2028, has provided a water scarcity plan (which the bill defines as a report that includes measures to be implemented under different drought scenarios defined by the U.S. Drought Monitor to reduce water use).
- The applicant has provided the data center’s projected and actual water use and water efficiency measures.
- The applicant has made specified disclosures regarding workforce needs associated with the project.
- The applicant has provided all water resource plans, water usage reports, supporting documentation, and any approval issues by a state or local agency related to the plans or applications.
- The project is not located in a groundwater basin designated as critically overdrafted by the Department of Water Resources (DWR). DWR may waive this prohibition upon a comprehensive assessment demonstrating the project does not pose a disproportionate risk to the health, welfare, or environment of an environmental justice community or equity investment-eligible community.
- The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project as determined by DWR or the applicable water supplier.
- Requires DWR, in coordination with the State Water Resources Control Board (State Water Board), to conduct necessary studies and investigations and recommend no later than June 30, 2028, a commercial, industrial, and institutional (CII) water use classification system for users that qualify as large consumptive use facilities, including data centers.
- Requires the State Water Board, in coordination with DWR, to adopt the CII water use classification recommended by DWR pursuant to this bill by December 31, 2029.
- Requires each urban retail water supplier to implement the CII water use classification adopted pursuant to this bill.
FISCAL EFFECT:
1) By authorizing DWR to waive the prohibition on a local agency’s approval of the construction or expansion of a data center if the project is located in a basin designated as critically overdrafted by DWR, this bill imposes ongoing costs on DWR. DWR must conduct a “comprehensive assessment” demonstrating that the project does not pose a disproportionate risk to the health, welfare, or environment of an environmental justice community or equity investment-eligible community.
For its part, DWR estimates ongoing annual staffing costs of $750,000 (General Fund) to develop assessment criteria, manage waiver determinations, and potentially promulgate regulations. In addition, to conduct studies and investigations and recommend a CII water use classification for large consumptive use facilities like data centers, DWR estimates a one-time contracting cost of $1 million as well as $500,000 in annual ongoing costs for one senior environmental scientist. It is not clear to the committee that the bill requires ongoing work of DWR post-2029 and whether the department requires ongoing funding once it recommends and consults with the State Water Board on the new classification.
2) State Water Board estimates ongoing annual General Fund costs of $250,000 to coordinate with DWR, adopt a new CII water use classification, promulgate a regulation for large consumptive use facilities, and perform subsequent monitoring and updates.
The Legislative Analyst’s Office recently warned of General Fund structural deficits of around $35 billion per year in the 2027-28 fiscal year and ongoing.
COMMENTS:
1) Purpose. According to the author:
Data centers represent a new kind of development that can impose significant, highly concentrated water demands on local systems. This gap is particularly important because data centers operate continuously and can drive substantial peak-day demand, often requiring new treatment, storage, or distribution infrastructure. Without timely and standardized information during the entitlement process, municipalities and water retailers may lack clear visibility into a project’s water needs and the leverage to ensure that adequate supplies, infrastructure capacity, and conservation measures are in place prior to entering into service commitments…[This bill] provides local governments and water suppliers the information they need to evaluate data center water demand before making irreversible siting and infrastructure decisions.
2) Background. Data Centers and Water Use. There is growing awareness of the energy and water demands (primarily related to cooling) associated with data centers as artificial intelligence and other technologies are being rapidly deployed. Data centers can have substantial and sometimes irregular demand for cooling water. Evaporative cooling systems, like those sometimes used in data centers, are consumptive uses of water.
Consumptive water use means water that is withdrawn or diverted from the environment that is made unavailable for future use because it has evaporated, transpired, been incorporated into products or crops, or otherwise been made unavailable for immediate use. In contrast, non-consumptive uses of water quickly return to the environment. Examples of non-consumptive use include recreation, hydroelectric power generation, or instream flow.
Data centers need a reliable water supply. Due to the reliability requirement to deliver the demanded water, water infrastructure (both water delivery and wastewater) must be sized to accommodate the peaks in demand. Local water suppliers are then required to build capacity well in excess of average need and potentially may build capacity in excess of any need that materializes, especially if construction is based on limited information about projected water demand. Lack of reliable information about expected usage may result in overbuilding and the risk of stranded assets if data center projects either do not materialize or close.
CII Water Use. Water use by data centers falls under the CII classification but is not calculated under the urban water use objective in the State Water Board’s “Making Conservation A Way of Life” regulation, which is intended to increase water use efficiency in California's urban areas. However, as required by the legislative package that enacted Making Conservation a Way of Life, DWR completed a study in 2022 on CII water use and recommended performance measures to the State Water Board that would improve water use efficiency in the CII sector. One of the study’s recommendations was to require urban retail water suppliers to classify their CII users in 19 user types. The State Water Board incorporated this recommendation into the final Making Conservation a Way of Life regulation by requiring urban retail water suppliers to classify CII users into one of 22 categories by June 30, 2027. This bill requires DWR to develop a separate classification for CII users based on their consumptive use.
3) Support and Opposition. Writing in support, a coalition of environmental organizations argues that unlike other CII facilities, data centers are “always on” and that this bill “acts on the need for a new water use classification for large consumptive use facilities such as data centers that addresses these differences.” The coalition further argues local governments need more information to understand the nature, extent, and timing of data centers’ water use and to incorporate this information into their decisions. Many data centers receive potable water from municipal water systems, and small systems lack the capacity to serve large facilities. By requiring data center project applicants to assume responsibility for the costs of water infrastructure additions required to serve their needs, the coalition argues this bill “ensure[s] ratepayers do not end up bearing the costs of infrastructure they do not create demand for.”
Writing in an oppose-unless-amended position, the California Association of Counties, League of California Cities, and Rural County Representatives of California note that while they generally support providing more information to local government permitting authorities to guide the best possible decisionmaking outcomes for data centers, this bill undermines this “locally-driven approach by preempting local governments from making permitting decisions in the absence of the extensive new water use assessment process mandated by the bill.”
Local governments argue that the complexity of the new water use assessments and the conditioning of any new permits upon their completion presents substantial new challenges to city and county departments. They assert that local authorities must review the new components of the permitting application process, which is “a costly new duty for governments that are already under immense budgetary strain and a certain source of delays in the review process as staff work with applicants to ensure that applications are complete.”
Analysis Prepared by: Nikita Koraddi / APPR. / (916) 319-2081
Date of Hearing: April 22, 2026
ASSEMBLY COMMITTEE ON LOCAL GOVERNMENT
Juan Carrillo, Chair
ABPCA Bill Id:AB 2469 (
Author:Papan) – As Amended Ver:April 8, 2026
SUBJECT: Data centers: water use disclosures
SUMMARY: Prohibits a city, including a charter city, county, or city and county (city or county) from approving construction of a new, or expansion of an existing, data center unless an applicant for a data center project provides the local agency with detailed information regarding the data center’s water use and meets other requirements related to workforce and infrastructure for the data center. Specifically, this bill:
- Defines “water scarcity plan” as a report that includes measures to be implemented under different drought scenarios defined by the U.S. Drought Monitor to reduce water use.
- Defines “water use assessment” as a report that includes a description of a data center and its operations and the following information regarding water use by the data center:
- A detailed accounting of water intake expressed in gallons per day and total volume, including maximum and average daily demand, maximum and average monthly demand, demand over an average 12-month period, water withdrawals, phases of growth or expansion, trigger points for additional demand, full build-out and peak operation scenarios.
- A detailed explanation of each direct water use including specified information regarding cooling systems, humidification, potable and sanitary uses, fire suppression systems, and maintenance operations.
- A cooling alternatives analysis that compares the proposed cooling method to a range of alternatives including evaluation of water use at the data center and at the site of energy generation, an evaluation of impact on source water and water scarcity, and consideration of closed-loop cooling.
- A detailed estimate of indirect water use associated with energy production disaggregated by type.
- A cost of service study completed by the applicable water supplier within the last five years, or funded by the data center if none exists.
- Prohibits a city or county from approving the construction, or expansion that increases the maximum peak water use, of a data center unless the following conditions are satisfied:
- The applicant has provided a water supply assessment completed pursuant to existing law governing water supply planning, as specified.
- The applicant has provided a water use assessment, if requested by the city, county, or city and county.
- The applicant, beginning January 1, 2028, has provided a water scarcity plan.
- The applicant has provided the data center’s projected and actual water use and water efficiency measures.
- The applicant has made specified disclosures regarding workforce needs associated with the project.
- The applicant has provided all water resource plans, water usage reports, supporting documentation, and any approvals issued by a state or local agency related to the plans or applications.
- The project is not located in a groundwater basin designated as critically overdrafted by the Department of Water Resources (DWR). DWR may waive this prohibition upon a comprehensive assessment demonstrating the project does not pose a disproportionate risk to the health, welfare, or environment of an environmental justice community or equity investment eligible community.
- The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project as determined by DWR or the applicable water supplier.
- Requires DWR, in coordination with the State Water Resources Control Board (State Water Board), to conduct necessary studies and investigations and recommend no later than June 30, 2028 a commercial, industrial, institutional (CII) water use classification system for users that qualify as large consumptive use facilities, including data centers.
- Requires the State Water Board in coordination with DWR to adopt the CII water use classification recommended by DWR pursuant to this bill by December 31, 2029.
- Requires each urban retail water supplier to implement the CII water use classification adopted pursuant to this bill.
- Finds and declares that water conservation is a matter of statewide concern and is not a municipal affair as that term is used in Section 5 of Article XI of the California Constitution. Therefore, Section 1 of this act adding Section 65964.7 to the Government Code applies to all cities, including charter cities.
- Provides that no reimbursement is required by this bill pursuant to Section 6 of Article XIII B of the California Constitution because a local agency or school district has the authority to levy service charges, fees, or assessments sufficient to pay for the program or level of service mandated by this act, within the meaning of Section 17556 of the Government Code.
EXISTING LAW:
- Allows cities and counties to “make and enforce within its limits, all local, police, sanitary and other ordinances and regulations not in conflict with general laws.” It is from this fundamental power (commonly called the police power) that cities and counties derive their authority to regulate behavior to preserve the health, safety, and welfare of the public, including land use authority. (California Constitution, Article XI, § 7)
- Establishes the California Energy Commission with various responsibilities with respect to developing and implementing the state’s energy policies (Public Resources Code § 25000 et seq.).
- Establishes the State Water Board to provide for the orderly and efficient administration of the state’s water resources (Water Code § 174 et seq.).
- Requires the state to achieve a 20% reduction in urban per capita water use by December 31, 2020 (20x2020 target) and requires each urban retail water supplier to establish their own target to contribute towards achieving the statewide 20% reduction goal (Water Code §§ 10608.16, 10608.20).
- Defines “process water” as water used by industrial users to produce a product or product content or water used for research and development. Includes water used for cooling in buildings used in the manufacturing process, control rooms, data centers, laboratories, clean rooms, and other industrial facilities (Water Code § 10608.12).
- Permits an urban retail water supplier that has a substantial percentage of industrial water use in its service territory to exclude “process water” from its calculation of its urban water use target to meet the 20x2020 target [Water Code § 10608.24(e)].
- Requires the DWR, in coordination with the State Water Board, to conduct studies and investigations to develop recommendations for efficient water use by commercial, industrial, and institutional (CII) water users by October 1, 2021. The State Water Board shall adopt performance measures for CII water use based on these recommendations by June 30, 2022 (Water Code § 10609.10).
- Requires a water supplier to prepare a water supply assessment for a residential, commercial, or industrial project that must undergo review under the California Environmental Quality Act (CEQA) and will use more than a specified amount of water (see discussion under Background, below). The water supply assessment must contain information regarding the project’s water use and the ability of the water supplier to meet the project’s water demands (Water Code § 10910 et seq.).
- Requires DWR to investigate the state’s groundwater basins and, among other things, identify basins that are subject to critical conditions of overdraft (Water Code § 12924).
FISCAL EFFECT: This bill is keyed fiscal and contains a state-mandated local program.
COMMENTS:
- Bill Summary. This bill prohibits cities and counties from approving the construction, or expansion that increases the maximum peak water use, of a data center unless the following conditions are met:
- The applicant has provided a water supply assessment completed pursuant to existing law governing water supply planning, as applicable.
- The applicant has provided a water use assessment, if requested by the city or county.
- The applicant, beginning January 1, 2028, has provided a water scarcity plan.
- The applicant has provided the data center’s projected and actual water use and water efficiency measures.
- The applicant has made specified disclosures regarding workforce needs associated with the project.
- The applicant has provided all water resource plans, water usage reports, supporting documentation, and any approvals issued by a state or local agency related to the plans or applications.
- The project is not located in a groundwater basin designated as critically overdrafted by DWR. DWR may waive this prohibition upon a comprehensive assessment demonstrating the project does not pose a disproportionate risk to the health, welfare, or environment of an environmental justice community or equity investment eligible community.
- The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project as determined by DWR or the applicable water supplier.
This bill also requires DWR, in coordination with the State Water Board, to conduct necessary studies and investigations and recommend no later than June 30, 2028, a CII water use classification system for users that qualify as large consumptive use facilities, including data centers. The State Water Board, in coordination with DWR, must adopt the CII water use classification recommended by DWR pursuant to this bill by December 31, 2029. Each urban retail water supplier must implement the CII water use classification adopted pursuant to this bill.
This bill is sponsored by the author.
- Author’s Statement. According to the author, “California’s finite water supplies are experiencing growing stress from climate change, prolonged drought, and the expansion of large consumptive water users. While the Legislature has long recognized the importance of coordinating land use decisions with available water supplies, the rapid growth of data centers has exposed gaps in existing law. Data centers represent a new kind of development that can impose significant, highly concentrated water demands on local systems.
“This gap is particularly important because data centers operate continuously and can drive substantial peak-day demand, often requiring new treatment, storage, or distribution infrastructure. Without timely and standardized information during the entitlement process, municipalities and water retailers may lack clear visibility into a project’s water needs and the leverage to ensure that adequate supplies, infrastructure capacity, and conservation measures are in place prior to entering into service commitments.
“AB 2469 directly addresses these water management difficulties. AB 2469 requires meaningful water planning before local approval and protects critically overdrafted groundwater basins. In doing so, AB 2469 provides local governments and water suppliers the information they need to evaluate data center water demand before making irreversible siting and infrastructure decisions.”
- Planning and Approving New Development. Planning and approving new development is mainly a local responsibility. The California Constitution allows cities and counties to “make and enforce within its limits, all local, police, sanitary and other ordinances and regulations not in conflict with general laws.” It is from this fundamental power (commonly called the police power) that cities and counties derive their authority to regulate behavior to preserve the health, safety, and welfare of the public – including land use authority. Cities and counties enforce this land use authority through zoning regulations, as well as through an “entitlement process” for obtaining discretionary as well as ministerial approvals.
The scale of the proposed development and the existing environmental setting determine the degree of local review that occurs. For larger developments, the local entitlement process commonly requires multiple discretionary decisions regarding the subdivision of land, environmental review pursuant to the California Environmental Quality Act (CEQA), design review, and project review by the local agency’s legislative body (city council or county board) or by a planning commission delegated by the legislative body.
- Data Centers. Data centers are buildings or facilities that “support servers, digital storage equipment, and network infrastructure for the purpose of large-scale data processing and data storage. Increasing demand for data creation, processing, and storage from existing and emerging technologies, such as online platforms/social media, video streaming, smart and connected infrastructure, autonomous vehicles, and artificial intelligence, has led to exponential growth in data center workloads and compute instances.”[1]
- Data Centers and Water Use. Data centers use a lot of water. This is because data centers produce tremendous heat that must be removed from the facility to maintain safety and performance. A mid-sized data center uses 300,000 gallons of water a day, enough for 1,000 households, and data centers rank among the top ten industrial and commercial water users.[2] Data centers use a variety of cooling technologies often in the same facility between which
Not only do data centers use large volumes of water, the volume of water needed at any particular time can be irregular. Data centers use a variety of cooling technologies, either sequentially or depending on weather conditions and server load. Data center water use patterns can be irregular as a result of switching between these cooling technologies, including high demand peaks that water distribution infrastructure must be designed to accommodate, even if the average demand is far lower. Water infrastructure (both water delivery and wastewater) must be sized to accommodate these peaks in demand.
- “Consumptive” Water Use. Evaporative cooling systems, like those sometimes used in data centers, are “consumptive” uses of water. Consumptive water use refers to water that is withdrawn or diverted from the environment that is made unavailable for future use because it has evaporated, transpired, been incorporated into products or crops, or otherwise been made unavailable for immediate use. In contrast, non-consumptive uses of water quickly return to the environment. Examples of non-consumptive use include recreation, hydroelectric power generation, or instream flow.
- Water Supply Assessments. A water supply assessment is required for a proposed project with a water use that exceeds certain thresholds and is completed as part of the CEQA process. These thresholds vary depending on size and type of development and numbers of dwelling units, numbers of rooms in a hotel or motel development, or the number of employed persons in commercial developments. To complete the water supply assessment, the project proponent must provide information to municipal planning decisionmakers about the expected water use. The water supply assessment process provides the primary opportunity for public input and awareness of water use by a proposed water user.
- Related Legislation. AB 2619 (Papan) requires data center developers to provide information on water use to water suppliers and local governments prior to being issued a business license and upon renewal of a business license, and requires urban water suppliers to consider data center demand in water shortage planning. AB 2619 is pending in this committee.
- Prior Legislation. AB 93 (Papan) of 2025, similar to this bill, would have required a data center operator to provide its estimated or actual water use to its water supplier as a condition of obtaining or renewing a business license issued by a city or county. The Governor vetoed AB 93, stating:
“This bill requires data centers, when applying for an initial business license, to provide to their water supplier an estimate of expected water use. It further requires data centers, when applying for a renewal of a business license, to provide their water supplier with a report on annual water use.
“The widespread adoption of artificial intelligence technologies is driving an unprecedented demand for data center capacity throughout the nation. As the global epicenter of the technology sector, California is well positioned to support the development of this critically important digital infrastructure in the state.
“While I appreciate the author's intent, I am reluctant to impose rigid reporting requirements about operational details on this sector without understanding the full impact on businesses and the consumers of their technology.”
- Arguments in Support. The California Coastkeeper Alliance writes in support, “Data centers use water for multiple purposes, including energy generation and cooling. Many facilities consume the water they use for cooling via open-loop towers, with about 80% evaporating after a single use. Additionally, because servers must be maintained at a constant temperature, these facilities’ cooling needs fluctuate throughout the year depending on the weather. Water use peaks during the hottest months, when supplies are most strained. And unlike other CII facilities, data centers are ‘always on.’ For these reasons, data centers differ meaningfully from other CII facilities. AB 2469 acts on the need for a new water use classification for large consumptive use facilities such as data centers that addresses these differences.
“Local governments need more information to understand the nature, extent, and timing of data centers’ water use, and to incorporate this information in their decisions. Missing from corporate sustainability reports is site-specific information, as well as information on facilities’ peak demand. Many data centers receive potable water from municipal water systems, and small systems lack the capacity to serve large facilities. By requiring data center project applicants to assess water supply, plan for water scarcity, and report water use as conditions of project approval, AB 2469 would provide counties and cities with needed information to assess projects’ impacts.
“By requiring data center project applicants to assume responsibility for the costs of water infrastructure additions required to serve their needs, AB 2469 would also ensure ratepayers do not end up bearing the costs of infrastructure they do not create demand for. This principle is consistent with the “proportional cost of service” requirement in California’s Constitution. Additionally, the bill appropriately allocates risk to project applicants, ensuring that if a facility closes prematurely, water suppliers and ultimately ratepayers will not end up footing the bill for disused infrastructure.”
- Arguments in Opposition. California State Association of Counties, League of California Cities, and the Rural County Representatives of California, in an “oppose unless amended” position, write, “In general, we support providing more information to local government permitting authorities in order to guide the best possible decision-making outcomes for data centers. We also recognize that the rapid expansion of artificial intelligence data centers poses both potential for economic growth benefiting communities, as well as risks to local energy and water supplies. We support empowering local governments to have the best data possible for permitting these data centers, so that each community can make the land use decisions best suited to their residents.
“AB 2469, as currently written, undermines this locally-driven approach by preempting local governments from making permitting decisions in the absence of the extensive new water use assessment process mandated by the bill. Further, the bill forbids new data center projects in areas designated as a critically overdrafted groundwater basin under the Sustainable Groundwater Management Act, absent a waiver from the Department of Water Resources. The problems that this bill is seeking to address are real; the impacts on local utilities from data centers and the potential strain on depleted groundwater supplies are important to factor into land use decisions. However, taking away local authority to permit these projects undermines local governments’ ability to protect and represent their communities through established permitting mechanisms and community engagement processes.
“Local governments are best suited to understand the potential costs and benefits of data center projects in their communities. The Legislature can best support communities by crafting collaborative efforts to gather more information about projects in a manner that does not unduly constrain local governments.”
- Double-Referral. This bill is double-referred to the Water, Parks and Wildlife Committee, where it passed on a 9-2 vote on April 14, 2026.
REGISTERED SUPPORT / OPPOSITION:
Support
California Coastkeeper Alliance
Opposition
Bay Area Council
Building Owners and Managers Association of California
Calasian Chamber of Commerce
California African American Chamber of Commerce
California Business Properties Association
California Chamber of Commerce
California Hispanic Chambers of Commerce (CHCC)
California State Association of Counties (CSAC) (unless amended)
Data Center Coalition
League of California Cities (unless amended)
Naiop California
Rural County Representatives of California (RCRC) (unless amended)
Silicon Valley Leadership Group
TechCA
TechNet
Analysis Prepared by: Angela Mapp / L. GOV. / (916) 319-3958
Date of Hearing: April 14, 2026
ASSEMBLY COMMITTEE ON WATER, PARKS, AND WILDLIFE
Diane Papan, Chair
ABPCA Bill Id:AB 2469 (
Author:Papan) – As Amended Ver:April 8, 2026
SUBJECT: Data centers: water use disclosures
SUMMARY: Prohibits a local agency from approving construction of a new, or expansion of an existing, data center unless an applicant for a data center project provides the local agency with detailed information regarding the data center’s water use and meets other requirements related to workforce and infrastructure for the data center. Specifically, this bill:
- Defines “water scarcity plan” as a report that includes measures to be implemented under different drought scenarios defined by the U.S. Drought Monitor to reduce water use.
- Defines “water use assessment” as a report that includes a description of a data center and its operations and the following information regarding water use by the data center:
- A detailed accounting of water intake expressed in gallons per day and total volume, including maximum and average daily demand, maximum and average monthly demand, demand over an average 12-month period, water withdrawals, phases of growth or expansion, trigger points for additional demand, full build-out and peak operation scenarios;
- A detailed explanation of each direct water use including specified information regarding cooling systems, humidification, potable and sanitary uses, fire suppression systems, and maintenance operations;
- A cooling alternatives analysis that compares the proposed cooling method to a range of alternatives including evaluation of water use at the data center and at the site of energy generation, an evaluation of impact on source water and water scarcity, and consideration of closed-loop cooling;
- A detailed estimate of indirect water use associated with energy production disaggregated by type; and
- A cost of service study completed by the applicable water supplier within the last five years, or funded by the data center if none exists.
- Prohibits a city, county, or city and county from approving the construction, or expansion that increases the maximum peak water use, of a data center unless the following conditions are satisfied:
- The applicant has provided a water supply assessment;
- The applicant has provided a water use assessment, if requested by the city, county, or city and county;
- The applicant, beginning January 1, 2028, has provided a water scarcity plan;
- The applicant has provided the data center’s projected and actual water use and water efficiency measures;
- The applicant has made specified disclosures regarding workforce needs associated with the project;
- The applicant has provided all water resource plans, water usage reports, supporting documentation, and any approval issues by a state or local agency related to the plans or applications;
- The project is not located in a groundwater basin designated as critically overdrafted by the Department of Water Resources (DWR). DWR may waive this prohibition upon a comprehensive assessment demonstrating the project does not pose a disproportionate risk to the health, welfare, or environment of an environmental justice community or equity investment eligible community; and
- The applicant assumes responsibility for the full cost of any required water conveyance, treatment or storage, or distribution infrastructure improvements necessary to serve the project as determined by DWR or the applicable water supplier.
- Requires DWR, in coordination with the State Water Resources Control Board (State Water Board), to conduct necessary studies and investigations and recommend no later than June 30, 2028 a commercial, industrial, institutional (CII) water use classification system for users that qualify as large consumptive use facilities, including data centers.
- Requires the State Water Board in coordination with DWR to adopt the CII water use classification recommended by DWR pursuant to this bill by December 31, 2029.
- Requires each urban retail water supplier to implement the CII water use classification adopted pursuant to this bill.
EXISTING LAW:
- Requires DWR, in coordination with the State Water Board, to conduct studies and investigations to develop recommendations for efficient water use by commercial, industrial, and institutional (CII) water users by October 1, 2021. The State Water Board shall adopt performance measures for CII water use based on these recommendations by June 30, 2022 (Water Code § 10609.10).
- Requires a water supplier to prepare a water supply assessment for a residential, commercial, or industrial project that must undergo review under the California Environmental Quality Act (CEQA) and will use more than a specified amount of water (see discussion under Background, below). The water supply assessment must contain information regarding the project’s water use and the ability of the water supplier to meet the project’s water demands (Water Code § 10910 et seq.).
- Requires DWR to investigate the state’s groundwater basins and, among other things, identify basins that are subject to critical conditions of overdraft (Water Code § 12924).
FISCAL EFFECT: Unknown. This bill is keyed fiscal.
COMMENTS:
- Purpose of this bill. According to the author,
California’s finite water supplies are under growing stress from climate change, prolonged droughts, and the expansion of large consumptive water users. While the Legislature has long recognized the importance of coordinating land use decisions with available water supplies, the rapid growth of data centers has exposed gaps in existing law. Data centers represent a new kind of development that can impose significant, highly concentrated water demands on local systems.
This gap is particularly important because data centers operate continuously and can drive substantial peak-day demand, often requiring new treatment, storage, or distribution infrastructure. Without timely and standardized information during the entitlement process, municipalities and water retailers may lack clear visibility into a project’s water needs and the leverage to ensure that adequate supplies, infrastructure capacity, and conservation measures are in place prior to entering into service commitments.
[This bill] directly addresses these water management difficulties. [This bill] requires meaningful water planning before local approval and protects critically overdrafted groundwater basins. In doing so, [this bill] provides local governments and water suppliers the information they need to evaluate data center water demand before making irreversible siting and infrastructure decisions.
- Background. Data centers are buildings or facilities that “support servers, digital storage equipment, and network infrastructure for the purpose of large-scale data processing and data storage. Increasing demand for data creation, processing, and storage from existing and emerging technologies, such as online platforms/social media, video streaming, smart and connected infrastructure, autonomous vehicles, and artificial intelligence, has led to exponential growth in data center workloads and compute instances.”[1] There is increasing awareness of the energy and water demands (primarily related to cooling) associated with data centers as artificial intelligence (AI) and other technologies are being deployed.
While California has been home to data centers for decades, in recent years, developments in technology have increased the demand for large data centers capable of storing, processing, and serving huge amounts of data. California is a desirable destination for data center projects, with a highly skilled workforce, close proximity to computing demand, and access to large fiber optic connections around the world. Clusters of data centers exist in Silicon Valley, San Francisco, Los Angeles, and Sacramento, with other projects located around the state.
Cooling technology and water demand. Data centers can have substantial and sometimes irregular demand for cooling water. All computer chips produce heat as waste energy from the electricity flowing through them. While this heat is minimal in the context of a personal computer, data centers made up of thousands of servers produce an immense amount of heat that needs to be removed from the facility to maintain safety and performance. To manage this heat, data centers use a variety of cooling technologies, including:
- Air-based cooling. Chilled air is circulated through server racks using computer room air conditioners or air handlers to remove heat from equipment.
- Chilled water systems. Mechanical chillers produce chilled water that absorbs heat from servers through heat exchangers before the heat is rejected outdoors.
- Evaporative cooling systems. Cooling towers or evaporative coolers use the evaporation of water to remove heat, which can significantly reduce electricity use but increases water consumption.
- Liquid cooling. Coolant is delivered directly to server components or through cold plates and immersion systems, allowing heat to be removed more efficiently than with air cooling.
- Economization technologies. Air-side or water-side economizers take advantage of cool outdoor air or water temperatures to reduce the need for mechanical cooling when environmental conditions allow.
Many data centers combine several technologies either sequentially or depending on weather conditions and server load. The blend of possible technologies introduces tradeoffs between electricity and water use (and between onsite and offsite water use).
Irregular water demand and peak use. Data center water use patterns can be irregular as a result of switching between cooling technologies. Research shows that the “peaking factor” (the factor of the peak use over average use) for data centers can be double or more the peaking factor for other large users.[2]. These high peaks occur because data centers need to shift to evaporative cooling technologies to exhaust waste heat during hot and dry weather conditions, or use more water to remove more heat. Shifting between cooling technologies can result in large surges in demand that need to be accommodated by water distribution infrastructure, even if the average demand is far lower.
Consumptive water use. Evaporative cooling systems, like those sometimes used in data centers, are consumptive uses of water. This bill would require data center operators to distinguish their consumptive and nonconsumptive water uses. Consumptive water uses refers to water that is withdrawn or diverted from the environment that is made unavailable for future use because it has evaporated, transpired, been incorporated into products or crops, or otherwise been made unavailable for immediate use. In contrast, non-consumptive uses of water quickly return to the environment. Examples of non-consumptive use include recreation, hydroelectric power generation, or instream flow.
Scale of potential demand. Existing and proposed data centers range from relatively small “edge” or collocated facilities to huge “hyperscalers,” including a proposed $10 billion, 330 MW project in Imperial County that could use as much as 750,000 gallons of water per day. As data centers continue to surge in growth, concerns about data center water use are driving discussions around sustainability, evaluations of appropriate location siting and available supply.
Implications for water infrastructure. Data centers need a reliable water supply. Due to the reliability requirement to deliver the demanded water, water infrastructure (both water delivery and wastewater) must be sized to accommodate the peaks in demand. Local water suppliers are then required to build capacity well in excess of average need and potentially may build capacity in excess of any need that materializes, especially if they are building based on limited information about projected water demand.
Absent reliable information about expected usage, water infrastructure decisions are based on estimates and projections that may or may not be borne out. In practice, this limited visibility compounds the general trend across California water agencies to project (and build for) higher water use than is actually realized.[3] In addition to overbuilding for capacity, local water suppliers risk stranded assets if data center projects either do not materialize or close. In an industry characterized by many proposed projects with fewer constructed projects and rapid obsolescence of cutting-edge technology, these risks are meaningful and may exacerbate concerns over water affordability.
Improving planning and coordination. Better data about water use, whether during the water supply assessment process (if required, see discussion below) or based on research data from across the sector, would assist local water agencies in planning for actual need. Local water utilities could also work with data centers to understand options for the times of highest demand and collaborate on strategies to deliver water supply reliability.[4] The risk of stranded or overbuilt assets can be mitigated by requiring new large customers to pay for necessary infrastructure upgrades as part of the connection process, potentially extending beyond traditional connection fees to include upgrades to mains, pumping stations, and other infrastructure as needed.
CII water use. Water use by data centers falls under the CII classification, but is not calculated under the urban water use objective (“Making Conservation A Way of Life”) intended to increase water use efficiency in California's urban areas. However, as required by the legislative package to enact Making Conservation a Way of Life, DWR conducted a study (completed in 2022) on CII water use and recommended performance measures to the State Water Board that would improve water use efficiency in the CII sector. One of the study’s recommendations was to require urban retail water suppliers to classify their CII users by one of 19 user types (e.g., manufacturing/industrial, technology/science). The State Water Board incorporated this recommendation into the final Making Conservation a Way of Life regulations by requiring urban retail water suppliers to classify CII users into one of 22 categories by June 30, 2027; the categories are based on the ENERGY STAR Portfolio Manager categories. This bill requires DWR to develop a separate classification for CII users based on their consumptive use of water by _____.
Water supply assessments. A water supply assessment is required for a proposed project (CII or otherwise) with a water use that exceeds certain thresholds and is completed as part of the CEQA process. The water use thresholds that trigger a water supply assessment are as follows (Water Code § 10912):
- A proposed residential development of more than 500 dwelling units;
- A proposed shopping center or business establishment employing more than 1,000 persons or having more than 500,000 square feet of floor space;
- A proposed commercial office building employing more than 1,000 persons or having more than 25,000 square feet of floor space;
- A proposed hotel or motel that has more than 500 rooms;
- A proposed industrial, manufacturing, or processing plant, or industrial park planned to house more than 1,000 persons, occupying more than 40 acres of land, or having more than 650,000 square feet of floor area;
- A proposed mixed-use project that includes one or more of the above; and
- A proposed project that would demand an amount of water equivalent to, or greater than, the amount of water required by a 500 dwelling unit project.
To complete the water supply assessment, the project proponent must provide information to municipal planning decisionmakers about the expected water use. The water supply assessment process provides the primary opportunity for public input and awareness of water use by a proposed CII (or other) water user.
- Arguments in support. The California Coastkeeper Alliance supports this bill and argues that it will inform local decision-making, condition data center project approvals on meeting necessary requirements, and avoid increased water rates resulting from data center water demand. California Coastkeeper Alliance states: “By requiring data center project applicants to assume responsibility for the costs of water infrastructure additions required to serve their needs, [this bill] would also ensure ratepayers do not end up bearing the costs of infrastructure they do not create demand for. This principle is consistent with the “proportional cost of service” requirement in California’s Constitution. Additionally, the bill appropriately allocates risk to project applicants, ensuring that if a facility.”
- Oppose unless amended. The California State Association of Counties (CSAC) has taken an “oppose unless amended” position on this bill noting that “the problems this bill is seeking to address are real.” However, CSAC contends this bill will interfere with the local decision-making process and impose new requirements on local agencies to review the water use assessment this bill creates that will increase local agency costs. CSAC states “Local governments are best suited to understand the potential costs and benefits of data center projects in their communities. The Legislature can best support communities by crafting collaborative efforts to gather more information about projects in a manner that does not unduly constrain local governments.” CSAS expresses a desire to work with the author to amend this bill to “preserve local permitting authority,” “address the proposed state waiver process” (by DWR for critically over-drafted groundwater basins), and “avoid imposing new costs to local governments.”
- Arguments in opposition. The Data Center Coalition opposes this bill and maintains it imposes “additional burdensome and disparate reporting requirements on data centers as compared to other” CII users, raises privacy and security concerns, and will undermine California’s already shrinking data center market. Rather than placing unique requirements on data centers, the Data Center Coalition asserts “a more equitable approach would acknowledge that data centers are just one water consumer among many diverse industries. Data center operators are actively prioritizing responsible water use through operational best practices and innovative development strategies, often collaborating with local authorities and conservation organizations on water restoration and reclamation projects.”
- Dual referral. This bill has also been referred to the Assembly Local Government Committee.
- Related legislation. AB 2619 (Papan) of the current legislative session requires data center developers to provide information on water use to water suppliers and local governments prior to being issued a business license and upon renewal of a business license, and requires urban water suppliers to consider data center demand in water shortage planning. AB 2619 is also set for hearing in this Committee on April 14, 2026.
AB 1577 (Bauer-Kahan) of the current legislative session, among other provisions, requires a data center to submit total water consumption, potable water consumption, and water usage effectiveness to the California Energy Commission on a monthly basis. AB 1577 is pending in the Assembly Utilities and Energy Committee.
SB 887 (Padilla) of the current legislative session specifies that development and operation of a data center is not eligible for a California Environmental Quality Act (CEQA) categorical exemption, and authorizes data centers meeting specified criteria to be eligible for the “environmental leadership development” program which provides CEQA judicial streamlining. SB 887 is pending in the Senate Energy, Utilities, and Communication Committee.
AB 93 (Papan) of 2025 would have required a data center operator to provide its estimated or actual water use to its water supplier as a condition of obtaining or renewing a business license issued by a city or county. AB 93 was vetoed by Governor Newsom. The veto message states:
This bill requires data centers, when applying for an initial business license, to provide to their water supplier an estimate of expected water use. It further requires data centers, when applying for a renewal of a business license, to provide their water supplier with a report on annual water use.
The widespread adoption of artificial intelligence technologies is driving an unprecedented demand for data center capacity throughout the nation. As the global epicenter of the technology sector, California is well positioned to support the development of this critically important digital infrastructure in the state.
While I appreciate the author's intent, I am reluctant to impose rigid reporting requirements about operational details on this sector without understanding the full impact on businesses and the consumers of their technology.
AB 222 (Bauer-Kahan) of 2025 requires developers of AI models to estimate energy use associated with using the AI model, requires data centers to report energy use to the California Energy Commission, and requires the California Energy Commission to adopt efficiency standards for data centers. AB 222 was held in the Senate Appropriations Committee.
SB 57 (Padilla), Chapter 647, Statutes of 2025, authorizes the California Public Utilities Commission to conduct a specified assessment of electrical corporations’ potential costs and rate impacts associated with serving new electrical loads from data centers.
SB 1298 (Cortese) of 2024 would have authorized the California Energy Commission to exempt from certification a thermal power plant with generating capacity of up to 150 megawatts that is to be used solely as a backup generation facility for a data center, if certain conditions are met. SB 1298 was held on the Assembly Floor.
REGISTERED SUPPORT / OPPOSITION:
Support
California Coastkeeper Alliance
Oppose Unless Amended
California State Association of Counties
League of California Cities
Rural County Representatives of California
Opposition
Bay Area Council
Building Owners and Managers Association of California
CalAsian Chamber of Commerce
California African American Chamber of Commerce
California Business Properties Association
California Chamber of Commerce
California Hispanic Chambers of Commerce
Data Center Coalition
NAIOP Commercial Real Estate Development Association of California
Silicon Valley Leadership Group
TechCA
Technet
Analysis Prepared by: Pablo Garza / W., P., & W. / (916) 319-2096
Md Abu Bakar Siddik, Arman Shehabi, and Landon Marston, “The Environmental Footprint of Data Centers in the United States,” Environmental Research Letters, 16 (2021). ↑
Yuelin Han, Pengfei Li, Adam Wierman, and Shaolei Ren, “Small Bottle, Big Pipe: Quantifying and Addressing the Impact of Data Centers on Public Water Systems,” arXiv preprint, doi:10.48550/arXiv.2603.02705 (2026). ↑
Johanna A. Capone and Landon T. Marston, “Water Demand Projection Accuracy and Demand Management Trends in California Cities,” Water Resources Research 61, no. 11 (2025). ↑
Marie Grimm, Nell Green Nylen, and Michael Kiparsky, Regulating Data Center Water Use in California, (Center for Law, Energy & the Environment, UC Berkeley School of Law, Berkeley, CA: 2026), 40-43. See https://www.law.berkeley.edu/data-center-water-use. ↑
Discussed in Hearing
Assembly Floor
Senate Floor
Senate Standing Committee on Appropriations
Senate Standing Committee on Local Government
Senate Standing Committee on Natural Resources and Water
Senate Standing Committee on Natural Resources and Water
Assembly Floor
Assembly Standing Committee on Local Government
Bill Author
Bill Co-Author(s):