SB 1147: Hazardous materials: aboveground storage tanks.
- Session Year: 2015-2016
- House: Senate
- Latest Version Date: 2016-04-06
The Aboveground Petroleum Storage Act generally regulates aboveground storage tanks that contain petroleum and that meet certain requirements. The act requires the owner or operator of an aboveground storage tank that meets certain specifications to prepare a spill prevention control and countermeasure plan and to implement the plan in compliance with specified federal law. The act defines an aboveground storage tank as a tank that has the capacity to store 55 gallons or more of petroleum and that is substantially or totally above the surface of the ground or a tank in an underground area, as defined, except for certain types of tanks and vessels.
This bill would prohibit a city, county, or city and county from enforcing standards for aboveground storage tanks that are more stringent than state or federal standards for aboveground storage tanks unless the city, county, or city and county first adopts an ordinance establishing those standards.
The Aboveground Petroleum Storage Act, implemented by the unified program agencies, generally regulates aboveground storage tanks that contain petroleum and that meet certain requirements. The act requires the owner or operator of an aboveground storage tank that meets certain specifications to prepare a spill prevention control and countermeasure plan and to implement the plan in compliance with specified federal law. The act requires the unified program agency to inspect each storage tank or a representative sampling of the storage tanks at a single location at least once every 3 years for purposes of determining whether the owner or operator is in compliance with that plan. The act defines an aboveground storage tank as a tank that has the capacity to store 55 gallons or more of petroleum and that is substantially or totally above the surface of the ground or a tank in an underground area, as defined, except for certain types of tanks and vessels.
This bill would require an aboveground storage tank with a storage capacity of more than 1,100 gallons to be replaced when the storage tank reaches the end of its useful life, as determined by the manufacturers guidelines, and would require an aboveground storage tank with a storage capacity of more than 5,000 gallons purchased before January 1, 2017, to be replaced on or before December 31, 2027. The bill would require an aboveground storage tank of any capacity to be replaced if it presents an immediate risk to public health or safety or the environment. The bill would require a storage tank required to be replaced pursuant to these provisions to be replaced with a storage tank that meets a certain standard. The bill would require an aboveground storage tank purchased on and after January 1, 2017, to meet that same standard. To the extent it would impose additional duties on the unified program agencies, this bill would impose a state-mandated local program.
The California Constitution requires the state to reimburse local agencies and school districts for certain costs mandated by the state. Statutory provisions establish procedures for making that reimbursement.
This bill would provide that no reimbursement is required by this act for a specified reason.
The Aboveground Petroleum Storage Act, implemented by the unified program agencies, generally regulates aboveground storage tanks that contain petroleum and that meet certain requirements. The act requires the owner or operator of an aboveground storage tank that meets certain specifications to prepare a spill prevention control and countermeasure plan and to implement the plan in compliance with specified federal law. The act requires the unified program agency to inspect each storage tank or a representative sampling of the storage tanks at a single location at least once every 3 years for purposes of determining whether the owner or operator is in compliance with that plan. The act defines an aboveground storage tank as a tank that has the capacity to store 55 gallons or more of petroleum and that is substantially or totally above the surface of the ground or a tank in an underground area, as defined, except for certain types of tanks and vessels.
This bill would require an aboveground storage tank with a storage capacity of more than 1,100 gallons to be replaced when the storage tank reaches the end of its useful life, as determined by the manufacturers guidelines, and would require an aboveground storage tank with a storage capacity of more than 5,000 gallons purchased before January 1, 2017, to be replaced on or before December 31, 2027. The bill would require an aboveground storage tank of any capacity to be replaced if it presents an immediate risk to public health or safety or the environment. The bill would require a storage tank required to be replaced pursuant to these provisions to be replaced with a storage tank that meets a certain standard. The bill would require an aboveground storage tank purchased on and after January 1, 2017, to meet that same standard. To the extent it would impose additional duties on the unified program agencies, this bill would impose a state-mandated local program.
The California Constitution requires the state to reimburse local agencies and school districts for certain costs mandated by the state. Statutory provisions establish procedures for making that reimbursement.
This bill would provide that no reimbursement is required by this act for a specified reason.
The Aboveground Petroleum Storage Act generally regulates aboveground storage tanks that contain petroleum and that meet certain requirements. The act defines an aboveground storage tank as a tank that has the capacity to store 55 gallons or more of petroleum and that is substantially or totally above the surface of the ground or a tank in an underground area, as defined, except for certain types of tanks and vessels. Existing law makes a violation of certain provisions of the act a crime.
This bill would amend the definition of aboveground storage tank to mean a tank that has the capacity to store 55 gallons or more of transportation fuel and that is substantially or totally above the surface of the ground or a tank in an underground area, as defined, except for certain types of tanks and vessels. The bill would define transportation fuel to include petroleum, ethanol, and biodiesel.
By expanding the kinds of aboveground storage tanks that would be regulated by the act, the bill would expand the application of a crime, thereby imposing a state-mandated local program.
The California Constitution requires the state to reimburse local agencies and school districts for certain costs mandated by the state. Statutory provisions establish procedures for making that reimbursement.
This bill would provide that no reimbursement is required by this act for a specified reason.
The Aboveground Petroleum Storage Act generally regulates aboveground storage tanks that contain petroleum and that meet certain requirements. The act defines an aboveground storage tank as a tank that has the capacity to store 55 gallons or more of petroleum and that is substantially or totally above the surface of the ground or a tank in an underground area, as defined, except for certain types of tanks and vessels. Existing law makes a violation of certain provisions of the act a crime.
This bill would amend the definition of aboveground storage tank to mean a tank that has the capacity to store 55 gallons or more of transportation fuel and that is substantially or totally above the surface of the ground or a tank in an underground area, as defined, except for certain types of tanks and vessels. The bill would define transportation fuel to include petroleum, ethanol, and biodiesel.
By expanding the kinds of aboveground storage tanks that would be regulated by the act, the bill would expand the application of a crime, thereby imposing a state-mandated local program.
The California Constitution requires the state to reimburse local agencies and school districts for certain costs mandated by the state. Statutory provisions establish procedures for making that reimbursement.
This bill would provide that no reimbursement is required by this act for a specified reason.
A city, county, or city and county shall not enforce standards for aboveground storage tanks that are more stringent than state or federal standards for aboveground storage tanks unless the city, county, or city and county first adopts an ordinance establishing those standards.
SECTION 1.Chapter 6.78 (commencing with Section 25299.210) is added to Division 20 of the Health and Safety Code, to read:6.78.Aboveground Storage Tank Standard25299.210.For purposes of this chapter, aboveground storage tank or storage tank has the same meaning specified in Section 25270.2.
25299.215.(a)An aboveground storage tank with a storage capacity of more than 1,100 gallons shall be replaced when the storage tank reaches the end of its useful life, as determined by the manufacturers guidelines.
(b)Notwithstanding subdivision (a), an aboveground storage tank with a storage capacity of more than 5,000 gallons that was purchased before January 1, 2017, shall be replaced on or before December 31, 2027.
(c)An aboveground storage tank of any storage capacity shall be replaced if the storage tank presents an immediate risk to public health or safety or the environment.
(d)An aboveground storage tank required to be replaced pursuant to this section shall be replaced with a storage tank that meets UL 142, the Standard for Safety for Steel Aboveground Tanks for Flammable and Combustible Liquids, as established by Underwriters Laboratories.
25299.220.An aboveground storage tank purchased on and after January 1, 2017, shall meet UL 142, the Standard for Safety for Steel Aboveground Tanks for Flammable and Combustible Liquids, as established by Underwriters Laboratories.
SEC. 2.No reimbursement is required by this act pursuant to Section 6 of Article XIIIB of the California Constitution because a local agency or school district has the authority to levy service charges, fees, or assessments sufficient to pay for the program or level of service mandated by this act, within the meaning of Section 17556 of the Government Code.
For purposes of this chapter, aboveground storage tank or storage tank has the same meaning specified in Section 25270.2.
25299.215.(a)An aboveground storage tank with a storage capacity of more than 1,100 gallons shall be replaced when the storage tank reaches the end of its useful life, as determined by the manufacturers guidelines.
(b)Notwithstanding subdivision (a), an aboveground storage tank with a storage capacity of more than 5,000 gallons that was purchased before January 1, 2017, shall be replaced on or before December 31, 2027.
(c)An aboveground storage tank of any storage capacity shall be replaced if the storage tank presents an immediate risk to public health or safety or the environment.
(d)An aboveground storage tank required to be replaced pursuant to this section shall be replaced with a storage tank that meets UL 142, the Standard for Safety for Steel Aboveground Tanks for Flammable and Combustible Liquids, as established by Underwriters Laboratories.
25299.220.An aboveground storage tank purchased on and after January 1, 2017, shall meet UL 142, the Standard for Safety for Steel Aboveground Tanks for Flammable and Combustible Liquids, as established by Underwriters Laboratories.
SEC. 2.No reimbursement is required by this act pursuant to Section 6 of Article XIIIB of the California Constitution because a local agency or school district has the authority to levy service charges, fees, or assessments sufficient to pay for the program or level of service mandated by this act, within the meaning of Section 17556 of the Government Code.
All matter omitted in this version of the bill appears in the bill as introduced in the Senate, February 18, 2016. (JR11)For purposes of this chapter, the following definitions apply:
(a)Aboveground storage tank or storage tank means a tank that has the capacity to store 55 gallons or more of petroleum transportation fuel that is substantially or totally above the surface of the ground, except that, for purposes of this chapter, aboveground storage tank or storage tank includes a tank in an underground area. Aboveground storage tank does not include any of the following:
(1)A pressure vessel or boiler that is subject to Part 6 (commencing with Section 7620) of Division 5 of the Labor Code.
(2)A tank containing hazardous waste or extremely hazardous waste, as respectively defined in Sections 25117 and 25115, if the Department of Toxic Substances Control has issued the person owning or operating the tank a hazardous waste facilities permit for the storage tank.
(3)An aboveground oil production tank that is subject to Section 3106 of the Public Resources Code.
(4)Oil-filled electrical equipment, including, but not limited to, transformers, circuit breakers, or capacitors, if the oil-filled electrical equipment meets either of the following conditions:
(A)The equipment contains less than 10,000 gallons of dielectric fluid.
(B)The equipment contains 10,000 gallons or more of dielectric fluid with PCB levels less than 50 parts per million, appropriate containment or diversionary structures or equipment are employed to prevent discharged oil from reaching a navigable water course, and the electrical equipment is visually inspected in accordance with the usual routine maintenance procedures of the owner or operator.
(5)A tank regulated as an underground storage tank under Chapter 6.7 (commencing with Section 25280) of this division and Chapter 16 (commencing with Section 2610) of Division 3 of Title 23 of the California Code of Regulations and that does not meet the definition of a tank in an underground area.
(6)A transportation-related tank facility, subject to the authority and control of the United States Department of Transportation, as defined in the Memorandum of Understanding between the Secretary of Transportation and the Administrator of the United States Environmental Protection Agency, as set forth in Appendix A to Part 112 (commencing with Section 112.1) of Subchapter D of Chapter I of Title 40 of the Code of Federal Regulations.
(7)A tank or tank facility located on and operated by a farm that is exempt from the federal spill prevention, control, and countermeasure rule requirements pursuant to Part 112 (commencing with Section 112.1) of Subchapter D of Chapter I of Title 40 of the Code of Federal Regulations.
(b)Board means the State Water Resources Control Board.
(c)(1)Certified Unified Program Agency or CUPA means the agency certified by the Secretary for Environmental Protection to implement the unified program specified in Chapter 6.11 (commencing with Section 25404) within a jurisdiction.
(2)Participating Agency or PA means an agency that has a written agreement with the CUPA pursuant to subdivision (d) of Section 25404.3, and is approved by the secretary, to implement and enforce the unified program element specified in paragraph (2) of subdivision (c) of Section 25404, in accordance with Sections 25404.1 and 25404.2.
(3)(A)Unified Program Agency or UPA means the CUPA, or its participating agencies to the extent that each PA has been designated by the CUPA, pursuant to a written agreement, to implement and enforce the unified program element specified in paragraph (2) of subdivision (c) of Section 25404. The UPAs have the responsibility and authority, to the extent provided by this chapter and Sections 25404.1 to 25404.2, inclusive, to implement and enforce the requirements of this chapter.
(B)After a CUPA has been certified by the secretary, the unified program agency shall be the only agency authorized to enforce the requirements of this chapter.
(C)This paragraph does not limit the authority or responsibility granted to the office, the board, and the regional boards by this chapter.
(d)Office means the Office of the State Fire Marshal.
(e)Operator means the person responsible for the overall operation of a tank facility.
(f)Owner means the person who owns the tank facility or part of the tank facility.
(g)Person means an individual, trust, firm, joint stock company, corporation, including a government corporation, partnership, limited liability company, or association. Person also includes any city, county, district, the University of California, the California State University, the state, any department or agency thereof, and the United States, to the extent authorized by federal law.
(h)Petroleum Transportation fuel means crude all of the following:
(1)Crude oil, or a fraction thereof, that is liquid at 60 degrees Fahrenheit temperature and 14.7 pounds per square inch absolute pressure.
(2)Ethanol.
(3)Biodiesel.
(i)Regional board means a California regional water quality control board.
(j)Release means any spilling, leaking, pumping, pouring, emitting, emptying, discharging, escaping, leaching, or disposing into the environment.
(k)Secretary means the Secretary for Environmental Protection.
(l)Storage or store means the containment, handling, or treatment of petroleum, transportation fuel, for a period of time, including on a temporary basis.
(m)Storage capacity means the aggregate capacity of all aboveground storage tanks at a tank facility.
(n)Tank facility means one or more aboveground storage tanks, including any piping that is integral to the tanks, that contain petroleum transportation fuel and that are used by an owner or operator at a single location or site. For purposes of this chapter, a pipe is integrally related to an aboveground storage tank if the pipe is connected to the tank and meets any of the following:
(1)The pipe is within the dike or containment area.
(2)The pipe is between the containment area and the first flange or valve outside the containment area.
(3)The pipe is connected to the first flange or valve on the exterior of the tank, if state or federal law does not require a containment area.
(4)The pipe is connected to a tank in an underground area.
(o)(1)Tank in an underground area means a storage tank to which all of the following apply:
(A)The storage tank is located in a structure that is at least 10 percent below the ground surface, including, but not limited to, a basement, cellar, shaft, pit, or vault.
(B)The structure in which the storage tank is located, at a minimum, provides for secondary containment of the contents of the tank, piping, and ancillary equipment, until cleanup occurs. A shop-fabricated double-walled storage tank with a mechanical or electronic device used to detect leaks in the interstitial space meets the requirement for secondary containment of the contents of the tank.
(C)The storage tank meets one or more of the following conditions:
(i)The storage tank contains petroleum transportation fuel to be used or previously used as a lubricant or coolant in a motor engine or transmission, oil-filled operational equipment, or oil-filled manufacturing equipment, is situated on or above the surface of the floor, and the structure in which the tank is located provides enough space for direct viewing of the exterior of the tank except for the part of the tank in contact with the surface of the floor.
(ii)The storage tank only contains petroleum transportation fuel that is determined to be a hazardous waste, complies with the hazardous waste tank standards pursuant to Article 10 (commencing with Section 66265.190) of Chapter 15 of Title 22 of the California Code of Regulations as it may be amended, and the tank facility has been issued a unified program facility permit pursuant to Section 25404.2 for generation, treatment, accumulation, or storage of hazardous waste.
(iii)The storage tank contains petroleum transportation fuel and is used solely in connection with a fire pump or an emergency system, legally required standby system, or optional standby system as defined in the most recent version of the California Electrical Code (Section 700.2 of Article 700, Section 701.2 of Article 701, and Section 702.2 of Article 702, of Chapter 7 of Part 3 of Title 24 of the California Code of Regulations), is situated on or above the surface of the floor, and the structure in which the tank is located provides enough space for direct viewing of the exterior of the tank except for the part of the tank in contact with the surface of the floor.
(iv)The storage tank does not meet the conditions in clauses (i), (ii), or (iii), but meets all of the following conditions:
(I)It contains petroleum. transportation fuel.
(II)It is situated on or above the surface of the floor.
(III)The structure in which the tank is located provides enough space for direct viewing of the exterior of the tank, except for the part of the tank in contact with the surface of the floor, and all piping connected to the tank, including any portion of a vent line, vapor recovery line, or fill pipe that is beneath the surface of the ground, and all ancillary equipment, can either be visually inspected by direct viewing or has both secondary containment and leak detection that meet the requirements of the regulations adopted by the office pursuant to Section 25270.4.1.
(2)For a shop-fabricated double-walled storage tank, direct viewing of the exterior of the tank is not required under paragraph (1) if inspections of the interstitial space are performed or if it has a mechanical or electronic device that will detect leaks in the interstitial space.
(3)(A)A storage tank in an underground area is not subject to Chapter 6.7 (commencing with Section 25280) if the storage tank meets the definition of a tank in an underground area, as provided in paragraph (1) and, except as specified in subparagraph (B), the regulations that apply to all new and existing tanks in underground areas and buried piping connected to tanks in underground areas have been adopted by the office pursuant to Section 25270.4.1.
(B)A storage tank meeting the description of clause (i) of subparagraph (C) of paragraph (1) shall continue to be subject to this chapter, and excluded from the definition of an underground storage tank in Chapter 6.7 (commencing with Section 25280), before and after the date the regulations specific to tanks in underground areas have been adopted by the office.
(p)Viewing means visual inspection, and direct viewing means, in regard to a storage tank, direct visual inspection of the exterior of the tank, except for the part of the tank in contact with the surface of the floor, and, where applicable, the entire length of all piping and ancillary equipment, including all exterior surfaces, by a person or through the use of visual aids, including, but not limited to, mirrors, cameras, or video equipment.
SEC. 2.No reimbursement is required by this act pursuant to Section 6 of Article XIIIB of the California Constitution because the only costs that may be incurred by a local agency or school district will be incurred because this act creates a new crime or infraction, eliminates a crime or infraction, or changes the penalty for a crime or infraction, within the meaning of Section 17556 of the Government Code, or changes the definition of a crime within the meaning of Section 6 of Article XIIIB of the California Constitution.
|
Date
|
Status
|
|---|---|
| Jun 23, 2016 | June 28 set for first hearing canceled at the request of author. |
| Jun 9, 2016 | Referred to Com. on E.S. & T.M. |
| Jun 2, 2016 | Read third time. Passed. (Ayes 38. Noes 0. Page 4145.) Ordered to the Assembly. |
| Jun 2, 2016 | In Assembly. Read first time. Held at Desk. |
| Jun 2, 2016 | Read third time. Passed. (Ayes 38. Noes 0.) Ordered to the Assembly. |
| May 5, 2016 | Read second time. Ordered to third reading. |
| May 4, 2016 | From committee: Do pass. (Ayes 6. Noes 0. Page 3765.) (May 4). |
| May 4, 2016 | From committee: Do pass. (Ayes 6. Noes 0.) (May 4). |
| Apr 29, 2016 | Set for hearing May 4. |
| Apr 28, 2016 | Re-referred to Com. on GOV. & F. |
| Apr 21, 2016 | From committee: Do pass and re-refer to Com. on RLS. (Ayes 7. Noes 0. Page 3643.) (April 20). Re-referred to Com. on RLS. |
| Apr 21, 2016 | From committee: Do pass and re-refer to Com. on RLS. (Ayes 7. Noes 0.) (April 20). Re-referred to Com. on RLS. |
| Apr 6, 2016 | From committee with author's amendments. Read second time and amended. Re-referred to Com. on E.Q. |
| Mar 30, 2016 | From committee with author's amendments. Read second time and amended. Re-referred to Com. on E.Q. |
| Mar 28, 2016 | April 6 hearing postponed by committee. |
| Mar 15, 2016 | Set for hearing April 6. |
| Mar 3, 2016 | Referred to Com. on E.Q. |
| Feb 19, 2016 | From printer. May be acted upon on or after March 20. |
| Feb 18, 2016 | Introduced. Read first time. To Com. on RLS. for assignment. To print. |
|
Date
|
Description
|
Location
|
Votes
|
|
|---|---|---|---|---|
| Jun 2, 2016 | Senate 3rd Reading SB1147 Galgiani | Senate Floor |
Passed |
|
| May 4, 2016 | Do pass | Senate Standing Committee on Governance and Finance |
Passed |
|
| Apr 20, 2016 | Do pass, but first be re-referred to the Committee on [Rules] | Senate Standing Committee on Environmental Quality |
Passed |
This list shows positions taken on this bill by organizations on the date displayed, which is linked to the original source.
Positions by individuals are not included.
Office of Senate Floor Analyses (916) 651-1520 Fax: (916) 327-4478 | SB |
THIRD READING
Bill No: SB 1147
:
SENATE ENVIRONMENTAL QUALITY COMMITTEE: 7-0, 4/20/16
AYES: Wieckowski, Gaines, Bates, Hill, Jackson, Leno, Pavley
SENATE GOVERNANCE & FIN. COMMITTEE: 6-0, 5/4/16
AYES: Hertzberg, Beall, Hernandez, Lara, Moorlach, Pavley
NO VOTE RECORDED: Nguyen
DIGEST: This bill prohibits a city, county, or city and county from enforcing standards for aboveground storage tanks that are more stringent than state or federal standards for aboveground storage tanks unless the city, county, or city and county first adopts an ordinance establishing those standards.
ANALYSIS: Existing federal law requires, pursuant to the federal Spill Prevention Control and Countermeasure (SPCC) rule (40 CFR Part 112), owners and operators of tank facilities to prepare and implement an SPCC Plan which is enforceable by Certified Unified Program Agencies (CUPAs).
Existing state law:
- Establishes the Aboveground Petroleum Storage Act (APSA) (Health and Safety Code §25270 et seq.) which:
- Defines “aboveground storage tank” (AST) as a “tank that has the capacity to store 55 gallons or more of petroleum and that is substantially or totally above the ground,” except as specified.
- Defines “petroleum” as “crude oil, or a fraction thereof, that is liquid at 60 degrees Fahrenheit temperature and 14.7 pounds per square inch absolute pressure.”
- Defines “tank facility” as one or more ASTs, including any piping integral to the tanks, that contain petroleum and that are used by the owner or operator at a single location or site.
- Requires the CUPAs to implement APSA.
- Requires tank facilities with storage capacity between 1,320 gallons and 10,000 gallons to be subject to the requirements of APSA.
- Requires the owner or operator of an AST to prepare a SPCC Plan, periodically inspect the AST, and allow the CUPA to inspect as well.
- Requires CUPAs to inspect tank facilities with a 10,000 gallon minimum total storage capacity at least once every three years.
- Requires the owner or operator to pay a fee to cover implementation costs of APSA.
- Authorizes the State Water Resources Control Board and regional water quality control boards to oversee cleanup or abatement efforts of unauthorized releases from ASTs.
- Requires the Department of Forestry and Fire Protection – Office of the State Fire Marshal (OSFM) to adopt regulations and provide guidance and oversight to CUPAs implementing APSA.
- Allows money in the Waste Discharge Permit Fund to be used by a regional board to remedy a significant unforeseen water pollution problem and other specified actions.
- Authorizes CUPAs to assess administrative penalties on an owner or operator for failing to meet the requirements of APSA and provides that violations of specified APSA requirements are a misdemeanor.
- Allows local tank ordinances to be more stringent than state or federal requirements, but since this bill allows more stringent requirements with an approved ordinance, there does not appear to be a conflict of language.
This bill prohibits a city, county, or city and county from enforcing standards for ASTs that are more stringent than state or federal standards for ASTs unless the city, county, or city and county first adopts an ordinance establishing those standards.
Background
Aboveground petroleum storage program. The APSA directs CUPAs to regulate facilities that store more than 1,320 gallons of petroleum in aggregate, stored in ASTs with capacities of 55 gallons or greater. These facilities typically include large petroleum tank facilities, aboveground fuel tank stations and vehicle repair shops with aboveground petroleum storage tanks, but can also include farms or construction sites. AB 1566 (Wieckowski, Chapter 532, Statutes of 2012) tasked the OSFM with overseeing the CUPAs’ implementation of the APSA and required the State Fire Marshal to adopt regulations governing state oversight of APSA implementation.
All facilities subject to the APSA that store 10,000 gallons or more of petroleum must (1) be inspected at least once every three years by a CUPA, (2) report information about the tank facility to the CUPA, and (3) pay a fee to help cover the cost of the program. Facilities that store between 1,320 gallons and 10,000 gallons of petroleum must only meet the reporting and fee requirements. In addition, most facilities subject to the ASPA must prepare SPCC Plans, but certain farms, logging sites, and construction sites are exempted. Federal regulations require the spill prevention plans to, among other things, describe the oil handling operations, spill prevention practices, discharge or drainage controls, and the personnel, equipment and resources at the facility that are used to prevent oil spills. Facility owners must also periodically inspect the tanks and connected pipes.
Standards for aboveground storage tanks. ASTs must meet certain standards set out in state and local fire codes. Fire codes in California are typically developed and adopted according to the following process:
- A model fire code is developed by the National Fire Protection Association (NFPA).
- The State of California then adopts that model code, with any amendments specific to California, as the California Fire Code.
- Local agencies in California then enact an ordinance to adopt the California Fire Code. Those ordinances may include amendments that are more stringent than the California Fire Code, if the local governing body makes findings that the amendments are necessary because of local climatic, geological, or topographical conditions.
The California Fire Code requires the design, fabrication, and construction of tanks to conform to certain standards developed by the NFPA. These standards include provisions for different types of storage tanks, such as steel tanks without additional protections as well as “protected” steel tanks, which must meet a higher standard. ASTs must generally be protected tanks unless they hold less flammable motor oil. However, the California Fire Code includes some exemptions from these standards for tanks on farms.
Kern County. The Kern County Environmental Health Services Division is the CUPA in Kern County. The Kern County Fire Department also participates in implementing the APSA because it is responsible for issuing permits for storage tanks under the Kern County Fire Code. In 2013, following delegation of oversight responsibility for APSA to the OSFM, Kern County began rigorously enforcing the APSA and identifying tanks as not meeting the required standards in the Kern County Fire Code. These standards require farms to use protected tanks.
A 2016 evaluation of Kern County’s implementation of the Unified Program found that Kern County was not adequately ensuring that violators of the APSA had in fact returned to compliance by replacing tanks that did not meet standards. Accordingly, some tank owners have been told that they must remove their tanks. These owners are concerned that Kern County has been enforcing standards higher than state regulations without first adopting an ordinance.
FISCAL EFFECT: Appropriation: Fiscal Com.: Local:
California Cotton Ginners Association
California Cotton Growers Association
California Fresh Fruit Association
Milk Producers Council
Western Agricultural Processors Association
None received
ARGUMENTS IN SUPPORT: According to the author, SB 1147 improves clarity and consistency to the regulation of ASTs by providing a mechanism for cities and counties to regulate these tanks on the local level. The author states that recently, there have been concerns in Kern County where ASTs have been “red-tagged” for being out-of-compliance with County standards. Statewide, ASTs are required to meet UL 142 (the Standard for Safety for Steel Aboveground Tanks for Flammable and Combustible Liquids as established by Underwriters Laboratories); however, Kern County has required tanks to meet more stringent standards and have done so without adopting a local ordinance. The author asserts that SB 1147 maintains local regulation and resolves this issue by requiring cities and counties to adopt an ordinance prior to enforcing AST standards that are more stringent than state or federal AST standards.
5/6/16 14:26:28
SENATE COMMITTEE ON GOVERNANCE AND FINANCE
Senator Robert M. Hertzberg, Chair
2015 - 2016 Regular
Bill No: | SB 1147 | Hearing Date: | 5/4/16 |
Author: | Galgiani | Tax Levy: | No |
Version: | 4/6/16 | Fiscal: | No |
Consultant: | Favorini-Csorba | ||
Hazardous materials: aboveground storage tanks
Requires local governments to adopt an ordinance prior to enforcing standards on aboveground storage tanks that are more stringent than state standards.
Background
Unified Program. State law requires the Secretary of the California Environmental Protection Agency (CalEPA) to establish a unified hazardous waste and hazardous materials management regulatory program, known as the “Unified Program” (SB 1082, Calderon, 1993). The Unified Program consolidated, coordinated, and made consistent the following six programs that aim to regulate hazardous materials and wastes, including the Aboveground Petroleum Storage Act (ASPA).
A local agency, such as a county or city, applies to CalEPA to become a Certified Unified Program Agency (CUPA), responsible for implementing the Unified Program within its jurisdiction. Under the unified program, CUPAs issue permits, perform inspections, levy fees, and take enforcement actions on facilities that store hazardous waste, and the implementation of the Unified Program must be consistent throughout each county. CUPAs may also adopt other requirements on facilities subject to the Unified Program as long as they are more stringent than the statewide requirements.
Currently, there are 83 CUPAs in California, including all 58 counties, which are required by state law to apply to be CUPAs. County environmental health departments frequently serve as CUPAs, but in other cases fire agencies or public safety departments may be the CUPA for a jurisdiction or participate in the administration of the Unified Program. CalEPA periodically reviews and evaluates individual CUPAs to determine how successfully they are implementing the Unified Program.
Aboveground Petroleum Storage Program. The APSA directs CUPAs to regulate facilities that store more than 1,320 gallons of petroleum in aggregate, stored in aboveground storage tanks with capacities of 55 gallons or greater. These facilities typically include large petroleum tank facilities, aboveground fuel tank stations and vehicle repair shops with aboveground petroleum storage tanks, but can also include farms or construction sites. AB 1566 (Wieckowski, 2012) tasked the Office of the State Fire Marshal with overseeing the CUPAs’ implementation of the APSA and required the State Fire Marshal to adopt regulations governing state oversight of APSA implementation.
All facilities subject to the APSA that store 10,000 gallons or more of petroleum must (1) be inspected at least once every three years by a CUPA, (2) report information about the tank facility to the CUPA, and (3) pay a fee to help cover the cost of the program. Facilities that store between 1,320 gallons and 10,000 gallons of petroleum must only meet the reporting and fee requirements. In addition, most facilities subject to the ASPA must prepare spill prevention control and countermeasure plans, but certain farms, logging sites, and construction sites are exempted. Federal regulations require the spill prevention plans to, among other things, describe the oil handling operations, spill prevention practices, discharge or drainage controls, and the personnel, equipment and resources at the facility that are used to prevent oil spills. Facility owners must also periodically inspect the tanks and connected pipes.
Standards for Aboveground Storage Tanks. Aboveground storage tanks must meet certain standards set out in state and local fire codes. Fire codes in California are typically developed and adopted according to the following process:
- A model fire code is developed by the National Fire Protection Association (NFPA).
- The State of California then adopts that model code, with any amendments specific to California, as the California Fire Code.
- Local agencies in California then enact an ordinance to adopt the California Fire Code. Those ordinances may include amendments that are more stringent than the California Fire Code, if the local governing body makes findings that the amendments are necessary because of local climatic, geological, or topographical conditions.
The California Fire Code requires the design, fabrication, and construction of tanks to conform to certain standards developed by the NFPA. These standards include provisions for different types of storage tanks, such as steel tanks without additional protections as well as “protected” steel tanks, which must meet a higher standard. Above-ground storage tanks must generally be protected tanks unless they hold less flammable motor oil. However, the California Fire Code includes some exemptions from these standards for tanks on farms.
Kern County. The Kern County Environmental Health Services Division is the CUPA in Kern County. The Kern County Fire Department also participates in implementing the APSA because it is responsible for issuing permits for storage tanks under the Kern County Fire Code. In 2013, following delegation of oversight responsibility for APSA to the Office of the State Fire Marshal, Kern County began rigorously enforcing the APSA and identifying tanks as not meeting the required standards in the Kern County Fire Code. These standards require farms to use protected tanks.
A 2016 evaluation of Kern County’s implementation of the Unified Program found that Kern County was not adequately ensuring that violators of the APSA had in fact returned to compliance by replacing tanks that did not meet standards. Accordingly, some tank owners have been told that they must remove their tanks. These owners are concerned that Kern County has been enforcing standards higher than state regulations without first adopting an ordinance.
Proposed Law
Senate Bill 1147 prohibits a city, county, or city and county from enforcing standards for aboveground storage tanks that are more stringent than state or federal standards unless it adopts an ordinance establishing those standards.
State Revenue Impact
No estimate
Comments
1. Purpose of the bill. Aboveground storage tanks are necessary to store fuel for agricultural equipment in an accessible manner. Yet recently, some tank owners in Kern County have been told that their tanks are in violation of county standards for tanks and that they must remove them. This removal must often be performed within 30 days of the notice of violation and represents a significant cost to landowners. Moreover, Kern County’s standards appear to exceed state standards that some tank owners would otherwise be in compliance with. SB 1147 requires local agencies to pass an ordinance prior to enforcing standards on aboveground storage tanks that are higher than statewide standards. This simple fix ensures that tank owners have adequate notice about the standards that they must meet and provides a mechanism for local governments to regulate aboveground storage tanks.
2. Sure, but will it work? SB 1147 arose out of concerns that Kern County was imposing a higher standard than state regulations for the storage of flammable liquids, which potentially results in costly replacements for tank owners. Accordingly, a previous version of the bill would have delayed the replacement of some storage tanks and statutorily defined statewide standards for tanks. The bill has since been amended to contain the current requirement to adopt an ordinance in order to enforce higher standards. However, this requirement appears to duplicate existing law, which already requires local agencies to adopt ordinances and make findings prior to increasing standards. Furthermore, the Kern County Fire Code was amended in 2013 to specify the standards that above-ground storage tanks must meet. Thus SB 1147 may not address the challenges facing tank owners who have been tagged as violating the APSA in Kern County. The Committee may wish to consider whether SB 1147 is necessary.
Support and Opposition
(4/28/16)
Support: California Cotton Growers and Ginners Association (co-sponsor); Wester Agricultural Processors Association (co-sponsor); California Fresh Fruit Association; Milk Producers Council.
Opposition: Unknown.
-- END --
SENATE COMMITTEE ON ENVIRONMENTAL QUALITY
Senator Wieckowski, Chair
2015 - 2016 Regular
Bill No: SB 1147
Author: | Galgiani | ||
Version: | 4/6/2016 | Hearing Date: | 4/20/2016 |
Urgency: | No | Fiscal: | No |
Consultant: | Rachel Machi Wagoner | ||
SUBJECT: Hazardous materials: aboveground storage tanks
ANALYSIS:
Existing federal law:
- Pursuant to the federal Spill Prevention Control and Countermeasure (SPCC) rule (40 CFR Part 112), requires owners and operators of tank facilities to prepare and implement an SPCC Plan which is enforceable by Certified Unified Program Agencies (CUPAs).
Existing California law:
- Under the Aboveground Petroleum Storage Act (APSA) (Health and Safety Code §25270 et seq.):
- Defines “aboveground storage tank” (AST) as a “tank that has the capacity to store 55 gallons or more of petroleum and that is substantially or totally above the ground,” except as specified.
- Defines “petroleum” as “crude oil, or a fraction thereof, that is liquid at 60 degrees Fahrenheit temperature and 14.7 pounds per square inch absolute pressure.”
- Defines “tank facility” as one or more ASTs, including any piping integral to the tanks, that contain petroleum and that are used by the owner or operator at a single location or site.
- Requires the Certified Unified Program Agencies (CUPAs) to implement APSA.
- Requires tank facilities with storage capacity between 1,320 gallons and 10,000 gallons to be subject to the requirements of APSA.
- Requires the owner or operator of an AST to prepare a spill prevention control and countermeasure plan, periodically inspect the AST, and allow the CUPA to inspect as well.
- Requires CUPAs to inspect tank facilities with a 10,000 gallon minimum total storage capacity at least once every three years.
- Requires the owner or operator to pay a fee to cover implementation costs of APSA.
- Authorizes the State Water Resources Control Board (SWRCB) and regional water quality control boards (RWQCBs) to oversee cleanup or abatement efforts of unauthorized releases from ASTs.
- Defines “aboveground storage tank” (AST) as a “tank that has the capacity to store 55 gallons or more of petroleum and that is substantially or totally above the ground,” except as specified.
- Requires the Department of Forestry and Fire Protection (CAL FIRE) – Office of the State Fire Marshal (OSFM) to adopt regulations and provide guidance and oversight to CUPAs implementing APSA.
- Allows money in the Waste Discharge Permit Fund to be used by a regional board to remedy a significant unforeseen water pollution problem and other specified actions.
- Authorizes CUPAs to assess administrative penalties on an owner or operator for failing to meet the requirements of APSA and provides that violations of specified APSA requirements are a misdemeanor.
- Allows local tank ordinances to be more stringent than state or federal requirements, but since SB 1147 would allow more stringent requirements with an approved ordinance, there does not appear to be a conflict of language.
This bill:
- Prohibits a city, county, or city and county from enforcing standards for aboveground storage tanks that are more stringent than state or federal standards for aboveground storage tanks unless the city, county, or city and county first adopts an ordinance establishing those standards.
Background
- APSA. APSA regulates facilities with aggregate aboveground petroleum storage capacities of 1,320 gallons or more, which include aboveground storage containers or tanks with petroleum storage capacities of 55 gallons or greater. These facilities typically include large petroleum tank facilities, aboveground fuel tank stations and vehicle repair shops with aboveground petroleum storage tanks.
APSA does not regulate non-petroleum products.
Facilities with total petroleum storage quantities at or above 10,000 gallons are inspected at least once every three years by a Certified Unified Program Agency and have reporting and fee requirements, while facilities with petroleum storage quantities equal to or greater than 1,320 gallons but less than 10,000 gallons have reporting and fee requirements only.
All regulated facilities must meet the federal SPCC rule requirements and must develop a spill prevention, control, and countermeasure plan that meets federal requirements.
APSA was established following a major spill event in Martinez, California in April 1988, during which an estimated 400,000 gallons of crude oil spilled into sensitive marshes, the Suisun Bay and the Bay Delta Estuary.
APSA required the Regional Water Quality Control Boards (regional boards) to oversee inspections of AST facilities to ensure that a federally mandated SPCC plan was in place, that tanks were not leaking, and that a monitoring program was undertaken, if necessary. It also required owners and operators of ASTs, which at the time was approximately 4,500 fee-paying AST facilities, to file a storage statement and submit a biennial registration fee to the State Water Resources Control Board (SWRCB). SWRCB was then required to use these fees to support the inspection program. The APSA also required CUPAs to enforce the requirements of the APSA regarding the SPCCs.
According to the SWRCB, in Fiscal Year 2002-03, due to the state’s fiscal crisis, the funding authority and positions for the AST inspection program were eliminated from SWRCB’s and regional boards’ budgets (Budget Act of 2002-03, Control Section 31.60). As a result, the SWRCB and the regional boards discontinued the AST inspection program. The owners and operators of AST facilities continued to pay the biennial fee into the Fund, which eventually obtained a balance of approximately $7.5 million.
AB 1130 (Laird, Chapter 626, Statutes of 2007) transferred the responsibility for the implementation, enforcement, and administration of the APSA from the SWRCB and regional boards to the CUPAs. In addition to other technical changes to the program, the bill deleted the existing fee structure and in its place authorized the CUPAs to collect a fee, beginning January 1, 2010, to cover reasonable and necessary program costs.
AB 1566 (Wieckowski, Chapter 532, Statutes of 2012) delegated state oversight responsibility to the OSFM effective January 1, 2013 and required regulations be adopted for state oversight of APSA implementation.
According to CAL FIRE, there are currently approximately 14,930 facilities regulated under the APSA requirement.
Comments
Purpose of Bill. According to the author, SB 1147 improves clarity and consistency to the regulation of aboveground storage tanks by providing a mechanism for cities and counties to regulate these tanks on the local level. The author states that recently, there have been concerns in Kern County where ASTs have been ‘red-tagged’ for being out-of-compliance with County standards. Statewide, ASTs are required to meet UL 142 (the Standard for Safety for Steel Aboveground Tanks for Flammable and Combustible Liquids as established by Underwriters Laboratories); however, Kern County has required tanks to meet more stringent standards and have done so without adopting a local ordinance. The author asserts that SB 1147 would maintain local regulation and resolve this issue by requiring cities and counties to adopt an ordinance prior to enforcing AST standards that are more stringent than state or federal AST standards.
DOUBLE REFERRAL:
If this measure is approved by the Senate Environmental Quality Committee, the do pass motion must include the action to re-refer the bill to the Senate Rules Committee.
SOURCE:
California Cotton Growers Association
California Cotton Ginners Association
Western Agricultural Processors Association
SUPPORT:
California Fresh Fruit Association
Milk Producers Council
OPPOSITION:
None received
-- END --